1. Catalogs
  2. Baltur
  3. TBG 35 60HZ
video corpo

TBG 35 60HZ

TBG 35 60HZ

TBG 35 60HZ

Product catalog summary
Specifications:
The gas burner, model TBG 35 60HZ, complies with European standard EN676 and operates in a single-stage mode. It is designed to emit low levels of NOx and CO, meeting class 3 requirements of the standard.

Design and Operation:
The burner features a combustion air intake with a throttle damper, allowing manual adjustment of the air flow rate. It includes a sliding boiler coupling flange to adapt the blast-pipe to various boiler types. Maintenance is simplified by the ability to remove the combustion head without detaching the burner from the boiler.

Gas Train:
The CE version gas train includes an operation and safety valve with electromagnetic drive, a minimum pressure switch, a pressure regulator, and a gas filter. There is an option for a gas train with valve tightness control. The gas train exit can be set to high or low.

Safety and Detection:
Flame detection is achieved through an ionisation electrode with a connector for a micro amp meter. The burner is equipped with fail-proof connectors for the burner/gas train connection.

Electrical Specifications:
The burner requires an AC power supply with a voltage of 220V and a frequency of 60Hz. It operates on a single-phase (1N) system. The fan motor power is 0.37 kW.

Physical Dimensions and Weight:
The burner has a width of 1030 mm, a depth of 510 mm, and a height of 410 mm. It weighs 28 kg without packaging and 30 kg with packaging.

Performance Range:
The burner operates with natural gas, with a minimum thermal power of 80 kW and a maximum of 410 kW. The minimum flow rate is 8 Sm³/H, and the maximum is 43 Sm³/H.
See more

Catalog excerpts

TBG 35 60HZ-1

Gas burner compliant with European standard EN676. Singlestage operation. Gas burner with low NOx and CO emissions in accordance with European standard EN676: class 3. Regulating combustion air and blastpipe. Combustion air intake with throttle damper. Manual adjusting of the air flow rate. Maintenance facilitated by the possibility of removing the combustion head without having to remove the burner from the boiler. Sliding boiler coupling flange to adapt the blastpipe to the various types of boilers. CE version gas train is complete with operation and safety valve with electromagnetic drive, minimum pressure switch, pressure regulator and gas filter. Possibility to choose gas train with valve tightness control. Fail proof connectors for burner/gas train connection Gas train exit: high/low. Flame detection by ionisation electrode with connector for micro amp meter. 7pole socket for burner electric and thermostatic supply. Electric protection rating: Operating range Operating range 8 Pressure (mbar) Technical data Tipo articolo Gas burner compliant with European standard EN676. Single stage operation.

 Open the catalog to page 1
TBG 35 60HZ-2

with European standard EN676: class 3. Regolazione aria e testa

 Open the catalog to page 2
TBG 35 60HZ-3

with European standard EN676: class 3. Regolazione aria e testa Regulating combustion air and blastpipe. Regolazione aria Combustion air intake with throttle damper. Manual adjusting of the air flow rate. Minimum Thermal Power (kW) to ErP Maximum Thermal Power (kW) to ErP Min flow rate (Sm³/H) Max flow rate (Sm³/H) Manutenzione facilitata Maintenance facilitated by the possibility of removing the combustion head without having to remove the burner from the boiler. Sliding boiler coupling flange to adapt the blastpipe to the various types of boilers. CE version gas train is complete with operation...

 Open the catalog to page 3

All Baltur catalogs and technical brochures

  1. TBG 60 60HZ

    3  Pages

  2. TBG 60 50HZ

    3  Pages

  3. TBG 45 60HZ

    3  Pages

  4. TBG 45 50HZ

    3  Pages

  5. TBG 35 50HZ

    3  Pages

  6. ETASUN

    2  Pages

  7. BCHS.2 80 P

    2  Pages

  8. BTG 3 50-60Hz

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.