Overview
The ACO QUATRIX® is an automated anti-flooding device designed for black water connections, conforming to BS EN 13564 standards. It features an in-line Type 3 backflow valve with an access chamber, suitable for both internal and external applications.

Design and Installation
The device is designed for installation in solid floor constructions and connects to 110mm and 160mm diameter drain pipes. It includes a height-adjustable access chamber with an optional DPM bonding flange. The reversible cover is designed for tiled or cementitious floor finishes and can rotate for alignment with floor tiling. The motor/valve body is IP67 rated, ensuring suitability for various environments.

Functionality
Under normal conditions, the backflow flaps remain open to allow wastewater flow. In the event of backflow, a pressure sensor activates the motorised flap, which shuts under pressure, triggering an audible alarm and a flashing light. The control box includes a 24-hour power backup for reliability during power cuts. A secondary flap allows for manual operation, with positions for normal use and emergency or long-term non-use.

Key Features
  • Conforms to BS EN 13564 standards.
  • Double flap security with manual override.
  • Reversible access cover for tile or cement floor finishes.
  • Compatible with 110mm and 160mm diameter pipes.
  • All parts are removable for cleaning.
  • Optional DPM flange for enhanced installation flexibility.


Technical Specifications
  • Automatic backflow valve suitable for black or domestic grey water.
  • IP67 rated motor and IP56 rated control box with visual and audible alarms.
  • Lockable access chamber with adjustable height and rotation.
  • Reversible access cover with Load Class K3 to BS EN 1253.
  • Weight: 17kg.
  • 500mA passive Building Management System output interface.
  • Mains supply: 230V, 0.5A.


Ordering Information
Part numbers and dimensions are provided for different configurations, including options for chamber extension pieces and DPM flanges.

Contact Information
ACO Building Drainage, ACO Business Centre, Caxton Road, Bedford, Bedfordshire MK41 0LF. Tel: 01462 816666, Fax: 01462 851490, Email: [email protected], Website: www.acobuildingdrainage.co.uk
See more

Catalog excerpts

Quatrix® without Chamber-1

ACO QUATRIX® Backflow valve with access chamber The ACO QUATRIX® backflow valve is an in-line Type 3 automated anti-flooding device conforming to BS EN 13564 suitable for black water connections (faecal wastewater) installed with its own access chamber. The motorised flap activates and shuts under pressure sounding an audible alarm accompanied by a flashing light. When backflow abates the process is reversed. In the event of a power cut, the control box has a 24 hour power back-up. Versatile design Quatrix backflow devices have a 2-position secondary flap for manual operation. The ACO QUATRIX®, which installs into solid floor construction with connection to 110mm and 160mm Ø drain pipe, features a height adjustable access chamber with optional DPM bonding flange. Access is gained through a reversible cover designed for tiled or cementitious floor finishes which rotates for ease of alignment with floor tiling and is fully sealed. The IP67 rated motor/valve body ideal for internal or external applications. 1. Locked open (normal) Reliable function Under normal conditions the backflow flaps are open allowing waste water to flow to the drain. When backflow occurs, reversing the direction of flow, water will reach a certain level within the pipe activating a pressure sensor which is monitored at the control box. 2. Locked shut (for emergency use or long periods of non-use) Double flap security with manual override Reversible access cover for tile infill or cement floor finishes Backflow valve with sealed access chamber height adjustable access shaft rotates for tile alignment All parts removable for cleaning DPM flange option For internal or external applications

 Open the catalog to page 1
Quatrix® without Chamber-2

Automatic backflow valve for use in black water or domestic grey water, IP67 rating ACO Quatrix-K with access chamber and cover Power operated flap and manual locking flap ACO Quatrix-K with access chamber and cover IP56 rated control box with visual and audible alarm Lockable access chamber adjusts for height and rotation 100mm chamber extension piece (option) 110/160 Reversible access cover 300mm x 300mm Load Class K3 to BS EN 1253 Control box (117mm wide x 180mm high x 75mm deep) Weight, 17kg 500mA passive Building Management System output interface Connections to backflow unit Bezel rotates...

 Open the catalog to page 2

All ACO Building Drainage catalogs and technical brochures

  1. LipuJet-P-OAP

    3  Pages

  2. Pipe®

    36  Pages

  3. AS701 Upstand

    2  Pages

  4. AS901 Hi Load

    2  Pages

  5. AS501

    2  Pages

  6. AS401

    2  Pages

  7. AS301

    2  Pages

  8. AS201

    2  Pages

  9. AS101

    2  Pages

  10. FreeDeck

    20  Pages

  11. Pipe®

    60  Pages

  12. Easyflow

    16  Pages

  13. Shower Gullies

    35  Pages

  14. Shower Channels

    48  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.