Overview: The BC105S-2AE Series Fan Coil Thermostats are designed for room temperature control in commercial and residential buildings. They offer precise temperature management, energy savings, and reduced power consumption by up to 50%.
Applications: These thermostats are compatible with 2-pipe fan coil units, EC Motor Fans, and can be equipped with features like timers, programmable settings, 0-10V valves, Modbus communication, and dry contacts for windows or doors.
Specifications:
  • Power Supply: 220VAC±10%, 50/60 Hz
  • Temperature Range: 5-35°C with ±0.5°C accuracy
  • Fan Type: EC Motor 0-10V
  • Valve Control: 0-10V
  • Communication: Modbus with various baud rates
  • Protection Grade: IP30
  • Installation: Surface mounting with a 60mm hole pitch
User Guide:
  • Power: Use the power button to switch the thermostat on or off.
  • Temperature Setting: Adjust using the up and down arrows.
  • Mode Selection: Switch between Cool, Heat, and Ventilation modes using the 'M' button.
  • Fan Control: Adjust fan speed and voltage output through parameter settings.
  • Valve Control: Configure 0-10V valve settings via parameter menu.
  • Backlight: Activates with any key press and times out after 6 seconds.
  • Keypad Lockout: Lock or unlock buttons by pressing specific keys for 3 seconds.
Parameter Settings: Access the parameter setting menu by pressing 'M' and the up arrow for 5 seconds. Adjust system type, auto mode, sensor type, fan control, and more.
Modbus Settings: Configure Modbus parameters by turning off the thermostat and holding the 'M' key for five seconds. Adjust address, baud rate, and parity settings.
Installation: Mount the thermostat on a clean, dry indoor wall, avoiding direct airflow from heating/cooling devices. Ensure compliance with local wiring and safety regulations.
Disposal: Dispose of the device according to local electronic waste regulations, not as domestic garbage.
See more

Catalog excerpts

Breeze BC105-4AEDM Datasheet-1

BC105S-2AE Series User Manual This Fan coil thermostats are widely used in all commercial and residential buildings room temperature control, accuracy control provides you comfortable environment, and have the effect of saving energy and reducing up to 50% power consumption. This universal thermostats work with: ^ 2-pipe fan coil unit ^ EC Motor Fan ^ Timer/Programmable (model No. with T Only) ^ Modbus communication (model No. with M Only) ^ Dry contact for window or door, Hotel card holder ^ External sensor for air or pipe temperature 2. Temperature setting range: 5-35°C 4. Temperature control Accuracy: ± 1°C 6. Valve Control: 0-10V valves 7. Remote Sensor Type: NTC10K,B=3950 8. Communication: Modbus 4800,9600,19200bps baud rate 9. Dry contact: for window, door or hotel card holder 10. Storage temperature: -20C~60C, Operating temperature: 0~50°C 15. Installation type: Surface mounting, Hole pitch: 60mm User Guide: ON/OFF: Press power button to switch ON and OFF thermostat. Temperature Setting: Press “^” to reduce temperature, press “A” to raise temperature Mode: Press “M” to change mode between Cool tfc, Heat * and Ventilation ❖ mode will be confirmed by pressing other button or automatically after 6 seconds Fan: Control EC Motor fan with 0-10V output, user can set up the voltage output by flowing steps: Switch off the thermostat and press “M” and “'"'”5 seconds to enter parameter setting menu, press the “M” or to change the item, and press to For example: The value is 40, The output voltage is 4V. (40*10%=4V). Item 07: Low Speed; (Range from 11 ~40 Default=40) Item 08: Med Speed; (Range from 41~70 Default=70) Item 09: High Speed; (Range from 71 ~99 Default= 90) Press power button “O” or wait 30S to exit and save all settings Valve: control 0-10V valve, user can set up the voltage output by flowing steps: Switch off the thermostat and press “M” and 5 seconds to enter parameter setting menu, press the “M” or to change the item, and press to Item 01: Heating mode KP, Range from 1 ~99, Default=10 Item 02: Cooling mode KP, Range from 1~99, Default=10 Item 03: Sampling time, Range from 1~99,(s), Default=20 Item 04: KI, Range from 1~99, Default=1 Item 05: kD, Used Item 06: Span, Range from 1~99, Default=5 Warning: the value above must set by specialized installation person!!! Backlight: Any key press will activate the backlight. Backlights will timeout 6 seconds after last key press. Keypad Lockout: (ONLY available when Item 11 set to 1/2/3): Press “^”and “A” for 3 seconds to lock the buttons and press “^”and “A” for 3 seconds to unlock. Clock (Only for the model number with T): Power on thermostat, press “M” for 3 seconds 1, the symbol hour flash, press ^or ^ to adjust hour 2, press “M” key, minute flash, press “^” or “A” to adjust minute 3, press “M” key, week flash, press “^” or “A” to adjust week Press power button “O” or wait 30S to exit and save all settings Timer on/off (Only for the model number with T): Repeat the Clock steps 1~4 above 1, Timer on and hour flash, press “^” or “A” to adjust hour 2, press “M” key, minute flash, press “^” or “A” to adjust minute 3, press “M” key, Timer off and hour flash, press “^” or “A” to adjust hour 4, press “M” key, minute flash, press “^” or “A” to adjust minute 5, press “M” or wait 6 seconds to confirm Note: This function only acts once and valid on current day. Press power button “O” or wait 30S to exit and save all settings Programmable (Only for the model number with T): Power on thermostat, press “M” and for 3 seconds 2, Press “^”and “A” to set start hour 3, Press “M” and use “^” “A” to set start minute 4, Press “M” and use “^” “A” to set desired temperature 5, Press “M” to enter event 2/3/4 and repeat step 2~4 6, Press “M” to edit “Sat & Sun” and repeat step 1~5 7, Press “M” or wait 6 seconds to confirm all the settings above Press power button “O” or wait 30S to exit and save all settings Parameter Settings: Switch off the thermostat and press “M” and “■*■”5 seconds to enter parameter setting menu, press the “M” or “'5'” to change the item, and press'^ -Mo change the value, press power button “O” or wait 30S to exit and save all settings Table Explanation: 1- Selectable System Type: control 2-pipe fan coil unit only 2- Auto Mode: you can set your 2-pipe system running as manual or auto season changeover 3- Sensor Type: 1: Internal sensor only. 2: external sensor only 3: the external sensor attaches to water pipe for measuring the water pipe temperature to change mode between Heat and Cool automatically, this function is only available under 2-pipe Fan coil (Option 1=0) and auto system (Option 2=1) at the same time

 Open the catalog to page 1
Breeze BC105-4AEDM Datasheet-2

if the water temperature is higher than or equal to certain temperature (Default as 22℃,see option 9). 4-Fan Control: when the room temperature reaches setpoint, you can set the fan stop running or continuous blowing Mount the room thermostat on the conduit box. Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources. Mount about 1.5 m above the floor 5-Unoccupied Status: when the hotel card is pulled out, the unoccupancy status will be: 0: no output; 1: thermostat will work in energy saving mode with setback setpoint, fan will run at low speed 7- Display...

 Open the catalog to page 2

All Breeze Controls catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.