Ordering Information
The Adquio Multi IOs Modbus Module is identified by the reference ADQ-SA-5R-4DO-8ADI-4AO-4PT1000. It is an active input and output module featuring 5 relays (10A to 250V), 4 digital outputs (DO), 4 analog outputs (AO), 8 digital/analog inputs (D/AI), 4 PT1000 inputs, and both a 485 master and slave.

Technical Data
  • Process Voltage: Nominal 24 VDC, maximum 28 VDC, with protection against voltage reversal and a nominal protection fuse up to 3 A.
  • Consumption: 130 mA from a 24V power supply, with a maximum consumption peak at start-up of 150 mA.
  • Analog Inputs: 8 inputs with a range of 0-10 V, 12-bit resolution, and overvoltage protection.
  • Digital Inputs: 8 inputs with a 24 VDC signal, overvoltage protection, and input signal indicator.
  • PT1000 Inputs: 4 inputs with 15-bit resolution, adjustable by software.
  • Analog Outputs: 4 outputs with a range of 0-10V, 12-bit resolution, and overvoltage protection.
  • Digital Outputs: 4 outputs with a maximum load of 2 A and overvoltage protection.
  • Relay Contacts: 5 contacts with a maximum current per contact of 10A and nominal voltage of 250V AC.

System Data
  • Environmental Conditions: Operating temperature from 0°C to +60°C, storage and transport from -40°C to +70°C, with a maximum humidity of 95% non-condensing.
  • Mechanical Data: Horizontal mounting with IP20 protection level, housing made of ABS UL-94-HB dark gray.
  • Communications: Supports Modbus RTU protocol for both 485 master and slave.

Modbus Configuration
The module includes a detailed Modbus register configuration table and address configuration using microswitches.

Certifications
The module complies with various safety, health, EMC, and RoHS standards, including EN ISO 13849-1: 2015, EN 62061: 2005, and EN 61000-6-4: 2007.

Contact Information
Neuronal Innovation Control SL, Rúa Ánade Real 11, 15172 Oleiros, La Coruña, Spain. Telephone: 881 246 255, Email: [email protected], Website: adquio.com
See more

Catalog excerpts

ADQUIO MULTI IOS MODBUS MODULE-1

TECHNICAL DATA SHEET ADQUIO MULTI IOS MODBUS MODULE Modbus input and output module 1 Ordering information Reference Life cycle * Adquio multi IOs modbus module, input and output module with 5 relays from 10A to 250V, 4 DO, 4A0, 8 D / AI, 4 PT1000, 1 485 master and 1 485 slave * For planning and commissioning of new installations use modules in Active state only Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 1
ADQUIO MULTI IOS MODBUS MODULE-2

Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 2
ADQUIO MULTI IOS MODBUS MODULE-3

3 Technical data Parameter Process voltage Connections Removable terminal block 5.08 Pitch 2 contacts Nominal value Maximum supported Protection against voltage reversal Nominal protection fuse up to Consumption From a 24V power supply Maximum consumption 130 mA + Consumption of loads on digital outputs Maximum consumption peak at start-up CAUTION! Exceeding the maximum power supply voltage for process or supply voltages could cause irrecoverable damage to the system. The system could be destroyed. WATCH OUT!! Improper connection cables cause overheating at the terminals. Acquio pro, they can...

 Open the catalog to page 3
ADQUIO MULTI IOS MODBUS MODULE-4

3.1 Technical data of the analog inputs Parameter Removable terminal block 5.08 Pitch 4 contacts Input signal indicator Overvoltage protection 3.2 Technical data of the analog inputs (if the inputs are used as digital) Parameter Removable terminal block 5.08 Pitch 7 contacts Input signal indicator Overvoltage protection 3.3 Technical data of the PT1000 inputs Parameter Number of inputs Removable terminal block 5.08 Pitch 8 contacts Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 4
ADQUIO MULTI IOS MODBUS MODULE-5

3.3 Technical data of the analog outputs Parameter Removable terminal block 5.08 Pitch 4 contacts Maximum load Output signal indicator Overvoltage protection 3.5 Technical data s of the digital outputs Parameter Removable terminal block 5.08 Pitch 4 contacts Maximum load Output signal indicator Overvoltage protection 3.6 Technical data of the relay contacts Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 5
ADQUIO MULTI IOS MODBUS MODULE-6

Removable terminal block 5.08 Pitch 10 contacts Maximum current per contact Nominal voltage of contacts Operation LEDs 4 System data 4.1 Environmental conditions Parameter Temperature Operation 0 ° C ... + 60 ° C ( Horizontal mounting on DIN rail) 4.2 Mechanical data Parameter Mounting Value Horizontal Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 6
ADQUIO MULTI IOS MODBUS MODULE-7

Protection level Housing material Mounting alternatives Rail DIN EN 50022 DIN mounting screws Screw with a diameter of 4 mm tightening torque Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 7
ADQUIO MULTI IOS MODBUS MODULE-8

4.5 Tabla de configuración de registros modbus Posiciones Modbus Función Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Digital output 1 Change Holding Register Digital output 2 Change Holding Register Digital output 3 Change Holding Register Digital output 4 Change Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Acquio multi IOs modbus module V 1.1 en_us...

 Open the catalog to page 8
ADQUIO MULTI IOS MODBUS MODULE-9

Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Holding Register Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 9
ADQUIO MULTI IOS MODBUS MODULE-10

Holding Register Holding Register Holding Register Holding Register Modbus slave, restart to apply Holding Register Holding Register Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 10
ADQUIO MULTI IOS MODBUS MODULE-11

4.6 Modbus address configuration table with microswitches Interruptor 1 Dirección Modbus Acquio multi IOs modbus module V 1.1 en_us

 Open the catalog to page 11
ADQUIO MULTI IOS MODBUS MODULE-12

Neuronal Innovation Control SL Rúa Ánade Real 11 15172 Oleiros, La Coruña Spain Telephone: 881 246 255 E-mail: [email protected] https://adquio.com © 2020-2021 Neuronal Innovation Control SL We reserve all rights to this document and to the information contained therein. The reproduction, use or disclosure to third parties without express authorization is strictly prohibited. Acquio multi IOs modbus module V 1.1 en_us