Catalog excerpts

Reversible air/water heat pump Cooling capacity 195,2 ÷ 639,6 kW Heating capacity 209,3 ÷ 674,2 kW • High efficiency also at partial loads • Reduced amount of refrigerant • Night mode Option integrated hydronic kit An optional, integrated hydronic kit containing the main hydraulic components, to obtain a solution that allows you to save money and to facilitate installation. It is available in different configurations with storage tank or with fixed pumps also inverter. CONTROL PCO⁵ Dual-circuit unit The units are dual-circuit, to ensure maximum efficiency both at full load and at partial load. The environmental impact of the units is reduced considerably owing to the last generation R32 refrigerant. Combining a reduced refrigerant load with a low global warming potential (GWP), these units boast low equivalent CO₂ values. ■ The leak detector is supplied as per standard. Use refrigerant fluid R32, whose classification according to ISO 817 is A2L (non-toxic, odourless and slightly flammable refrigerant). Working at full load up to -15 °C outside air temperature in winter, and up to 49 °C in summer. Hot water production up to 60 °C (for more details refer to the technical documentation). Operating field Microprocessor adjustment, with 7", touch screen keyboard, which allows to navigate intuitively among the various screens, allowing to modify the operating parameters and graphically view the progress of some variables in real time and the ad adjustment includes complete management of the alarms and their log. — Possibility to control two units in a Master-Slave configuration (from size 0800 to 2400) — The presence of a programmable timer allows functioning time periods and a possible second set-point to be set. — The temperature control takes place with the integral proportional logic, based on the water output temperature. — Floating HP control: available for all models with an inverter fan or DCPX. Thanks to continuous fan modulation, unit operation is optimised in every working position in cooling mode. The result is enhanced machine energy efficiency with partial loads. — "EASYLOG" data logger as per standard: allows all operating data read by the pCO5 to be stored on an SD card. — Night Mode: it is possible to set a silenced operation profile. Perfect for night operation since it guarantees greater acoustic comfort in the evenings, and a high efficiency in the time of greater load. The possibility to use electronic expansion valve, offers significant benefits, especially when the chiller is working with partial loads, increasing the energy seasonal efficiency of the unit. ° Standard A High efficiency E Silenced high efficiency L Standard silenced Electronic expansion valve Reversible outdoor heat pumps for the production of chilled/heated water designed to satisfy the needs of residential and commercial buildings, or for industrial applications. The base, the structure and the panels are made of galvanized steel treated with polyester paint RAL 9003. The whole range uses copper - aluminium condensation coils with reduced diameter rows, allowing a lower quantity of gas to be used compared to traditional coil
Open the catalog to page 1
— Low Superheat Control: Progressive superheating reduction in conditions of stability. This allows to increase energy performance: both in modulation and in full load conditions; — DLT control: Control of electronic valve at discharge temperature in certain operating conditions. This is demonstrated in an enhanced reliability of the control and a considerable expansion of the machine’s operating range, especially in heating mode. — AER485P1 — AERBACP — MULTICHILLER_EVO + AER485P1 In the 'J25-BMS2' port, the compatible accessories are: — AERNET — "BMS card" and "J25-BMS2" are two ports on...
Open the catalog to page 2
Device for peak current reduction Ver °,A,E,L A grey background indicates the accessory must be assembled in the factory A grey background indicates the accessory must be assembled in the factory Power factor correction Ver °,A,E,L A grey background indicates the accessory must be assembled in the factory A grey background indicates the accessory must be assembled in the factory A grey background indicates the accessory must be assembled in the factory A grey background indicates the accessory must be assembled in the factory
Open the catalog to page 3
(1) Water produced from 4 °C ÷ 20 °C (2) Water produced from 8 °C ÷ -10 °C (3) This option is not available with the Z operating field. The desuperheater must be intercepted in heating mode. In cooling mode, a water temperature no lower than 35°C must always be guaranteed on the heat exchanger inlet. (4) For all configurations including pump J please contact the factory. (5) Hydronic kit not available with sizes 0800 version °/L/A, 0900 version °, 1000 version °, 1800 version °. (6) For all possible configurations which include the “J” pump please be in touch with Aermec. Hydronic kit is...
Open the catalog to page 4
Size Cooling performance 12 °C / 7 °C (1) Cooling capacity Input power Cooling total input current EER Water flow rate system side Pressure drop system side Heating performance 40 °C / 45 °C (2) Heating capacity Input power Heating total input current COP Water flow rate system side Pressure drop system side (1) Data EN 14511:2022; Heat exchanger water (services side) 12°C / 7°C; outside air 35°C (2) Data EN 14511:2022; System side water heat exchanger 40 °C / 45 °C; Outside air 7 °C d.b. / 6 °C w.b. Size Cooling performance 12 °C / 7 °C (1) Cooling capacity Input power Cooling total input...
Open the catalog to page 5
Size Cooling performance 12 °C / 7 °C (1) Cooling capacity Input power Cooling total input current EER Water flow rate system side Pressure drop system side Heating performance 40 °C / 45 °C (2) Heating capacity Input power Heating total input current COP Water flow rate system side Pressure drop system side (1) Data EN 14511:2022; Heat exchanger water (services side) 12°C / 7°C; outside air 35°C (2) Data EN 14511:2022; System side water heat exchanger 40 °C / 45 °C; Outside air 7 °C d.b. / 6 °C w.b. Seasonal efficiency Size Fans: ° SEER - 12/7 (EN14825: 2018) (1) Calculation performed with...
Open the catalog to page 6All AERMEC catalogs and technical brochures
-
FCZI-D
5 Pages
-
FCZ-D
5 Pages
-
HWF
4 Pages
-
WFGI
9 Pages
-
WFGN
7 Pages
-
WFI
9 Pages
-
WFN
8 Pages
-
WRL 026 -161
5 Pages
-
Aermec Company Profile
21 Pages
-
BHP
6 Pages
-
DUALJET
10 Pages
-
AERMEC FOR WINE
20 Pages
-
Aermec Data Centre solutions
12 Pages
-
Aermec Guida Idronica
40 Pages
-
Aermec Split System VRF
92 Pages
-
ANK
8 Pages
-
ANLI
8 Pages
-
Aermec Company Profile
15 Pages
-
Variable multi flow
8 Pages
-
MGW
2 Pages
-
NSI
4 Pages
-
TA
4 Pages
-
TS
2 Pages
-
Omnia Radiant
4 Pages
-
MHM
4 Pages
-
MHW
2 Pages
-
Technical Focus
16 Pages
-
All product
404 Pages
-
Split System and VRF systems
48 Pages
-
GPUY:products guide 2012
194 Pages
Archived catalogs
-
Data sheet - Fan coils
4 Pages
-
Data sheet - Dehumidifier
2 Pages
-
Data sheet - UR
4 Pages
-
Data sheet- split system
2 Pages