ALEZIO S
32Pages

{{requestButtons}}

Catalog excerpts

ALEZIO S - 1

ALEZIO S REVERSIBLE AIR-TO-WATER ˝SPLIT INVERTER˝ HEAT PUMPS • ALEZIO S/E from 4.6 to 14.6 kW with electrical backup via integrated immersion heater • ALEZIO S/E V200 from 4.6 to 14.6 kW with 180-litre DHW tank built into the indoor module and electrical backup via immersion heater • ALEZIO S/H from 4.6 to 14.6 kW with (or without) hydraulic backup via boiler • ALEZIO S/H V200 from 4.6 to 14.6 kW with 180-litre DHW tank built into the indoor module with (or without) hydraulic backup via boiler ALEZIO S/E, ALEZIO S/E V200 (with electrical backup): heating and cooling with underfloor heating/refreshing S V200 model including DHW tank. ALEZIO S/H and ALEZIO S/H V200 (with hydraulic backup): heating and cooling with underfloor heating/refreshing S V200 model including DHW tank. ALEZIO S/E V200 (with electrical backup) and ALEZIO S/H V200 (with hydraulic backup): for heating and cooling using fan coil units. Free, natural and renewable energy Electricity (power supplied to the compressor) Compatible room thermostat SMART TC° Air-to-water heat pump OPERATING CONDITIONS operating temperature limits in heating mode Outside air: - 20/+ 35°C (- 15°C with AWHP 4.5 and 6 MR) Water: + 18/+ 60°C (+ 55°C for 4.5 kW) in "cooling" mode Outside air: +7/+ 46°C Water: + 18/+ 25°C in air conditionning mode (only for Alezio SV200 models) Outside air: + 7/+ 46°C Water: + 7/+ 25°C Heating circuit Max. operating pressure: 3 bar Max. operating temp.: 95°C ALEZIO S and S V200 heat pumps stand out for their high performance: COP from 4.22 to 5.11 at an outside temperature of + 7°C (EER of 3.96 to 4.75 at an outside temperature of + 35°C). A high-tech product equipped with an INVERTER system with power accumulator. ALEZIO S heat pumps offer greater stability in the temperature setpoint, a significant reduction in energy consumption and quiet operation. ALEZIO S heat pumps offer complete comfort all year round thanks to their reversible design and their capacity for cooling (underfloor cooling type, water at + 18°C), or air conditionning using fan coil units (water at + 7°C) for Alezio S and Alezio S V200 models. These heat pumps are suitable for integration in new builds and renovation projects alike thanks to their compact construction, advanced design and ease of installation. ALEZIO S V200 models are used for domestic hot water management. As standard, ALEZIO S V200 models have a built-in DHW storage tank with a 180-litre capacity in the indoor module, forming a beautifully designed uniform column. DHW circuit (ALEZIO S V200) Max. operating pressure: 10 bar Max. operating temp.: 65°C

Open the catalog to page 1
ALEZIO S - 2

PRESENTATION OF THE RANGE ALEZIO S heat pumps comprise an outdoor module and a MIV-S wall-mounted indoor module in the case of the ALEZIO S, and a MIV-S V200 module fitted with a 180-litre domestic hot water tank in the case of the ALEZIO S V200. AWHP OUTDOOR MODULE TECHNICAL DATA The AWHP 4.5 MR to 16 TR outdoor modules are used in our current split air-to-water ranges. The outdoor module comprises: • a modulating compressor, an aluminium fin heat exchanger • 1 to 2 axial fan(s) (depending on the model) • a liquid separator and power reserve • a 4-way reversal valve • a HP pressure switch...

Open the catalog to page 2
ALEZIO S - 3

MODELS AVAILABLE ALEZIO S MODELS EASYLIFE A++ FOR RADIATOR HEATING OR HEATING AND COOLING WITH UNDERFLOOR HEATING/COOLING BACKUP VIA INTEGRATED IMMERSION HEATER 2, 4 OR 6 KW 6 OR 9 KW SINGLE-PHASE THREE-PHASE Heat pump with electrical backup for heating using radiators and cooling with underfloor heating/cooling. (1) Water flow temp.: + 35°C, outside temp.: + 7°C. (2) Water flow temp.: + 18°C, outside temp.: + 35°C EASYLIFE A++ FOR RADIATOR HEATING OR HEATING AND COOLING WITH UNDERFLOOR HEATING/COOLING WITH (OR WITHOUT) HYDRAULIC BACKUP VIA BOILER ALEZIO S 6 MR/H Heat pump with hydraulic...

Open the catalog to page 3
ALEZIO S - 4

MODELS AVAILABLE ALEZIO S V200 MODELS EASYLIFE A++ A INTEGRATED IMMERSION HEATER Heat pump with electrical backup for heating using radiators and cooling with underfloor heating/ cooling or air conditioning with fan coil units. (1) Water flow temp.: + 35°C, outside temp.: + 7°C. (2) Water flow temp.: + 18°C, outside temp.: + 35°C EASYLIFE A++ A WITH (OR WITHOUT) HYDRAULIC BACKUP VIA BOILER Heat pump with hydraulic backup via boiler for radiator heating and cooling with underfloor heating/cooling or air conditioning with fan coil units. (1) Water flow temp.: + 35°C, outside temp.: + 7°C. (2)...

Open the catalog to page 4
ALEZIO S - 5

MODELS AVAILABLE The reference scale is given below for heating and DHW indicating the product's energy performance to be included on the corresponding energy label. •• Energy Label Echelle Système Chauffage+ECS 2020 REFERENCE SCALE FOR THE SYSTEM ENERGY LABEL ENERGY LABELLING The ALEZIO S heat pump is supplied with an energy label, which contains a large amount of information: energy efficiency, annual energy consumption, name of manufacturer, noise level, etc. By combining your heat pump with, for example, a solar system, a DHW storage tank, a control system or even another generator, you...

Open the catalog to page 5
ALEZIO S - 6

TECHNICAL SPECIFICATIONS Backup via immersion heater MIV-S/E INDOOR MODULE SPECIFICATIONS MAIN DIMENSIONS (mm AND INCHES) MIV-S/E 400 KEY ቢ Heating return Ø G 1" ባ Heating flow Ø G 1" ቦ Gas refrigeration connection: 5/8” flare ቧ Liquid refrigeration connection: 3/8” flare COMPONENTS MIV-S/EM AND MIV-S/ET 8-litre expansion vessel Safety valve Flowmeter High efficiency heating pump with EEI < 0.23 MODEL SHOWN: MIV-S/E with front panel removed. E Electronic board F Decoupling cylinder G Electrical resistance : • from 2 to 6 kW for MIV-S/EM • from 3 to 9

Open the catalog to page 6
ALEZIO S - 7

TECHNICAL SPECIFICATIONS ALEZIO S/E TECHNICAL SPECIFICATIONS OPERATING TEMP. LIMIT In heating mode: • Water: + 18°C/+ 60°C (+55°C for 4.5-kW model), • Outside air: - 20°C/+ 35°C (- 15°C for 4.5- and 6-kW models) In cooling mode: • Water: + 18°C/+ 25°C, • Outside air: +7°C/+ 46°C MODEL ALEZIO S Heat output at + 7°C/+ 35°C (1) Heating COP at + 7°C/+ 35°C (1) Heat output at – 7°C/+ 35°C (1) Heating COP at – 7°C/+ 35°C (1) Absorbed electrical power at + 7°C/+ 35°C (1) Nominal amperage at +7 °C/+35 °C (1) Heating seasonal energy efficiency* at 35°C/55°C (without control system) Heating seasonal...

Open the catalog to page 7