Introduction
This document outlines smoke control systems in multi-storey residential buildings, emphasizing legislative frameworks and design strategies. It underscores the critical role of smoke control in ensuring safe evacuation and facilitating fire-fighting operations.
Design Approaches
Smoke control system design varies with building layout, including options like openable ventilators, automatically opening ventilators, ventilation shafts, and pressurisation systems. These systems aim to keep escape routes clear and protect fire-fighting cores.
Legislation and Standards
Smoke control requirements are based on the Building Regulations for England and Wales (2000) and detailed in Approved Document B (ADB) 2006. Buildings over 18m or with deep basements require a fire-fighting core with a lift, adhering to BS 5588-5: 2004 standards.
Means of Escape
ADB mandates ventilation in corridors or lobbies leading to staircases to prevent smoke ingress. Small buildings under 11m can use a stairwell ventilator, while larger buildings need additional measures like AOVs or shaft systems.
Smoke Control for Fire-Fighting Cores
Fire-fighting cores must ensure smoke-free access, including a protected staircase, lobby, and lift. Systems like the BRE shaft or Colt shaft maintain clear conditions.
The Colt Shaft
The Colt shaft is a mechanical system offering performance similar to the BRE shaft but requires less space, using variable speed extract fans for efficient pressure and smoke management.
Ventilator Performance
The Kameleon ventilator is designed for smoke and heat ventilation, excelling in U value, air permeability, and weather resistance. It is CE marked and manufactured to ISO 9000 standards.
Conclusion
Colt provides comprehensive smoke control solutions, including design, supply, and installation, ensuring compliance with safety standards and enhancing building design flexibility.
Product Overview
The document details specifications and applications for various ventilation and smoke control systems, such as the Kameleon ventilator, EN Stairwell Ventilator, Defender Smoke & Fire Dampers, and Doorman Smoke Door Actuator, all designed to enhance safety through natural ventilation and smoke extraction.
Specifications
  • Kameleon Ventilator: Available in various finishes, designed for 90° installation, with dimensions from 400mm to 2000mm, featuring a concealed control mechanism and a 50° opening angle.
  • EN Stairwell Ventilator: A low-profile, louvred ventilator for heat and smoke exhaust, suitable for vertical or horizontal installation, compliant with BS 5588 and EN 12101-2 standards.
  • Defender Smoke & Fire Dampers: Motorised dampers for smoke control in HVAC systems, with robust construction and various sizes and control options.
  • Doorman Smoke Door Actuator: Controls door movement in smoke control schemes, ensuring doors remain locked when not in use but open during emergencies.
Installation and Operation
  • Ventilators and dampers are designed for easy installation and operation, with manual and automatic control options.
  • Pressurisation systems maintain pressure differentials to prevent smoke ingress, using components like inlet fans, ductwork, and pressure relief dampers.
Certification and Compliance
  • Products are CE marked and comply with standards such as EN 12101-2 and BS 476 Part 20.
  • Regular maintenance is recommended to ensure system effectiveness, with services provided by Colt Service.
Features and Benefits
  • Robust construction and high free area for effective smoke control.
  • Wide range of optional extras and finishes to suit various architectural requirements.
  • Comprehensive maintenance packages and emergency cover provided by Colt Service.
Overview of Services
Colt International Limited offers comprehensive services in designing and implementing Smoke and Heat Exhaust Ventilation Systems (SHEVS), including scheme design, project management, supply, installation, commissioning, and maintenance, ensuring system compatibility.
Post-Installation Services
Approximately nine months post-installation, Colt conducts a free full system check to ensure proper operation and offers further training for local personnel if needed. Defective parts are replaced at no cost within the warranty period, and a test certificate is issued.
Company Information
Colt International Limited, based in Havant, Hampshire, specializes in architectural solutions, climate control, smoke control, and service and maintenance, and can be contacted via phone, fax, or email.
See more

Catalog excerpts

SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-1

CI/SfB Classification Smoke Control in Apartments and Fire Fighting Shafts Smoke Control

 Open the catalog to page 1
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-2

Front Cover:The Centrium,Woking. Developer: Barratt Homes. Colt Doorman actuators installed into smoke shafts with Colt Seefire ventilators at the top of the shafts. INTRODUCTION This brochure is intended to provide an understanding of how smoke control systems can protect multi-storey residential buildings and what the legislative framework is. Why provide smoke control in apartment buildings? I In multi-storey apartment buildings, the main escape route is always via common corridors and/or lobbies to protected stairs. I Smoke can easily spread from the accommodation, and if a door is simply...

 Open the catalog to page 2
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-3

1 The Postbox Apartments, Birmingham. Window actuators, smoke dampers, stairwell ventilators, car park ventilation. 2 The Centrium,Woking. (as above). 3 Castlegate House, Manchester. Doorman door actuators, stairwell ventilators. 4 The Centrium,Woking. (as above). 5 Bridgewater Place, Manchester. Doorman door actuators, stairwell ventilators. 6 Mount Pleasant, Liverpool. Window actuators, stairwell ventilators. 7 Hardy’s Development, Manchester Doorman door actuators, stairwell ventilators.

 Open the catalog to page 3
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-4

Smoke Control for Means of Escape (MOE) in apartment buildings MEANS OF ESCAPE Small single stair buildings If the building is under 11m high, has no more than 3 storeys and the staircase does not connect to a covered car park, then only a stairwell ventilator is required, provided that the escape distances are limited to 4.5m in the corridor. If the corridor is also ventilated, then escape distances can be extended up to 7.5m. direction and 30m if escape is in two directions, and any corridor or lobby that opens onto a staircase should be ventilated. All other apartment buildings In all other...

 Open the catalog to page 4
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-5

OPERATION If natural ventilation is used, ADB recommends that the shaft: I Should be vertical with no more than 4m at an inclined angle (max 30°). I Is closed at the base I Has a minimum cross-sectional area of 1.5m2 with a minimum dimension of 0.85m in either direction I Extends at least 0.5m above the highest structure within 2m I Extends 2.5m above the ceiling of the highest level served by the shaft I Should be constructed from noncombustible material and the vents to be equivalent to an E30S fire door The vent into the shaft, the vent at the top of the shaft and any safety grilles in the...

 Open the catalog to page 5
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-6

Smoke Control for Fire-Fighting Cores Fire-fighting cores provide smoke free access to the upper floors of a building and allow the fire fighters to attack the fire from a position of relative safety. Where an outside wall is adjacent to stairs and lobbies: Fire-fighting cores include the following elements: I A 1m2 OV is required to the stairs at each storey or a 1.5m2 remote operated OV at the head of the stairs. I A 1m2 OV is required to each lobby. I A protected staircase Where an outside wall is not available: I A protected lobby I A fire-fighting lift (not for shallow basements) Note that...

 Open the catalog to page 6
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-7

The BRE shaft In automatic mode, the system is activated by the building fire detection system or a dedicated fire detection system incorporating smoke detectors in the accommodation adjacent to each door into the fire fighting core and supplied as part of the ventilation system. The detection system has the capability of distinguishing on which storey the fire occurs and providing a dedicated output for each storey. A break glass switch is also provided in the lobby on each storey for manual activation. Under fire conditions the damper or door on the fire floor as well as the AOV open. The dampers...

 Open the catalog to page 7
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-8

THE COLT SHAFT What is the Colt shaft? The Colt shaft is a mechanical shaft system which provides equivalent performance to a BRE shaft for the ventilation of fire fighting lobbies. It can therefore be considered an equivalent to the recommendations of Approved Document B and BS 5588-5:2004 for ventilation of fire fighting shafts. This shaft performs as well as or better than the BRE shaft and requires only 20% of the shaft area. The Colt Shaft, which is suitable for use in any fire-fighting core, requires a shaft of only 0.6m2 compared with 3m2 for the BRE shaft. This represents an 80 per cent...

 Open the catalog to page 8
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-9

Extended Corridor COLT EXTENDED CORRIDOR SYSTEM Colt has conducted a series of smoke tests which demonstrate that the Colt Shaft can perform to an equivalent standard as a standard 3m2 BRE Shaft when this is fitted in the same situation. The tests also showed that the system reacts quickly to pressure changes, smoke clears quickly from the lobby when the accommodation or stair doors are opened, and the lobby is kept clear of smoke once the accommodation door is closed. With the door to the accommodation closed, a typical 5m2 lobby will clear totally within 15 to 20 seconds of opening the stair...

 Open the catalog to page 9
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-10

Calculation of Minimum Free Area for Apartment Ventilators Prior to the latest edition of ADB, there was no defined method of measuring the free area of an AOV. As a result the common practice was to provide a bottom hung casement ventilator and sizing it so that the aggregate of the two side sections and the top opening resulted in a total of 1.5m2 as shown above. The plan area of the ventilator would also have to exceed 1.5m2. Under the new Approved Document B, however, the way AOV’s are measured has changed with the definition of ‘minimum free area’. If using a casement ventilator, the side...

 Open the catalog to page 10
SMOKE CONTROL IN APARTMENTS AND FIRE FIGHTING SHAFTS-11

Kameleon Ventilator Kent St, Liverpool. Kameleons. Colt Kameleon is an AOV (automatic opening) ventilator designed to ventilate corridors and stairwells in the event of a fire. I 8mm, 10mm single glazed clear glass unit I 20mm, or 28mm double-glazed clear glass unit I Double skin aluminium with infill material. The performance of Kameleon varies depending on the exact configuration. General description Kameleon is a natural casement ventilator, available in a wide range of sizes, flap options and control options. It may be installed into glazing systems or other types of walling systems, and...

 Open the catalog to page 11