Product catalog summary
Overview: This document provides comprehensive technical data for Carrier's 38AUZ and 38AUD air-cooled condensing units, designed for commercial use with capacities from 6 to 20 nominal tons. These units utilize Puron (R-410A) refrigerant.
Features and Benefits:
  • Durability: Units are made with prepainted galvanized steel for longevity, with optional special coil coatings for enhanced protection.
  • Efficiency: Energy Efficiency Ratios (EER) reach up to 11.2, complying with ASHRAE and Energy Star standards to lower operating costs.
  • Control Systems: Equipped with Comfort Alert diagnostic systems for reliability, including phase loss and reversal protection, and anti-short cycle protection.
  • Factory-Installed Options: Options include low ambient controls, non-fused disconnects, convenience outlets, and special coil coatings.
Performance and Specifications:
  • Cooling Capability: Efficient operation in ambient temperatures from 40°F to 125°F.
  • Sound Levels: Sound power levels are detailed for various models, adhering to ARI standards.
  • Physical Data: Includes specifications on refrigeration systems, coil materials, fan configurations, and airflow capacities.
Options and Accessories:
  • 38AUZ/D Options: Includes disconnect switches, coil protection, convenience outlets, and hail guards.
  • 40RU Options: Offers alternate fan motors, drives, CO2 sensors, and heating coils.
ARI Capacity Ratings: Detailed capacity ratings for single and dual circuit models, including net cooling capacity, total power, and efficiency ratios.
Installation and Service: Designed for easy installation and service with features like multipoise design and accessible components.
Key Components:
  • Economizer: Uses enthalpy control for ventilation and free cooling, integrating with thermostats and CO2 sensors.
  • UV-C Germicidal Lamps: Prevents mold and fungus on evaporator coils and condensate pans.
  • Discharge Plenum: Directs airflow with adjustable louvers, available in painted or unpainted finishes.
  • Return-Air Grille: Provides a protective and aesthetic finish, available in painted or unpainted finishes.
  • Subbase: Offers a stable platform for floor-mounted units, aiding condensate drain connections.
Selection Procedure:
  1. Determine cooling load, evaporator-air temperature, and quantity.
  2. Select appropriate condensing unit and air-handler combination based on cooling capacity requirements.
  3. Determine sizes of liquid and suction lines using the Refrigerant Piping Sizes table.
  4. Calculate fan RPM and brake horsepower (BHP) using the Air Handler Fan Performance table.
  5. Select motor and drive that meet the RPM and BHP requirements.
Performance Data: Includes detailed performance ratings for models like 38AUZ and 38AUD series under various conditions.
Controls: Describes operating sequences, including start-up procedures, thermostat operations, and safety circuit functions.
Electrical Data Overview: Provides electrical specifications for models 38AUZ07, 38AUZ08, 38AUZ12, 38AUZ14, 38AUZ16, and 38AUZ25, covering voltage range, compressor data, and power supply requirements.
Application Data: Outlines operating limits and emphasizes selecting air handlers with a minimum of 300 cfm/ton, with guidelines for refrigerant piping.
Piping Recommendations: Specifies liquid and suction line sizes, maximum lift, and charge quantities for different equivalent lengths.
Guide Specifications: Describes system description, quality assurance standards, delivery, storage, handling, and warranty information, emphasizing compliance with industry standards.
Compressor Specifications: Compressors include a crankcase heater and internal high pressure and temperature protection.
Condenser Coil: Air-cooled with an integral sub-cooler, using aluminum NOVATION Heat Exchanger Technology, with optional copper fins.
Refrigeration Components: Includes liquid line service valve, suction line service valve, compressor oil, and a partial refrigerant charge.
Controls and Safeties: Features control wire terminal blocks, compressor lockout, and Comfort Alert Diagnostic Board for fault code indications.
Operating Characteristics: Capacity and power consumption specifications are provided, with operational capabilities up to 125°F and down to 40°F.
Electrical Requirements: Specifies nominal electrical characteristics with a single-point connection and a 24-v transformer for control circuits.
Special Features: Includes low-ambient temperature control, optional condenser coil materials, non-fused disconnect switch, convenience outlet, programmable thermostat controls, and a louvered hail guard package.
See more

Catalog excerpts

38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-1

38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant 6 to 20 Nominal Tons Product Data FEATURES/BENEFITS These dependable outdoor air cooled condensing units match Carrier’s indoor-air handlers to meet a wide selection of cooling solutions. Constructed for long life C09227 38AUZ07- 14 shown - the environmentally sound refrigerant The 38AUZ single circuit and 38AUD dual circuit, scroll compressor models are designed and built to last. The high efficient designed outdoor coil construction allows for a more efficient design in a smaller cabinet size that utilizes an overall reduction in refrigerant charge. Where conditions require, special coil coating coil protection option is available. Cabinets are constructed of prepainted galvanized steel, delivering unparalleled protection from the environment. Inside and outside surfaces are protected to ensure long life, good looks, and reliable operation. Safety controls are used for enhanced system protection and reliability. Each unit utilizes the Comfort Alert diagnostic and troubleshoot control system. This protects the units operation and provides valuable diagnostic information when required. Factory-installed options (FIOPs) Carrier’s air-cooled air conditioning split systems: S provide a logical solution for commercial needs S have a rugged, dependable construction S are available in single and circuit scroll compressor capacity control S have cooling capability up to 125_F (52_C) ambient and down to 40_F (4_C) ambient standard Certified and pre- engineered factory-installed options (FIOPs) allow units to be installed in less time, thereby reducing installed cost. FIOPs include: S low ambient controls which provide cooling operation down to - 20_F (- 29_C) ambient temperatures S non-fused disconnect S 115-v GFI (ground fault interrupter) convenience outlet, powered and non- powered available S special coil coating coil protection S louvered hail guard

 Open the catalog to page 1
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-2

FEATURES AND BENEFITS (cont.) Efficient operation These air cooled condensing units will provide EER’s up to 11.2 which meets both ASHRAE and Energy Star efficiency levels. applications and provide positive drainage and prevent standing condensate. Controls for performance dependability 38AU This high efficiency will help reduce overall operating cost and energy consumption. The accessory economizer can provide ventilation air to improve indoor-air quality by using demand control ventilation. When used in conjunction with Carrier Comfort System and CO2 sensors, the economizer admits fresh outdoor...

 Open the catalog to page 2
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-3

MODEL NUMBER NOMENCLATURE 2 8 A U Z A 1 3 4 _____________ Model Type 38AU = Air Cooled Cond. Unit Puronr R--- 410A Refrigerant 5 6 7 8 9 10 11 12 13 14 15 16 17 18 4 A 0 G 6 -- 0 A 0 A 0 ____ Brand / Packaging 0 = Standard 1 = LTL Type of Coil D = Dual Circuit, A/C Scroll Compressor Z = Single Circuit, A/C Scroll Compressor Electrical Options A = None C = Non--- Fused Disconnect Refrigerant Options A = None B = Low Ambient Service Options 0 = None 1 = Un--- powered Convenience Outlet 2 = Powered Convenience Outlet Nominal Tonnage 07 = 6 Tons 08 = 7.5 Tons 12 = 10 Tons 14 = 12.5 Tons 16 = 15 Tons...

 Open the catalog to page 3
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-4

ARI* CAPACITY RATINGS COOLING CIRCUTS 38AUZ07/40RU07 38AUZ08/40RU08 38AUZ12/40RU12 38AUZ14/40RU14 38AUZ16/40RU16 38AUZ25/40RU25 1 1 1 1 1 1 UNIT 38AU UNIT COOLING CIRCUTS 38AUD12/40RU12 38AUD14/40RU14 38AUD16/40RU16 38AUD25/40RU25 2 2 2 2 LEGEND AHRI NOM. CAPACITY (TONS) 6 7.5 10 12.5 15 20 NET COOLING TOTAL POWER CAPACITY (kW) (MBH) 71 6.1 92 8.2 117 10.3 148 13.5 180 16.4 240 21.6 NOM. CAPACITY (TONS) 10 12.5 15 20 NET COOLING TOTAL POWER CAPACITY (kW) (MBH) 117 10.4 147 13.4 180 16.4 240 21.6 --- Air ---Conditioning, Heating and Refrigeration Institute ASHRAE --- American Society of Heating,...

 Open the catalog to page 4
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-10

OPTIONS AND ACCESSORIES 38AUZ/D OPTIONS AND ACCESSORIES ITEM OPTION* ACCESSORY† Disconnect Switch (non-fused) X Special--- coated Coil Protection X Convenience Outlet (115-v)** X Low Ambient Temperature X X MotorMaster Ir Control Wired Condenser Coil Grille X Louvered Hail Guard X X Programmable Thermostats X * Factory-installed option. † Field-installed accessory. ** Powered and non--- powered versions available Louvered hail guard package protects coils against damage from flying debris and hail. 115-v convenience outlet is used to power electric drills, lights, and refrigerant recovery machines....

 Open the catalog to page 10
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-11

OPTIONS AND ACCESSORIES (cont.) ITEM Alternate Fan Motors Alternate Drives CO2 Sensors Condensate Drain Trap Discharge Plenum Economizer Electric Heat Hot Water Heating Coils Overhead Suspension Package Prepainted Units Return Air Grille Steam Heating Coil Subbase UV-C Germicidal Lamp** * Factory-installed option. † Field-installed accessory. ** Contact application engineer. OPTION* X X ACCESSORY† X X X X X X X X X X X X Economizer (enthalpy controlled) provides ventilation air and provides “free” cooling if the outside ambient temperature and humidity are suitable. The economizer can also be...

 Open the catalog to page 11
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-12

OPTIONS AND ACCESSORIES (cont.) 40RU WITH DISCHARGE PLENUM RETURN-AIR GRILLE AND SUBBASE 40RU WITH HOT WATER OR STEAM COIL HOT WATER OR STEAM COIL 38AU DISCHARGE PLENUM RETURN-AIR GRILLE SUBBASE FAN COIL UNIT FAN COIL UNIT 40RU WITH ECONOMIZER AND UV-C GERMICIDAL LAMPS 40RU WITH CONDENSATE TRAP ECONOMIZER UV-C GERMICIDAL LAMPS C09038 12

 Open the catalog to page 12
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-13

Combination ratings for 38AUZ/D units matched with 40RU Series air handlers are in this book. If unit is used with an air handler, use the Carrier Electronic Catalog AHU (Air-Handling Unit) selection program to obtain combined ratings. I. Determine cooling load, temperature, and quantity. IV. evaporator-air Given: V. Total Cooling Capacity Required (TC) . . . . . . . . . . . . . . . . . . . 121,000 Btuh Sensible Heat Capacity Required (SHC) . . . . . . . . . . . . . . . . . . . 95,000 Btuh Compressor Type . . . . . . . . . . . . . . . . . . . . . . . . . Scroll Temperature Air Entering Condenser...

 Open the catalog to page 13
38AUZ / 38AUD Air Cooled Condensing Unit Puronr (R---410A) Refrigerant-14

38AU TYPICAL WIRING SCHEMATIC C09624 Typical 38AUZ*16 Single Circuit 14

 Open the catalog to page 14

All CARRIER commercial catalogs and technical brochures

  1. 40UV-UH-14SI

    32  Pages

  2. 42B-6SI

    24  Pages

  3. 19DV

    32  Pages

  4. 30XA

    136  Pages

  5. 30RAP

    104  Pages

Archived catalogs

  1. Carrier VRF

    44  Pages

  2. ComfortVIEW 3

    6  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.