PTI_DucoGrille_Close_105_en
28Pages

{{requestButtons}}

Catalog excerpts

PTI_DucoGrille_Close_105_en - 1

Fitting Instructions 1.1 Dimensions 1.2 Orientation 1.3 Actuator side 1.4 Wiring diagram – Belimo NM24A 1.5 Wiring diagram – Belimo NM230A 1.6 Wiring diagram – Belimo NM24A-SR 1.7 Wiring diagram – Belimo NM230ASR 1.8 Wiring diagram – Belimo NF24A 1.9 Wiring diagram – Belimo NFA 1.10 Wiring diagram – Belimo NF24A-SR 2. 2.1 In structural opening 2.2 In curtain wall – preparation 2.3 In curtain wall > 125mm 2.4 In curtain wall < 125mm 2.5 Duco Acoustic Module 150 3. Replacing actuator on side Replacing actuator

Open the catalog to page 1
PTI_DucoGrille_Close_105_en - 2

General CONTENT 1.1 Dimensions 1.2 Orientation 1.3 Actuator side 1.4 Wiring diagram – Belimo NM24A 1.5 Wiring diagram – Belimo NM230A 1.6 Wiring diagram – Belimo NM24A-SR 1.7 Wiring diagram – Belimo NM230ASR 1.8 Wiring diagram – Belimo NF24A 1.9 Wiring diagram – Belimo NFA 1.10 Wiring diagram – Belimo NF24A-SR

Open the catalog to page 2
PTI_DucoGrille_Close_105_en - 3

The DucoGrille Close 105 is available in a range of dimensions: - Width : Ranging from 258 to 3000mm - Height : Ranging from 258 to 3000mm Attention: For maximum dimensions, consider the figure below.. Opening width Opening height Opening size width: width DGC 105 + 2 x clearance 5mm Opening size height: height DGC 105 + 2 x clearance 5mm Clearance 5mm DucoGrille Close 105 weighs 16kg/m². (for other dimensions, you can extrapolate)

Open the catalog to page 3
PTI_DucoGrille_Close_105_en - 4

No spring return actuator possible Side actuator Centered actuator Depending on the width and height ratio, the unit will be equipped with horizontal or vertical blades. This way, the highest permeability efficiency is always achieved.

Open the catalog to page 4
PTI_DucoGrille_Close_105_en - 5

Actuator side Ventilation & Sun Control The DucoGriUe Close 105 can be supplied with or without actuator control. It is good practice to point the actuator with its open side to the inside of the building (for easy service access). If installation conditions do not allow to route a cable along the inside of the DucoGrille Close 105, the fitter may want to drill a cable passage in the side edge of the frame. In such a case, install a cable gland to provide splice protection and to eliminate unwanted air leakage. The DucoGrille Close 105 can be rotated 180° to turn the actuator side from left...

Open the catalog to page 5
PTI_DucoGrille_Close_105_en - 6

Wiring diagram - Belimo NM24A Electrical data Nominal voltageAC/DC 24 V Nominal voltage frequency50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation 1.5 W Power consumption in rest position 0.2 W Power consumption for wire sizing 3.5 VA Connection supply / control Cable 1 m, 3 x 0.75 mm2 Parallel operationYes (note the performance data) Electrical installation A Notes • Connection via safety isolating transformer. • Parallel connection of other actuators possible. Observe the performance data. Cable colours: 1 = black 2= red 3 = white Wiring...

Open the catalog to page 6
PTI_DucoGrille_Close_105_en - 7

Wiring diagram - Belimo NM230A Electrical data Nominal voltage AC 230 V Nominal voltage frequency50/60 Hz Nominal voltage rangeAC 85...264 V Power consumption in operation 2.5 W Power consumption in rest position 0.6 W Power consumption for wire sizing 5.5 VA Connection supply / control Cable 1 m, 3 x 0.75 mm2 Parallel operationYes (note the performance data) Electrical installation A Notes • Caution: Power supply voltage! • Parallel connection of other actuators possible. Observe the performance data. Cable colours: 1 = blue 2 = brown 3 = white Caution : Ensure that the blades are always...

Open the catalog to page 7
PTI_DucoGrille_Close_105_en - 8

Wiring diagram - Belimo NM24A-SR Ventilation & Sun Control Electrical data Nominal voltageAC/DC 24 V Nominal voltage frequency50/60 Hz Nominal voltage rangeAC 19.2...28.8 V / DC 19.2...28.8 V Power consumption in operation2 W Power consumption in rest position0.4 W Power consumption tor wire sizing4 VA Connection supply / control Cable 1 m, 4 x 0.75 mm2 Parallel operationYes (note the performance data) Electrical installation A Notes • Connection via safety isolating transformer. • Parallel connection of other actuators possible. Observe the performance data. Wiring diagrams Cable colours:...

Open the catalog to page 8
PTI_DucoGrille_Close_105_en - 9

Electrical data Nominal voltage Nominal voltage frequency Nominal voltage range Power consumption in operation Power consumption in rest position Power consumption for wire sizing Connection supply Connection control Parallel operation Yes (note the performance data) Electrical installation Notes • Caution: Power supply voltage! • Parallel connection of other actuators possible. Observe the performance data. Wiring diagrams Cable colours: 1 = blue 2 = brown 1 = black 2 = red 3 = white 5 = orange Caution : Ensure that the blades are always spaced minimum 6mm apart from one another (20...

Open the catalog to page 9
PTI_DucoGrille_Close_105_en - 10

Wiring diagram - Belimo NF24A Ventilation & Sun Control Electrical data Nominal voltageAC/DC 24 V Nominal voltage frequency50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6.. 28.8 V Power consumption in operation 6 W Power consumption in rest position 2.5 W Power consumption for wire sizing 8.5 VA Connection supply / controlCable 1 m, 2 x 0.75 mm2 Parallel operationYes (note the performance data) Connection via safety isolating transformer. Parallel connection of other actuators possible. Observe the performance data Wiring diagrams AC/DC 24 V, open-close I ~ - + C~D -- Cable...

Open the catalog to page 10
PTI_DucoGrille_Close_105_en - 11

Wiring diagram - Belimo NFA Ventilation & Sun Control Electrical data Nominal voltage AC 24...240 V / DC 24...125 V Nominal voltage frequency50/60 Hz Nominal voltage rangeAC 19.2...264 V / DC 21.6-137.5 V Power consumption in operation 6 W Power consumption in rest position 2.5 W Power consumption for wire sizing 9.5 VA Connection supply / controlCable 1 m, 2 x 0.75 mmg Parallel operationYes (note the performance data) Electrical installation A Notes • Caution: Power supply voltage! • Parallel connection of other actuators possible. Observe the performance data. Wiring diagrams

Open the catalog to page 11
PTI_DucoGrille_Close_105_en - 12

Wiring diagram - Belimo NF24A-SR Ventilation Electrical data Nominal voltageAC/DC 24 V Nominal voltage frequency50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 3.5 W Power consumption in rest position 2.5 W Power consumption for wire sizing 5.5 VA Connection supply / controlCable 1 m, 4 x 0.75 mm2 Parallel operationYes (note the performance data) Electrical installation Wiring diagrams AC/DC 24 V, modulating I ~ - + rY^-DC (0)2...10V rU-12- DC 2.. ,10V Cable colours 1 = black 2 = red 3 = white 5 = orange Caution : Ensure that the blades are...

Open the catalog to page 12

All Duco catalogs and technical brochures

  1. MVHR SYSTEMS

    56 Pages