Catalog excerpts
Product Data GEMINI™ SELECT 38APS025-065, 38APD025-130 Commercial Air-Cooled Condensing Units with PURON® Refrigerant (R-410A) 50/60 Hz 25 to 130 Nominal Tons (88 to 457 Nominal kW) a38-7096 025 UNIT WITH LOW SOUND OPTION A38-7097 040-060 UNIT A38-7095 070 UNIT These dependable split systems match Carrier's 40RU or 39 Series indoor-air handlers with the versatile outdoor 38AP condensing units for a wide selection of commercial cooling solutions. • Split condensing units compatible with ASHRAE 90.1 • Chlorine-free, non-ozone depleting Puron refrigerant (R-410A) • Condenser coils feature the Novation® heat exchanger with microchannel coil technology • 38APS single-circuit unit has up to 3 rotary scroll compressors • 38APD unit has up to 6 rotary scroll compressors with 2 independent circuits • Standard scroll compressor units operate as low as 33% (single circuit) or 13% (dual circuit) of nominal capacity • Optional digital scroll compressors allow incremental unloading down to 16% (single circuit) or 6% (dual circuit) of nominal capacity for VAV applications. The digital scroll is always on the lead circuit (one per unit). • Protection against high discharge and low suction refrigerant pressure, and low oil pressure Features/Benefits The 38AP condensing unit offers the utmost in system configuration and control adaptability. Its premiumquality standard components ensure durable, efficient, and reliable operation. The 38AP units offer high unit EERs (Energy Efficiency Ratios) up to 11.5 and IPLVs (integrated part load values) up to 16.2. Copyright 2012 Carrier Corporation Form 38AP-11PD
Open the catalog to page 1Features/Benefits (cont) These units provide greater efficiency than similar units in the marketplace, which translates into year-round operating savings. The latest safety standards for 38AP units are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards, ETL approved. Versatility The 38AP Series condensing units feature up to 6 compressors and 2 refrigerant circuits, and can be matched with a wide variety of air-handling units. Single circuit condensing units can operate with a single air handler. Dual circuit condensing units can operate with a...
Open the catalog to page 2AEROACOUSTIC™ FAN vs. PROPELLER FAN 90 SOUND POWER [dB(A)] MODE Run Status Service Test Temperature Pressures Setpoints Alarm Status Inputs Outputs Configuration Time Clock ENTER ESCAPE Operating Modes a30-2187 Alarms 85 80 75 70 65 60 PENETRATES BUILDING STRUCTURE 55 50 25 SCROLLING MARQUEE DISPLAY 40 63 130 168 250 400 630 1080 1600 2400 4000 6300 8000 1/3 OCTAVE BAND CENTER FREQUENCY (Hz) AEROACOUSTIC FAN a30-3162 PROPELLER FAN AEROACOUSTIC FAN VS PROPELLER FAN Com fortL ink MOD E Alarm Run Status Servic e Tes t perat ures Pressu res Setpo ints Status Tem Inputs Outpu ts Config uration...
Open the catalog to page 3Model number nomenclature 38AP D 025 38AP – Split System Condensing Unit Refrigeration Circuit Options* D – Dual Refrigeration Circuit S – Single Refrigeration Circuit Unit Size 025 060 027 065 030 070 040 080 050 090 100 115 130 Pow er Supply 1 – 575-3-60 2 – 380-3-60 5 – 280/230-3-60 6 – 460-3-60 9 – 380/415-3-50 Condenser Coil/Low Sound Options 4 – MCHX, No Sound Treatment 5 – E-coat, MCHX, No Sound Treatment C – MCHX, Low Sound Fan(s) D – E-coat MCHX, Low Sound Fan(s) H – MCHX, Low Sound Fan(s), Compressor Blankets J – E-coat MCHX, Low Sound Fan(s), Compressor Blankets Revision Level A...
Open the catalog to page 4Options and accessories ITEM Condenser Coil/Low Sound Options E-Coated MCHX Low Sound Fan(s) Low Sound Compressor Blankets Vibration Isolation Pads Line Length Options Long Line Length Check Valve Ambient/Capacity Control/Interrupt Options Digital Compressor* High Short Circuit Current Rating Interrupt Motormaster V Low Ambient Control Electrical Options Dual Point Power (sizes 115 and 130 only) Non-Fused Disconnect Controls/Communications Options Navigator™ Display Remote Enhanced Display Touch Pilot™ Display EMM BACnet Communications BACnet Translator Control LON Translator Control...
Open the catalog to page 10Non-fused disconnect includes factory-installed nonfused disconnect capability for power and control located at the unit. Packaging options include bottom skid with standard coil protection and bottom skid, top crate with bag. Standard coil protection is also included on all unit packaging. Energy management module (EMM) provides energy management capabilities to minimize condensing unit energy consumption. The EMM is also available as a fieldinstalled accessory. BACnet communications option provides factory installed communication capability with a BACnet MS/TP network. Allows integration...
Open the catalog to page 1112 1077 (489) 1095 (497) 1240 (563) 1258 (571) 1246 (565) 1264 (573) 1113 (505) 1131 (513) 1276 (579) 1294 (587) 1282 (582) 1300 (590) STANDARD WEIGHT, lb (kg) CENTER OF GRAVITY, in. (mm) X Y 17.8 (452) 36.9 (937) 17.8 (452) 37.0 (940) 18.2 (462) 37.6 (955) 18.2 (462) 37.6 (955) 18.2 (462) 37.5 (953) 18.2 (462) 37.6 (955) 17.8 (452) 36.9 (937) 17.8 (452) 37.0 (940) 18.2 (462) 37.6 (955) 18.2 (462) 37.6 (955) 18.2 (462) 37.5 (953) 18.2 (462) 37.6 (955) 78.6 (1996) 66.5 (1689) 73.1 (1857) 61.0 (1549) HEIGHT, in. (mm) H a38-7223 H SEE NOTE #6 8.52 [216.4 ] 24.56 [623.8 ] 21.06 [534.9 ] 15.31...
Open the catalog to page 12UNIT CIRCUIT B COMPRESSOR ACCESS FRONT VIEW (DUAL CIRCUIT) CONTROL BOX HINGED ACCESS PANEL SIDE SEE NOTE #5 48 [1219] MIN. 42 [1067] MIN. 78.5 (1994) 73.0 (1854) HEIGHT, in. (mm) H H SEE NOTE #6 27.98 [710.7 ] RADIUS 20 [508] CONTROL BOX HINGED ACCESS CENTER OF GRAVITY, in. (mm) X Y 35.0 (869) 44.0 (1118) 33.7 (856) 44.1 (1120) 34.9 (886) 44.0 (1118) 33.4 (848) 44.1 (1120) 34.4 (874) 44.1 (1120) 35.0 (869) 44.0 (1118) 33.7 (856) 44.1 (1120) 34.9 (886) 44.0 (1118) 33.4 (848) 44.1 (1120) 34.4 (874) 44.1 (1120) FRONT VIEW (SINGLE CIRCUIT) COMPRESSOR ACCESS 1968 (893) 2094 (950) 1977 (897) 2120...
Open the catalog to page 1314 2561 2450 2633 2522 (1162) (1111) (1194) (1144) STANDARD WEIGHT, lb (kg) X 36.2 (920) 50.9 (1293) 35.1 (892) 50.9 (1293) Y 43.6 (1107) 40.6 (1031) 34.5 (876) 40.6 (1031) H 73.0 (1854) 73.0 (1854) 78.5 (1994) 78.5 (1994) HEIGHT, in. (mm) FRONT VIEW (38APS065) CONTROL BOX HINGED ACCESS 1.50 [38.1 ] SEE NOTE #4 TYP. FRONT VIEW (38APD070) CONTROL BOX HINGED ACCESS 1.50 [38.1 ] SEE NOTE #4 TYP. 8 FIELD CONTROL WIRING CONNECTIONS 1.00 [25.4 ] S1 4.00 [101.6 ] 34.99 [888.7 ] RADIUS 24 [610] CONTROL BOX HINGED ACCESS 42 [1067] MIN. 4.78 [121.3 ] 15.59 [396.0 ] AIR FLOW 28.48 [723.4 ] S2 X...
Open the catalog to page 14All CARRIER commercial catalogs and technical brochures
-
40UV-UH-14SI
32 Pages
-
42B-6SI
24 Pages
-
A WORLD OF COMFORT PRINT
10 Pages
-
A WORLD OF COMFORT
20 Pages
-
AirStream™ Room Fan Coils
4 Pages
-
The CRRSA Act (ESSER I)
2 Pages
-
A World of Comfort
2 Pages
-
Carrier-Catalogue-2018-2019
940 Pages
-
Axis™ Overhead Air Terminals
4 Pages
-
AERO® Air-Handling Units
4 Pages
-
19DV
32 Pages
-
30XA
136 Pages
-
30RAP
104 Pages
-
2019 Carrier Ductless
88 Pages
-
Carrier VRF
44 Pages
-
Special Seismic Compliance
1 Pages
-
Axis Overhead Air Terminals
2 Pages
-
Roomtop® 50AH036-072
24 Pages
-
OMNIZONE™ 50BV020-064
64 Pages
-
A World of Comfort
2 Pages
-
Low Noise Type CABINET FAN
16 Pages
-
Performance 16 Heat Pump
4 Pages
-
ComfortVIEW 3
6 Pages
-
VVT Zoning System
8 Pages
-
Heat Reclaim Chillers
2 Pages
-
Airstream Unit Ventilators
2 Pages
-
Airstream Room Fan Coils
2 Pages
-
Aero Air-Handling Units
2 Pages
-
17DA Centrifugal Chiller
2 Pages
-
AXIS? Overhead Air Terminals
3 Pages
-
Comfort? Series
2 Pages
-
GEMINI? 38AKS028-044
40 Pages
-
i-Vu Open Standard & Plus
2 Pages
Archived catalogs
-
ROOMAIR CONDITIONERS
6 Pages
-
AIRSTREAM™ Room Fan Coils
3 Pages
-
Water-Cooled Chillers
3 Pages
-
Antimicrobial Solutions
3 Pages