Product Overview:
The Buderus G215 Boiler is a high-efficiency, floor-standing boiler available in two models with outputs of 78kW and 95kW. It features cast iron sectional construction and is compatible with pressure jet burners. The boiler boasts an efficiency of up to 96% (NCV) and incorporates patented Ecostream Technology®. It can be pre-assembled or unassembled to meet site requirements and is compatible with renewable technologies such as solar thermal, heat pumps, and CHP.
Technical Specifications:
  • Rated Heat Output: 78kW (full load), 59kW (part load) for G215-78; 95kW (full load), 71kW (part load) for G215-95.
  • Net Efficiency: 95% (NCV).
  • Seasonal Efficiency: 85.7%.
  • Maximum Safety Temperature: 120°C.
  • Maximum Working Pressure: 4 bar.
  • Water Content: 85 liters for G215-78, 97 liters for G215-95.
  • Flue Gas Temperature: 160 – 198°C.
  • CO2 Content: 10% for gas, 13% for oil.
Dimensions and Clearances:
  • Boiler Sections: 6 for G215-78, 7 for G215-95.
  • Dimensions (H x L x W): 1110mm x 1027mm x 600mm for G215-78; 1110mm x 1147mm x 600mm for G215-95.
  • Service Clearances: Front - 1300mm (1000mm), Rear - 700mm (400mm), Left - 400mm (100mm), Right - 700mm (400mm).
Additional Information:
The document emphasizes that all information is provided in good faith and should be verified with installers or contract partners. Bosch Thermotechnology Ltd does not accept liability for third-party workmanship or operation. The document also includes contact information for Buderus Technical Services.
See more

Catalog excerpts

G215-1

TECHNICAL DATA SHEET PRODUCT: Buderus G215 Boiler_ G215 Floor Standing High Efficiency Boiler: ► Cast iron sectional boiler for use with pressure jet burners ► G/GE Cast Iron Thermostream boilers have Ecostream Technology® patented worldwide ► Available as pre-assembled or unassembled to suit site requirements ► No minimum flow rate ► No maximum return temperatures ► Flexible controls option using the Buderus 4000 controls system ► Can be used in conjunction with renewable technologies such as solar thermal, heat pumps and CHP Whilst it is always our intention to fully assist, it is essential to recognise that all information given by the company in response to an enquiry of any nature is provided in good faith and based upon the information provided with the enquiry. We recommend that advice should always be checked with your installer or contract partner. Consequently, the company cannot be held responsible for any liability relating to the use or repetition of such information or part thereof. In addition, whilst making every reasonable effort to monitor the performance and quality of our supply, installation and service network, we do not accept responsibility for the workmanship or operation of any third party company that the company may have promoted either in conversation, e-mail or other communication. Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole. Rl Ifl^KI 1^ Bosch Theimotechnology Ltd, Cotswold Way, Warndon, Worcester WR4 9SW (§=4th D^\C^U Buderus Technical Services Tel: 0844 892 3004, Fax: 01905 753130 DwOwO Bosch Group Web: www.BoschThLrmotechnology.co.uk Invented for life

 Open the catalog to page 1
G215-2

TECHNICAL DATA SHEET PRODUCT: Buderus G215 Boiler Whilst it is always our intention to fully assist, it is essential to recognise that all information given by the company in response to an enquiry of any nature is provided in good faith and based upon the information provided with the enquiry. We recommend that advice should always be checked with your installer or contract partner. Consequently, the company cannot be held responsible for any liability relating to the use or repetition of such information or part thereof. In addition, whilst making every reasonable effort to monitor the performance...

 Open the catalog to page 2
G215-3

TECHNICAL DATA SHEET PRODUCT: Buderus G215 Boiler The safety limit cut-out temperature can be adjusted within the 4000 series controls dependant on system requirements, The maximum possible system flow temperature is the safety limit temperature minus 18k. "Calculated flue gas temperatures used for cross-sectional calculation according to EN 303 The actual flue gas temperature may differ from this, subject to burner setting and actual system temperature. ***Flue gas mass flow has been measured at 60% for part load, and full load values relate to the upper and lower output range. ****The seasonal...