ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details
725Pages

{{requestButtons}}

Catalog excerpts

ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 1

ADDENDUM - 2019 Electrical installation solutions for buildings - Technical details Complementary volume to the catalogue “Electrical installation solutions for buildings” © • Detailed product specification and characteristics • Operating curves, connection diagrams, application examples etc.

Open the catalog to page 1
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 3

MINIATURE CIRCUIT-BREAKERS RESIDUAL CURRENT DEVICES Electrical installation solutions for buildings Technical details ARC FAULT DETECTION DEVICES ENERGY EFFICIENCY PLUG-IN SYSTEMS LIGHT SWITCHES AND SOCKET OUTLETS INTRUSION ALARM SYSTEMS CONSUMER UNITS AUTOMATION BOARDS JUNCTION BOXES

Open the catalog to page 3
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 4

— Two volumes, one objective: to always find the best solution From a single catalogue with two complementary volumes: streamline to simplify, analyse to choose. The catalog Electrical installation solutions for buildings comes in two separate but integrated volumes: one dedicated to the description and easy selection of products code and one for professionals searching for in-depth details and specifications, installation examples and special technical solutions. Electrical installation solutions for buildings An indispensable tool for those who are looking for easy selection of a...

Open the catalog to page 4
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 5

— MCBs S 200 series B characteristic Order details Type code Order code Rated current Order details Pack unit Type code Order code Rated current Order details Pack unit Type code Order code suitable for flow-type heaters 12 kW *2 suitable for flow-type heaters 18 kW *1 Rated current Order details Type code Price Weight 1 piece 1 piece Order code Rated current Order details Type code Order code Price Weight 1 piece 1 piece Pack unit TIP: You can always find a detailed online information about the particular product item: suitable for flow-type heaters 12 kW suitable for flow-type heaters 18...

Open the catalog to page 5
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 7

Electrical installation solutions for buildings - Technical details MCBs Index Definitions according to standards for miniature Limitation of specific let-through energy I2t 1/16 Peak current Ip 1/35 SOC - Selected Optimized Coordination 1/45 Coordination tables: back-up 1/46 Coordination tables: selectivity 1/82 MCBs internal resistance, power loss and max. permissible earth-fault loop impedance 1/163 Performances at different ambient temperatures, altitudes and frequencies 1/169 Use of MCBs in direct current circuits 1/178 S 200 MUC series AC/DC Applications 1/181 Use of MCBs in altitude...

Open the catalog to page 7
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 8

— MCBs technical details Definitions according to standards for miniature circuit breakers Rated insulation voltage (Ui) according IEC/EN 60664-1: Root mean square (R.M.S.) withstand voltage value assigned by the manufacturer to the equipment or to a part of it, characterizing the specified (long-term) withstand capability of its insulation. NOTE: The rated insulation voltage is not necessarily equal to the rated voltage of the equipment which is primarily related to functional performance. IEC/EN 60898-1 Miniature Circuit Breakers according IEC/EN 60898-1 are intended for the protection...

Open the catalog to page 8
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 9

— MCBs technical details Definitions according to standards for miniature circuit breakers Rated operational voltage (Ue) The rated operational voltage of an equipment is a value of voltage which, combined with a rated operational current, determines the application of the equipment and to which the relevant tests and the utilization categories are referred. For single-pole equipment it is generally stated as the voltage across the pole. For multi pole equipment it is generally stated as the voltage between phases. An equipment my be assigned a number of combinations of rated operational...

Open the catalog to page 9
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 10

ELECTRICAL INSTALLATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 2CHC 419 005 C0201 Thermal release 0 Current: Tripping time conventional conventional non-tripping tripping current current Electromagnetic release 0 Currents: hold trip Tripping time 0 The indicated electromagnetic tripping values apply to a frequency range of 16 2/3 ... 60 Hz. For different network frequencies or direct current the values change according to the multiplier in the table below 0 The thermal releases are calibrated to a nominal reference ambient temperature; for Z and K, the value is 20 °C, for B and C = 30...

Open the catalog to page 10
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 11

1) Reference ambient temperature 30 °C (in the case of higher ambient temperatures, the current values are reduced by ca. 5 % per each 10 K)

Open the catalog to page 11
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 12

ELECTRICAL INSTALLATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 2CHC 419 005 C0201 0 The indicated electromagnetic tripping values apply to a frequency of 50/60 Hz. 0 The thermal release are calibrated to a nominal reference ambient temperature; for B, C, D, UCB and PVS it is 30 °C, for

Open the catalog to page 12
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 13

— MCBs technical details Tripping characteristics Tripping characteristics S200 / S200M / S200P Characteristic C IEC-EN60898 Multiples of Multiples of rated current rated current Multiples of Multiples of rated current rated current Minutes Seconds Minutes Seconds Tripping curve Tripping curve from cold state cold state from Minutes Seconds Tripping curve Tripping curve from cold state cold state from Minutes Seconds Tripping curve Tripping curve from cold state cold state from Multiples of Multiples of rated current rated current

Open the catalog to page 13
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 14

— MCBs technical details Tripping characteristics Tripping characteristics S200 / S200M / S200P Characteristic K IEC-EN60947-2 Multiples of rated current Tripping curve from cold state Minutes Seconds Minutes Multiples of rated current Tripping curve from cold state Tripping curve from cold state Tripping curve from cold state Tripping curve from cold state Multiples of rated current Multiples of rated current

Open the catalog to page 14
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 15

— MCBs technical details Tripping characteristics Tripping characteristics S200S Characteristic B

Open the catalog to page 15
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 16

— MCBs technical details Tripping characteristics Tripping characteristics SU200 M Characteristic C

Open the catalog to page 16
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 17

MCBs technical details Tripping characteristics Tripping characteristics S200 80-100A Multiple of rated current -►

Open the catalog to page 17
ADDENDUM – 2019 Electrical installation solutions for buildings – Technical details - 18

— MCBs technical details Tripping characteristics Characteristic K S 200 UDC a thermal trip b electromagnetic trip

Open the catalog to page 18

All ABB Home and Building Automation catalogs and technical brochures

  1. Zenit

    200 Pages

  2. Millenium

    64 Pages

  3. Smarter Home

    32 Pages

  4. Light switches

    56 Pages

  5. Create smarter

    40 Pages