1. Catalogs
  2. Baltur
  3. TBG 35 50HZ
video corpo

TBG 35 50HZ

TBG 35 50HZ

TBG 35 50HZ

Product catalog summary
Specifications:
The gas burner, model TBG 35 50HZ, complies with European standard EN676 and operates in a single-stage mode. It is designed for low NOx and CO emissions, classified as class 3 under the same standard. The burner features a combustion air intake with a throttle damper, allowing manual adjustment of the air flow rate.

Maintenance:
Maintenance is simplified by the ability to remove the combustion head without detaching the burner from the boiler. The burner includes a sliding boiler coupling flange to adapt the blast-pipe to various boiler types.

Gas Train:
The CE version gas train includes an operation and safety valve with electromagnetic drive, a minimum pressure switch, a pressure regulator, and a gas filter. There is an option for a gas train with valve tightness control. The gas train exit can be set to high or low.

Flame Detection and Electrical Supply:
Flame detection is achieved through an ionisation electrode with a connector for a micro amp meter. The burner is equipped with a 7-pole socket for electric and thermostatic supply. It operates on an AC power supply with a voltage of 230V and a frequency of 50Hz, requiring a single-phase connection.

Technical Data:
- Minimum Thermal Power: 80 kW
- Maximum Thermal Power: 410 kW
- Minimum Flow Rate: 8 Sm³/H
- Maximum Flow Rate: 43 Sm³/H
- Fan Motor Power: 0.37 kW
- Weight without packaging: 28 kg
- Weight with packaging: 30 kg
- Dimensions: Width 1030 mm, Depth 510 mm, Height 410 mm

Operating Range:
The burner operates with natural gas, with a power range from 0 to 400 kW and a pressure range from 0 to 8 mbar.
See more

Catalog excerpts

TBG 35 50HZ-1

Gas burner compliant with European standard EN676. Singlestage operation. Gas burner with low NOx and CO emissions in accordance with European standard EN676: class 3. Regulating combustion air and blastpipe. Combustion air intake with throttle damper. Manual adjusting of the air flow rate. Maintenance facilitated by the possibility of removing the combustion head without having to remove the burner from the boiler. Sliding boiler coupling flange to adapt the blastpipe to the various types of boilers. CE version gas train is complete with operation and safety valve with electromagnetic drive, minimum pressure switch, pressure regulator and gas filter. Possibility to choose gas train with valve tightness control. Fail proof connectors for burner/gas train connection Gas train exit: high/low. Flame detection by ionisation electrode with connector for micro amp meter. 7pole socket for burner electric and thermostatic supply. Electric protection rating: Operating range Operating range 8 Pressure (mbar) Technical data Tipo articolo Gas burner compliant with European standard EN676. Single stage operation.

 Open the catalog to page 1
TBG 35 50HZ-2

with European standard EN676: class 3. Regolazione aria e testa

 Open the catalog to page 2
TBG 35 50HZ-3

with European standard EN676: class 3. Regolazione aria e testa Regulating combustion air and blastpipe. Regolazione aria Combustion air intake with throttle damper. Manual adjusting of the air flow rate. Minimum Thermal Power (kW) to ErP Maximum Thermal Power (kW) to ErP Min flow rate (Sm³/H) Max flow rate (Sm³/H) Manutenzione facilitata Maintenance facilitated by the possibility of removing the combustion head without having to remove the burner from the boiler. Sliding boiler coupling flange to adapt the blastpipe to the various types of boilers. CE version gas train is complete with operation...

 Open the catalog to page 3

All Baltur catalogs and technical brochures

  1. TBG 60 60HZ

    3  Pages

  2. TBG 60 50HZ

    3  Pages

  3. TBG 45 60HZ

    3  Pages

  4. TBG 45 50HZ

    3  Pages

  5. TBG 35 60HZ

    3  Pages

  6. ETASUN

    2  Pages

  7. BCHS.2 80 P

    2  Pages

  8. BTG 3 50-60Hz

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.