1. Catalogs
  2. Genvex
  3. ECO 400 2019

ECO 400 2019

ECO 400 2019
1 / 20 PagesView full catalog

ECO 400 2019

Product catalog summary
Installation Overview: The ECO 400 mechanical ventilation system requires precise installation for optimal performance. Key steps include mounting the unit with a slight incline towards the drain pipe, ensuring airtight traps, and protecting against freezing temperatures. Proper airflow alignment is crucial for maintaining air balance.
Scale Drawings and Dimensions: The unit is right-facing by default but can be reoriented. It should be placed on a stable base to prevent vibrations and allow for condensate drainage, with at least 600mm clearance for maintenance.
Duct Connection and System: Ducts are labeled for correct connection, using spiral pipes with rubber seals for durability and noise reduction. Sound-locks are recommended to minimize noise, and care should be taken to prevent air stream short-circuiting.
Condensate Outlet: The unit can produce up to 8 liters of condensate daily. Proper installation of the condensate outlet with an airtight trap is essential, with insulation to prevent freezing. A thermostat-controlled heating tape may be required in cold conditions.
Insulation of Ducts: In cold loft spaces, ducts should have at least 100mm insulation to minimize heat loss, while 50mm is recommended in heated spaces. Proper insulation prevents condensation damage and ensures efficient heat recovery.
Reheating of Supply Air: The supply air may be cooler than room temperature in winter. A water or electric reheating plate can be installed to adjust the temperature, with proper installation and sensor placement to prevent frost damage.
Electrical Installation: Must be performed by an authorized electrician, with connections varying depending on the control panel model (Optima 251 or Optima 260).
Inspection and Alignment: Before operation, ensure correct installation and insulation, clean filters, and proper condensate drainage. Initial valve settings are provided for supply and exhaust ducts, with final alignment requiring airflow measuring equipment.
Maintenance and Troubleshooting: Regular maintenance is essential for optimal performance. Troubleshooting guidance is provided for common issues such as airflow errors and alarms.
Installation and Alignment: The unit should be aligned by an authorized Genvex retailer. For assistance, contact Genvex at +45 7353 2700.
Maintenance Procedures:
  • Filters: Replace filters when the timer indicates, avoiding vacuuming or air pressure to maintain efficiency. Filter types include G4 (Coarse), F5 (Fine), and F7 (Pollen).
  • Condensate Drain: Check for blockages to prevent water damage.
  • Countercurrent Heat Exchanger: Inspect and clean annually.
  • Fans: Clean annually, ensuring balancing wheels are not removed.
  • Supply and Extract Valves: Clean with a damp cloth without altering air settings.
Service and Spare Parts: Service agreements are available through Genvex, with a list of spare parts provided for maintenance needs.
Troubleshooting:
  • Electrical Heater: Safety thermostats disconnect if temperatures exceed limits, requiring manual re-engagement.
  • System Not Running: Check for blown fuses, loose wires, or incorrect settings.
  • Condensed Water Leakage: Ensure the condensate outlet is clear and protected from freezing.
  • Air Faults: Issues may arise from faulty fans, clogged filters, or incorrect settings.
  • Cold Supply Air: Possible causes include clogged heat exchangers or disconnected reheaters.
Alarms: The system includes a filter timer alarm and communication error alerts. Frost protection errors are indicated if water reheater temperatures are too low.
Electrical Diagrams: Detailed diagrams for OPT251 and OPT260 systems are provided, outlining connections and components.
Declaration of Conformity: Available on the Genvex website.
Company Overview: Genvex, part of the NIBE Group, is a Danish company specializing in ventilation systems that improve indoor air quality and energy efficiency.
See more

Catalog excerpts

ECO 400 2019-1

ECO 400 Mechanical ventilation with passive heat recovery

 Open the catalog to page 1
ECO 400 2019-3

INSTALLATION IMPORTANT: Follow these instructions when you install ECO 400: 1) The machine must be mounted with an incline of 10-15mm towards the drain pipe, so that the condensed water can run freely into the outlet. 2) An airtight trap must be mounted in a frost-free place to compensate for the fan's pressure. 3) The trap height must be a minimum of 50mm. 4) It must be ensured that the drain pipe goes downwards all the way to the outlet. 5) Pour 1 litre of water into the machine's condensate tray to ensure that it runs away unobstructed. It must be checked that there is water in the trap every...

 Open the catalog to page 3
ECO 400 2019-4

ECO 400 is supplied as right-facing (as shown in the drawing below). If you wish to flip the orientation of the unit, you can remove the front cover and back plate, mount the back plate on the front and turn the unit 180° around. 1. Fresh air 2. Exhaust 3. Extract air The unit must be placed on a firm base so that vibrations from the unit do not reproduce down through the ceiling and walls, and also so that the condensate outlet and its required trap can be led frost-free to an internal drain, as the unit can release up to 8 litres of condensed water per day during wintertime. 4. Supply air 5....

 Open the catalog to page 4
ECO 400 2019-5

Duct connection Friskluft Incomming Air Frischluft Afkast Exhaust Air Fortluft A yellow label is affixed to all duct pipes, which indicates which ventilation ducts shall be connected to the different pipes. Supply air connected The duct system from the unit to the supply air in the living space. Exhaust air connected The duct system from the wet room to the unit. Fresh air connected The duct system from the fresh air hood/fresh air grate from outside or from the ground exchanger to the unit. Abluft Indblæsning Supply Air Return outlet connected The duct system from the unit to the exhaust hood/exhaust...

 Open the catalog to page 5
ECO 400 2019-6

Condensate drain Lack of water in trap = water damage The units produce up to 8 litres of condensed water every 24 hours. It is therefore essential that the condensate outlet is correctly installed and the unit has an incline in the direction of the condensate outlet. The trap must be airtight, e.g. by bending a 15mm copper pipe to form a water trap (see sketch on the left) between the drainpipe on the unit (1/2" connector) and the trap can either be led to a fixed PE pipe or an adapter can be used that goes from a ½" to a 15mm hose connector. Should a hose connector be used, then remember however...

 Open the catalog to page 6
ECO 400 2019-7

nnnnnnnnr nnnnnnnnnn/ Insulation of ducts in cold loft spaces If you wish to take advantage of the unit's high heat recovery rate (efficiency rate), it is essential that the ducts are insulated correctly. Genvex recommends the following: Supply and extract ducts In order to minimise heat loss from the duct system in cold loft spaces, the air intake ducts and exhaust ducts must be insulated with a minimum of 100mm insulation. If the alternative insulation type (A) is used, it is recommended that the insulation is carried out using 2 x 50mm slatted mats with paper or aluminium foil on the outside...

 Open the catalog to page 7
ECO 400 2019-8

Insulation of ducts in heated spaces Genvex recommends the following: Supply and extract ducts In a warm loft space, the supply and exhaust ducts must be insulated with 50mm insulation finished with aluminium foil. Supply and extract ducts that lead into heated rooms in the building should not be insulated unless cooling, bypass or ground heating exchanger is used. In this case, the supply duct should be insulated. Fresh air and return ducts In warm loft spaces and heated rooms in the building, fresh air and return ducts should be insulated with a minimum of 50mm insulation. In addition, the...

 Open the catalog to page 8
ECO 400 2019-9

Electrical installation The electrical connection must be carried out by an authorised electrician. See the electrical diagram supplied. The cable between the unit and the control panel is a 4-wire for Optima 251, maximum 50m and an 8-wire for Optima 260, maximum 10m. Inspection and alignment of the unit In order to achieve optimal operation of the unit, it must be aligned using airflow measuring equipment. If there is a wish to run the unit prior to alignment, you can do the following before running the unit: 1. Check that the Genvex unit is mounted correctly and that all the ducts are properly...

 Open the catalog to page 9
ECO 400 2019-10

/ □□□□□□□□□ □□□□□□□□□ □□□□□□□□□ □□□□□□□□□ □□□□□□□□□ □□□□□□□□□ □□□□□□□□□J Optimal alignment of the unit In order to align a Genvex home ventilation unit, a calibrated airflow measuring device must be used. Before carrying out alignment, check that the 6 points in the section "Inspection and alignment of the unit" have been carried out. The unit can then be put into operation. It is recommended that the unit is aligned by an authorised Genvex retailer. If needed, contact Genvex on +45 7353 2700. Maintenance of the unit with control via Optima design display (combined with Optima 251 controls) A...

 Open the catalog to page 10
ECO 400 2019-11

Condensate drain In connection with the autumn filter change, the condensate outlet should be checked for blockages of dirt, and if there is water in the trap. Pour 1 litre of water into the condensate tray and see whether it runs away unobstructed. If the condensate outlet is not working, this may lead to water damage in the building. Countercurrent heat exchanger The countercurrent heat exchanger should be inspected annually. If it is dirty, take it out and wash in warm, soapy water and if necessary, flush well in a bathroom, using a hand shower. Fans Remember to turn off the power. 50 100...

 Open the catalog to page 11
ECO 400 2019-13

Safety thermostat in electrical heater (optional equipment) If an error occurs on an electrical heater, the safety thermostat will disconnect. The heater is equipped with a fire thermostat that automatically cuts off the power supply, if the temperature exceeds 50 °C. If the temperature decreases, the heater automatically re-engages. As an additional security there is a built-in thermal cutout, which disengages if the temperature exceeds 100 °C. Re-engaging must be done manually. Does not apply to PTC electrical heaters. The system is not running Unit stopped Possible error • Fuse in main board...

 Open the catalog to page 13

All Genvex catalogs and technical brochures

  1. COMBI 185 BP

    6  Pages

  2. ECO 400 2022

    6  Pages

  3. ECO 375

    6  Pages

  4. ECO 360 R

    6  Pages

  5. ECO 275

    6  Pages

  6. ECO 190 XL

    6  Pages

  7. GES Energy M

    3  Pages

  8. GE Energy 2

    3  Pages

  9. GE Energy 3

    3  Pages

  10. GE Premium 3

    4  Pages

  11. Vanvex R

    3  Pages

  12. Vanvex RS

    3  Pages

  13. GS-4

    3  Pages

  14. GE Premium 2

    4  Pages

  15. GE Energy 1

    3  Pages

  16. GES Energy S

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.