Hospitals
14Pages

{{requestButtons}}

Catalog excerpts

Hospitals - 1

Powerful. Reliable. Energy efficient. Viledon® air filtration solutions for hospitals Freudenberg Filtration Technologies

Open the catalog to page 1
Hospitals - 2

High standards of air filtration in hospitals The requirements for air filtration in the hospital environment can be summarised in three key statements: 1. rotection of patients, visitors and staff P against airborne contaminants 2. rotection against micro-organisms in P buildings 3. eliable filtering of non disease-causing R particles, as these can also act as a vehicle for spreading bacteria The function of air filters in hospitals Because many interior areas cannot be naturally ventilated, the majority of hospitals are air-conditioned. The increasing height of ward blocks also means that...

Open the catalog to page 2
Hospitals - 3

Standards and guidelines ensure security The role of HVAC systems is to guarantee a consistently high and hygienic interior air quality. Various guidelines and standards help to ensure that these advanced hygiene requirements, which play a particularly important role in a hospital’s air quality management function, are met at all times. The current standards include in particular Guideline VDI 6022 (in Germany) and the standards DIN 1946-4 and EN 13779. These regulations specifically define key criteria such as structural specifications, intake air quality, air filter quality, hygiene...

Open the catalog to page 3
Hospitals - 4

Meeting all hygiene requirements The hygiene regulations VDI 6022 formulated clear guidelines for HVAC systems in sensitive buildings like hospitals. The aim of these regulations is to guarantee the hygienic operation of HVAC systems and to protect the people who come into contact with them. Unlike the Viledon® air filtration solutions, conventional filters show significant shortcomings in relation to these regulations. Viledon® solutions fully conform to all the requirements of VDI 6022. Your benefits ■ moisture resistant up to 100% relative humidity ■ The materials used do not provide a...

Open the catalog to page 4
Hospitals - 5

jetSpin – advanced unique filter medium for pocket filters from class F 6 upwards. Viledon® service Specifically for hospitals, we offer: Hygiene inspections and hygiene checks in accordance with VDI 6022, using trained personnel Filter change, cleaning and disposal, including particle capture measurement Filter monitoring The built-in spacers ensure optimal pocket form during operation. Viledon® filterCair: the complete service package To ensure that you are able to exploit the high quality of our filters to maximum effect within your complex HVAC plant, we have developed a unique and...

Open the catalog to page 5
Hospitals - 6

Fungal spores and pollen under the electron microscope Typical impurities in the air Atmospheric dust Atmospheric dust is composed, among other things, of road dust, soot and organic deposits. Dust particles themselves are not usually pathogenic, but may carry micro-organisms. Pollen Pollen is part of the reproductive cells of plants. Although they are not pathogens, they can cause allergic reactions and asthma. Because pollen is larger than 15 microns, it can be effectively removed from the air using high-quality filters. Fungal spores Fungi contain many hundreds of different...

Open the catalog to page 6
Hospitals - 7

(above) Floor dust sample showing glass fibres and particles on the clean air side (left) Conventional glass-fibre pocket filter filter pocket ss-fibre Risks posed by loose glass-fibre particles Glass fibres are among the man-made mineral fibres, whose toxicity to humans is the subject of numerous investigations. From a strictly scientific point of view, based on existing epidemiological studies, a carcinogenic effect of glass fibres has neither been conclusively proved nor definitively ruled out. However, breathable glass fibre particles continue to be suspected of causing cancer. (right)...

Open the catalog to page 7
Hospitals - 8

Viledon® multi-stage filter concept in a hospital Everything relies on the right filter system In order to achieve the required level of indoor air quality, we combine different classes and types of filters into multi-stage systems. Generally, a 2-stage filtration system serves to capture both coarse and fine particles. In operating theatres or isolation rooms, terminal filters remove even finer particles from the air. These sensitive areas are subject to particularly stringent requirements. To ensure the highest standards of clean air in this environment, the air is circulated using low...

Open the catalog to page 8
Hospitals - 9

Silencer Air intake fan Heat register Droplet separator Air exhaust fan Rotating heat exchanger Humdifier Heat register 4 Filter mat or filter cell G3 – G4 Protection grid HEPA filter H 13 – H 14 High-volume flow HEPA filter H 13 – H 14 Compact pocket filter minimu

Open the catalog to page 9
Hospitals - 10

Filter mats Filter cells Compact pocket filters Freudenberg Filtration Technologies

Open the catalog to page 10
Hospitals - 11

NanoPleat cassette filters MaxiPleat cassette filters

Open the catalog to page 11
Hospitals - 12

EPA / HEPA filters with plastic frame HEPA filters with aluminium frame * MPPS = Most Penetrating Particle Size Also available: Terminal housings Terminal HEPA Filter / Hood Modules Fan filter units Safe-change housings (contamination-free filter changing) Accessories

Open the catalog to page 12
Hospitals - 13

Viledon® Excellence in filtration With Viledon®, Freudenberg Filtration Technologies offers hospitals a complete, top-quality range of filters from Class G 3 to H 14 for room ventilation and clean room technology. All our filters meet the highest standards of efficiency and operational safety, and all filters from Class F 5 to F 9 (EN 779) are EUROVENT certified. Our quality and management systems are certified under the current regulations of DIN EN ISO 9001, DIN EN ISO 14001 and OHSAS 18001. Viledon® filters have demonstrated proven success in many applications, providing reliable,...

Open the catalog to page 13
Hospitals - 14

Mix Produktgruppe aus vorblldllch bewlrtschafteten waidern und anderen kontrollierten HerkUnften www.fsc.org Zert.-Nr.SGS-COC-003186 © 1996 Forest Stewardsh ip Counci I Freudenberg Filtration Technologies KG 69465 Weinheim / Germany Phone +49 (0) 6201 80-6264 | Fax +49 (0) 6201 88-6299 viledon@freudenberg-filter.com | www.freudenberg-filter.com Viledon® is a registered and protected trademark of Carl Freudenberg KG. © Freudenberg Filtration Technologies KG 02 - CC - 009 - March 2010 - EN Freudenberg Filtration Technologies j~^1Freudenberg

Open the catalog to page 14

All Airwatec catalogs and technical brochures

  1. Win Air

    4 Pages

  2. PA 5 microns

    2 Pages

  3. Airwabox

    4 Pages