The BLUEJAY new generation multi-channel energy meter is designed for precise energy monitoring in both residential and industrial settings. It supports flexible channel configurations from 1 to 24, accommodating both single-phase and three-phase measurements for diverse applications.
Specifications
  • High accuracy energy measurement with 0.5s precision.
  • Supports single-phase and three-phase measurements.
  • Configurable for 1 to 24 channels.
  • Meets CATIII-300V safety standards and can withstand voltages up to 4KV.
  • Communication options include RS485 and Ethernet, with optional modules such as DI, DO, PO, and AO.
Main Features
  • Basic parameters include voltage, current, frequency, total power factor, active power, reactive power, apparent power, active energy, reactive energy, and individual harmonic.
  • Supports voltage and current harmonic distortion measurement, time of use (TOU), and current/voltage unbalance.
  • SOE record available in most models.
Model Variants
  • MCM211D, MCM243d, MCM263T, MCM283D, MCM283R with varying features such as harmonic distortion measurement and communication options.
  • Measurement signal access includes 1A & 5A, 100mA, 333mV, L-N 300V, 3P, and L-L 480V, 1P.
Technical Characteristics
  • Power supply: DC/AC 85~265 ± 10 %, 50 / 60 Hz.
  • Consumption: Less than 10 VA.
  • Current measurement (TRMS) with options for PT secondary 100mA, 333mV, and standard 1A/5A.
  • Voltage measurement (TRMS) with PT secondary 100VAC / 400VAC.
  • Safety: Voltage level / CATIII-300V, withstand voltage 2.5KV to 4KV.
  • Communication: RS485/Ethernet optional, Protocol: Modbus RTU/TCP, IP.
See more

Catalog excerpts

MCM243d-1

I DIN-RAIL ENERGY METER NEW MCM SERIES MULTI-CHANNEL ENERGY METERi Introduction BLUEJAY new generation multi-channel energy meter is engineered for precise energy monitoring in both residential and industrial settings. It offers flexible channel configurations from 1 to 24, supporting both single-phase and three-phase measurements for diverse applications. Designed with rigorous safety standards, the meter meets CATIII-300V requirements and can withstand voltages up to 4KV. It also provides versatile communication options, including RS485 and Ethernet, with optional modules such as DI, DO, PO, and AO for enhanced system integration. • 0.5s High accuracy energy measurement; • Single-phase and three-phase measurements; • Supports 1 to 24 channels multi-channel configuration; • Residential and industrial energy monitoring applications; • CATIlI-300V voltage safety standards; • Communication: RS485, Modbus-RTU; Ethernet, TCP/IP optional; • Expandable modules: DI, DO, PO, AI and AO optional; Technology of Electrical Automatic

 Open the catalog to page 1
MCM243d-2

Technology of Electrical Automatic

 Open the catalog to page 2

All Chongqing Blue Jay Technology Co.,Ltd catalogs and technical brochures

  1. DEM-3M1C

    3  Pages

  2. DEM‑4MC

    3  Pages

  3. MCM283R

    2  Pages

  4. MCM400

    2  Pages

  5. MCM2400

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.