Introduction
The DecoQT fan coil units are available in two sizes, DecoQT 70 and DecoQT 100, with options for 2 pipe and 4 pipe systems. These units can be provided as a packaged unit with controls and valves or customized with control ancillaries to reduce installation time.
Maintenance, Cleaning & Access
The DecoQT is designed for minimal maintenance with tool-free access for filter changes and cleaning. It features a removable panel for easy access to internal components and a removable condensate tray for coil access, suitable for residential apartments and hotels due to its low noise levels.
Applications
The DecoQT is designed for quiet operation, making it suitable for residential and hotel developments. It features an acoustically lined casework and a stylish grille for draught-free cooling.
Specifications
The casing is made from 1.0mm thick galvanized steel, ensuring robust construction. The unit includes a removable filter, copper coils with aluminum fins, and a condensate tray with insulation. The fans are energy-efficient with EC motors, having a lifespan of over 40,000 hours.
Controls
The DecoQT can be equipped with the EASYIO FW-14 controller, offering Wi-Fi and Ethernet connectivity. It supports various protocols for integration into building management systems, with options for digital controllers and accessories for fault reporting and temperature control.
Valves & Commissioning Sets
The DecoQT can be supplied with various valve options, including 4 port valves and PIC Valves for energy savings. Optional extras include fan monitoring boards, control relays, and transformers.
Additional Valve Options
Various valve options are available, including branch valve sets with PIC valves and commissioning sets for continuous water circulation. Strainers are recommended for the hydronic system, and raise lower actuators are available for certain controllers.
Technical Details
The technical details include noise ratings, performance data, and specific fan power (SFP) values. Detailed performance data is provided for different unit sizes under various conditions, with noise ratings as guidance.
Electrical Data
The electrical specifications include maximum running current, power, and starting current for different unit sizes. For example, DECOQT 70 has a maximum running current of 0.42 Amps and power of 58.3 Watts.
Drawings and Index
The document includes an index of drawings related to the DECOQT fan coil, detailing service areas and dimensions for DECOQT 70 and 100 units.
Contact Information
Biddle Air Systems is located in Nuneaton, Warwickshire, UK, with contact details for sales inquiries.
See more

Catalog excerpts

DECOQT-2

QUIET, EFFICIENT & EASY TO MAINTAIN The Biddle DecoQT fan coil has been designed for applications where silence is key and is ideally suited for use in residential and hotel developments. The acoustically lined casework ensures quiet operation, even when the DecoQT is running at full speed. With a stylish single-piece grille for inlet and outlet air, the DecoQT is discreet and silent, offering a comfortable, draught-free solution which suits the most stylish of environments. MAINTENANCE, CLEANING & ACCESS CUSTOMISABLE SOLUTIONS SINGLE INLET AND OUTLET GRILLE The DecoQT is designed for continuous...

 Open the catalog to page 2
DECOQT-3

SPECIFICATIONS CASING Manufactured from 1.0mm thick galvanised sheet Coils are manufactured from copper pipe which The fans used are some of the most energy The fan coil unit intakes and discharges air steel to create a rigid, robust and vibration free is mechanically bonded to aluminium fins. Coil efficient available. Each unit has double-inlet, through a single-piece hinged and curved grille construction, the casing is contoured and lined terminations are 15mm for both the heating and double-width centrifugal fans complete with that when opened provides access for cleaning or internally in...

 Open the catalog to page 3
DECOQT-4

DIRECT DIGITAL CONTROLLER RANGE The product’s controls offer is designed to be flexible to suit project specific controls or can be supplied with a range of capable direct digital controllers. The generous controls enclosure is available with every unit. Only supplied on request. The enclosure includes all electrics, switches and the digital controller and is mounted on the rear of the unit next to the coil terminations and valves. The enclosure is manufactured from galvanised sheet steel and is designed to house the majority of all controls on the market today. Biddle can supply a Johnson Controls...

 Open the catalog to page 4
DECOQT-5

VALVES & COMMISSIONING SETS Biddle offers a range of valve options for the DecoQT Series to suit the project’s requirements. The options are summarised below but please ask our sales team to discuss the options available to you and help decide which is best suited for your application. NO VALVES The unit can be supplied with exposed 15mm copper pipe connections for connecting to valves on site. The pipework is positioned at 40mm centres to facilitate the most common valve types on the market today. 4 PORT We can supply integrated 4 port valves to reduce site installation time on both the heating...

 Open the catalog to page 5
DECOQT-6

Sensible Total Unit Size Service area Unit Size Anticipated Air Installed volume SFP w/l/s NOISE RATING DECOQT PERFORMANCE DATA TECHNICAL DETAILS Unit Size DECOQT FAN COIL | TECHNICAL SPECIFICATIONS | 10 DECOQT ELECTRICAL DATA UNIT SIZE MAX RUNNING POWER WATTS [W] STARTING CURRENT AMPS [A] Service area MAX RUNNING CURRENT AMPS [A] a) Noise rating guide based on standard office environment and units installed in a suspended ceiling with a Dncw/Dnfw of 35 dB with up to 0 Pa external static resistance. b) EAT - Entering air temperature. c) Specific fan power values are calculated at 0 Pa. d) Heating...

 Open the catalog to page 6
DECOQT-7

BIDDLE AIR SYSTEMS St. Mary’s Road, Nuneaton CV11 5AU Warwickshire United Kingdom T: 02476 384233 E: [email protected] www.biddle-air.co.uk 3 Every effort has been made to ensure descriptions are correct at the time of print. Errors and omissions excepted. DECOQT|V1/2023

 Open the catalog to page 7

All BIDDLE catalogs and technical brochures

  1. DX AIR CURTAIN

    28  Pages

  2. PROAIR SERIES

    10  Pages

  3. FORCEFLOW

    11  Pages

  4. DOORFLOW

    17  Pages

  5. NOZ2

    7  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.