Application
LEO fan heaters are designed for large volume buildings like industrial and public spaces. They function by heating air through a heat exchanger filled with hot water. The casing is made from expanded polypropylene (EPP), with options in powder-coated steel (ST) or austenitic stainless steel (INOX). These heaters are for indoor use where air dustiness is below 0.3 g/m3 and should not be used in corrosive environments or those containing oil mist. The heat exchanger can use water or a glycol solution up to 60%, and the medium should not corrode copper tubes.
Technical Data
The document details specifications for LEO heaters, including airflow rates, power supply, consumption, insulation class, acoustic levels, and operational ranges. For instance, the LEO S1 model has a maximum airflow of 2300 m3/h and consumes 120 W. The maximum heating water temperature is 120°C for standard models and 130°C for INOX/ST versions, with a maximum operating pressure of 1.6 MPa. These devices are suitable for indoor environments with a maximum working temperature of 60°C.
Installation
Installation instructions cover mounting brackets, assembly, and U-profiles. Proper installation is essential for efficient heater operation.
Connection Diagrams
Diagrams are provided for connecting heaters to the building's heating system, ensuring proper integration and functionality.
Start-Up and Operation
Guidelines for starting and operating the heaters ensure safe and efficient use, including checking connections, ensuring proper water flow, and monitoring performance.
Service and Warranty Terms
Details on servicing the heaters and warranty terms are provided to ensure long-term reliability and customer satisfaction.
Conformity with WEEE Directive 2012/19/UE
The heaters comply with the WEEE directive, concerning the disposal and recycling of electronic equipment.
Technical Specifications
- Maximum heating water temperature: 120°C (INOX/ST: 130°C)
- Maximum operating pressure: 1.6 MPa
- Connection size: 3/4”
- Installation environment: Indoor
- Maximum working temperature: 60°C
- Device mass: 14.9 kg (INOX: 19.4 kg, ST: 19.4 kg)
- Mass of device filled with water: 15.9 kg (INOX: 20.4 kg, ST: 20.4 kg)
- Acoustic pressure level measured at 5m in a 1500m³ space
- Horizontal isothermal range for 0.5 m/s air stream speed
- Vertical nonisothermal range for ΔT = 5°C and 0.5 m/s air stream speed
Technical Data for LEO XL2 and XL3
- Max airflow: LEO XL2: 5800 m³/h, LEO XL3: 5300 m³/h
- Power supply: 230V/50Hz
- Max current consumption: LEO XL2: 2.3 A, LEO XL3: 2.4 A
- Max power consumption: LEO XL2: 520 W, LEO XL3: 550 W
- IP/Insulation class: 54/F
- Max acoustic pressure level: 67.5 dB(A)
- Horizontal range: LEO XL2: 26.0 m, LEO XL3: 23.5 m
- Vertical range: LEO XL2: 8.5 m, LEO XL3: 7.7 m
Installation Guidelines
- Fan heaters can be mounted to vertical or horizontal partitions in any position.
- Maintain minimal distances from walls and ceiling during installation.
- Use M8 screws provided with the bracket.
- U-profiles should be mounted in corners as shown in the diagram.
Connection Diagrams
- Up to 31 DRV modules can be connected and controlled with one T-box controller.
- DRV modules can be connected to the Building Management System (BMS).
- Connection must be carried out with a 3-wire cable (recommended UTP) to connectors DRV IN.
Start-Up and Operation
- Use flexible hoses on water exchanger connections.
- Install vent valves at the highest point of the system.
- Protect the system against pressure increase above 1.6 MPa.
- Check connections and system tightness before starting.
- Device operation is intended for temperatures above 0°C.
- Periodic inspections are recommended every 6 months.
See more

Catalog excerpts

LEO-1

FAN HEATER TECHNICAL DOCUMENTATION OPERATION MANUAL NAGRZEWNICA WODNA DOKUMENTACJA TECHNICZNA INSTRUKCJA UŻYTKOWANIA LUCHTVERWARMER TECHNISCHE DOCUMENTATIE GEBRUIKSAANWIJZING

 Open the catalog to page 1
LEO-4

LEO heaters make up a decentralised heating system. The air streaming through the heat exchanger filled with hot water is warmed up. Fan heaters are used for heating large volume buildings: general, industrial and public buildings etc. The casing of LEO heaters is made from extended polypropylene EPP. LEO in special version ST has a casing made from powder coated steel. The devices LEO in special version INOX have casing and air blades made of austenitic stainless steel. The devices are designed for indoor use where maximum air dustiness does not exceed 0,3 g/m3. Units are built using copper,...

 Open the catalog to page 4
LEO-5

De LEO-luchtverwarmers vormen een gedecentraliseerd verwarmingssysteem. De lucht stroomt langs de met heet water gevulde warmtewisselaar en wordt opgewarmd. Luchtverwarmers worden gebruikt voor het verwarmen van grote volumes in gebouwen: algemene, industriële en openbare gebouwen enzovoort. De units zijn ontworpen voor binnengebruik in een omgeving met een stofbelasting lager dan 0,3 g/m3. Отопительные аппараты LEO составляют децентрализованную систему отопления. Их работа основана на протекании горячей воды через теплообменник, который отдает тепло струе нагнетаемого воздуха. Предназначены...

 Open the catalog to page 5
LEO-6

LEO S1 INOX / ST | S2 INOX / ST | S3 INOX / ST LEO S1 Gear | Bieg | Stand | Cкорость Max airflow [m /h ] | Max. strumień przepływu powietrza [m3/h ] | Max. luchtdebiet [m3/uur] | Макс. объем воздуха [м3/ч] Power supply [V/Hz] | Zasilanie [V/Hz] | Stroomvoorziening [V/Hz] | Питание [В/Гц] Max current consumption [A] | Max. pobór prądu [A] | Max. stroomverbruik [A] | Макс. потребление тока [A] Max power consumption [W] | Mak. pobór mocy [W] | Max. energieverbruik [W] |Макс. расход мощности [Вт] IP/ Insulation class | IP/Klasa izolacji | IP/Isolatieklasse | IP/Класс изоляции Max acoustic pressure...

 Open the catalog to page 6
LEO-7

LEO L1 INOX / ST | L2 INOX / ST | L3 INOX / ST Gear | Bieg | Stand | Cкорость Max airflow [m /h ] | Max. strumień przepływu powietrza [m3/h ] | Max. luchtdebiet [m3/uur] | Макс. объем воздуха [м3/ч] Power supply [V/Hz] | Zasilanie [V/Hz] | Stroomvoorziening [V/Hz] | Питание [В/Гц] Max current consumption [A] | Max. pobór prądu [A] | Max. stroomverbruik [A] | Макс. потребление тока [A] Max power consumption [W] | Mak. pobór mocy [W] | Max. energieverbruik [W] |Макс. расход мощности [Вт] IP/ Insulation class | IP/Klasa izolacji | IP/Isolatieklasse | IP/Класс изоляции Max acoustic pressure level...

 Open the catalog to page 7
LEO-8

Gear | Bieg | Stand | Cкорость Max airflow [m /h ] | Max. strumień przepływu powietrza [m /h ] | Max. luchtdebiet [m3/uur] | Макс. объем воздуха [м3/ч] 3 Power supply [V/Hz] | Zasilanie [V/Hz] | Stroomvoorziening [V/Hz] | Питание [В/Гц] Max current consumption [A] | Max. pobór prądu [A] | Max. stroomverbruik [A] | Макс. потребление тока [A] Max power consumption [W] | Mak. pobór mocy [W] | Max. energieverbruik [W] | Макс. расход мощности [Вт] IP/ Insulation class | IP/Klasa izolacji | IP/Isolatieklasse | IP/Класс изоляции Max acoustic pressure level [dB(A)]* | Max. poziom ciśnienia akustycznego...

 Open the catalog to page 8
LEO-9

Fan heaters can be mounted to vertical or horizontal partitions in any position. During the montage, the minimal distances from the walls and ceiling have to be kept. Luchtverwarmers kunnen in elke positie bevestigd worden aan verticale en horizontale delen. Tijdens montage moet de minimumafstand tussen de muren en het plafond bewaard worden. Nagrzewnice mog^ bye montowane do przegrod pionowych i poziomych w dowolnej pozycji. Podczas montazu nalezy zachowac zalecane odlegtosci od przegrod. Bo3gyxoHarpeBaTe^M mowho ycTaHaBnuBaTb Ha BepTUKanbHbix unu ropM30HTa^bHwxneperopoflKa x. Bo BpeMA ycTaHOBKu...

 Open the catalog to page 9
LEO-10

4. CONNECTION DIAGRAMS 4. AANSLUITSCHEMA'S 4. SCHEMATY PODL^CZEN 4. CXEMbl nOflKnWMEHMfl SUMII Continious mode | Tryb ciqgty | Dauerbetrieb | flOCTOflHHbIM pe>KMM Wires size and type should be chosen by the designer ! Przekroj i typ przewodow powimen zostac dobrany przez projektanta.| Kabeldiameters en uitvoenng moet worden berekend door een elektrotechmsch engineer.! Thermostatic mode | Tryb termostatyczny | Thermostatischer Betrieb | CeHeHne m Tun npoBOflOB flonweH 6brrb nofloopaH npoexTupoBU^MKOM Wires size and type should be chosen by the designer. | Przekroj i typ przewodow powinien zostac...

 Open the catalog to page 10
LEO-11

Dławnice/Glands/Wartels/ Кабельные вводы (зажим) Wires size and type should be chosen by the designer.| Przekrój i typ przewodów powinien zostać dobrany przez projektanta.| Kabeldiameters en uitvoering moet worden berekend door een elektrotechnisch engineer.| Сечение и тип проводов должен быть подобран проектировщиком. EN: When connecting DRV modules to the T-box controller or BMS, you have to binary set addresses on each (each DRV must have individual address) DRV module by DIP-switch SW1. To address modules check if the power supply is turned off, than set then the addresses as shown in the...

 Open the catalog to page 11
LEO-12

EN: It is possible to connect up to 31 modules DRV and control them with one T-box controller .| PL: Możliwe jest łączenie do 31 modułów DRV. Umożliwia to obsługę do 31 urządzeń kompatybilnych z Systemem FLOWAIR, za pomocą jednego sterownika T-box.| NL: Het is mogelijk om tot 31 DRV-modules met elkaar te verbinden en deze te regelen met behulp van T-Box regeling . | RU: Можно соединить максимально 31 модулей DRV. Это позволяет управлять до 31 аппарата, совместимым с Системой FLOWAIR с помощью одного командоконтроллера T-box. EN: DRV modules can be connected to the BMS (Building Management System)....

 Open the catalog to page 12
LEO-13

Guidelines for System Connection ■ It is recommended to use flexible hoses on the water exchanger connections. ■ It is recommended to install vent valves at the highest point of the system. ■ The system should be executed so that, in the case of a failure, it is possible to disassemble the device. For this purpose it is best to use shut-off valves just by the device. ■ The system with the heating medium must be protected against an increase of the heating medium pressure above the permissible value (1.6 MPa). ■ While screwing exchanger to pipeline - connecting stubs has to be hold by wrench....

 Open the catalog to page 13

All Flowair catalogs and technical brochures

  1. FAN HEATERS LEO

    28  Pages

  2. ELIS DUO

    16  Pages

  3. LED AGRO

    16  Pages

  4. ELIS T

    24  Pages

  5. LEO FS

    36  Pages

  6. LEO FL

    24  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.