K OG

K OG

K OG

Product catalog summary
Overview: This document provides technical specifications and features of chilled water cassette units designed for integration into suspended ceilings. It covers both 2-pipe and 4-pipe systems, detailing various models and their capabilities.
Product Specifications:
  • Models: 5 models for 2-pipe systems ranging from 2.2 kW to 10.2 kW, and 4 models for 4-pipe systems ranging from 2.2 kW to 10.1 kW.
  • Design: Units are designed for easy integration into suspended ceilings with formats of 600 x 600 mm and 600 x 1200 mm.
  • Dimensions: Low built-in height of 287 mm.
  • Materials: Galvanized steel sheet with thermal and acoustical insulation to prevent condensation and reduce noise.
Key Features:
  • Direct access to electrical connections via a sliding chassis.
  • Integrated valves and electrical connections.
  • New air intake design and air distribution capability to separate rooms.
  • Integrated condensate drainage lift pump with a capacity of up to 600 mm.
  • Infrared remote control version available with valve and changeover.
  • Compatibility with Aquanet (factory-fitted option).
  • Cleanable synthetic air filter with 55% arrestance, G1 class.
  • Convertible from left-hand to right-hand operation.
Performance Data:
  • Sound Levels: Sound pressure levels range from 30 to 60 dB(A) depending on the model and fan speed.
  • Airflow: Varies by model, with maximum airflow reaching up to 1725 m3/h.
  • Water Flow: Chilled and hot water flow rates are specified for each model, with corresponding pressure drops.
Accessories and Options:
  • Manual thermostats for heating/cooling with on/off and 3-speed ventilation control.
  • Special frames for solid ceilings and relay kits for chilled water cassettes.
  • 3-way heating valves and condensate trays available for both 2-pipe and 4-pipe systems.
Installation and Electrical Requirements:
  • Power supply options include 3~400V-50Hz and 1~230V-50Hz depending on the model.
  • Specific power cable sections and fuse ratings are provided for models with and without electric heating.
See more

Catalog excerpts

K OG-1

INDOOR UNIT K 9-12-18 OG K OG 2 PIPES CHILLED WATER CASSETTES 5 Models - 2 Pipes From 2,2 kW to 10,2 kW AIR CONDITIONING OF AN ADJACENT ROOM adjacent room main room AIR RENEWAL outside 192 inside PRODUCT ADVANTAGES • Designed for suspended ceiling integration. • 600 x 600 and 600 x 1200 formats (30 and 45 models). • Low built-in height: 287 mm. • Direct access to electrical connections on sliding chassis. • Integrated valves and electrical connections. • New air intake. • Air distribution to a separate room. • Integrated condensate drainage lift pump up to 600 mm. • Infrared remote control version with valve and changeover. • Solid ceiling frame (accessory). • Aquanet compatible (Factory fitted option To confirm when ordered). • Galvanized steel sheet with thermal and acoustical insulation, eliminating condensations on the casing and providing low sound levels. • Possibility of closing one or two discharge flaps. • Cleanable synthetic type air filter (55% arrestance, G1 class). • Easy conversion left hand to right hand. INDOOR UNIT K 30-45 OG TRM-FA TAE 20

 Open the catalog to page 1
K OG-2

2 Pipe K OG K 9 OG K 12 OG K 18 OG K 30 OG K 45 OG Indoor unit kW 2,2 3,5 5 6,44 10,2 Capacity kW kW Electrical heating (factory option) Heating Capacity Power input (fan) Cooling kW 3,3 0,049 1,5 30/32/42 420/460/700 0,378 12 571x571x287 625x625x40 26 K 9 OG 2T SV 7OG051008 4,6 0,056 2,25 32/35/44 420/460/700 0,602 17,5 571x571x287 625x625x40 28 K 12 OG 2T SV 7OG051012 5,9 0,074 2,7 34/40/49 460/515/760 0,86 15 571x571x287 625x625x40 29 K 18 OG 2T SV 7OG051016 8,05 0,20 4,2 39/42/49 1100/1350/1550 1,208 17 1171x571x287 1225x625x40 49 K 30 OG 2T SV 7SP041036 11,6 0,18 5,4 39/45/51 1000/1250/1630...

 Open the catalog to page 2
K OG-3

INDOOR UNIT K 9-12-18 OG K OG 4 PIPES CHILLED WATER CASSETTES 4 Models - 4 Pipes From 2,2 kW to 10,1 kW AIR CONDITIONING OF AN ADJACENT ROOM adjacent room main room AIR RENEWAL outside 194 inside PRODUCT ADVANTAGES • Designed for suspended ceiling integration. • 600 x 600 and 600 x 1200 formats (30 and 45 models). • Low built-in height: 287 mm. • Direct access to electrical connections on sliding chassis. • Integrated valves and electrical connections. • New air intake. • Air distribution to a separate room. • Integrated condensate drainage lift pump up to 600 mm. • Infrared remote control version...

 Open the catalog to page 3
K OG-4

4 Pipe K OG K 9 OG K 12 OG K 18 OG K 45 OG Heating Capacity kW 2.2 3.43 4.9 10.1 Capacity kW Power input (fan) Cooling kW 2.2 0.049 30/32/42 420/460/700 0.378 0.19 12 571x571x287 625x625x40 27 K 9 OG 4T SV 7OG051020 3.2 0.056 32/35/44 420/460/700 0.59 0.275 17 571x571x287 625x625x40 28 K 12 OG 4T SV 7OG051022 4.9 0.074 34/40/49 460/515/760 0.843 0.421 17.5 571x571x287 625x625x40 29 K 18 OG 4T SV 7OG051024 6.67 0.22 48/54/60 1075/1360/1725 1.89 0.758 34.3 1171x571x287 1225x625x40 55 K 45 OG 4T SV 7SP041024 K 9 OG 4T AV 7OG051021 K 12 OG 4T AV 7OG051023 K 18 OG 4T AV 7OG051025 3x1 1 1/2’’ heating...

 Open the catalog to page 4

All AIRWELL catalogs and technical brochures

  1. PAC HT

    4  Pages

  2. PAC BT

    8  Pages

  3. 2019 HEATING

    56  Pages

  4. Heating

    80  Pages

  5. Air conditioning

    148  Pages

  6. NDLP

    1  Page

  7. DK-DN

    2  Pages

  8. X AR

    2  Pages

  9. AQVL/AQVH

    2  Pages

  10. CWP HP

    2  Pages

  11. MQL / MQH

    2  Pages

  12. VHF

    2  Pages

  13. XLM OG

    2  Pages

  14. AQU@FAN II

    2  Pages

  15. CRWC/CRWN

    16  Pages

Archived catalogs

  1. SAF 024-045

    2  Pages

  2. had

    2  Pages

  3. DAKOTA WDI

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.