YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS
1 / 17ページ

{{requestButtons}}

カタログの抜粋

YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 1

INSTALL CONFIDENCE YORK® BULKHEAD MOUNTED CHILLED BEAMS ENGINEERING GUIDE Johnson Controls

カタログの1ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 2

YORK® Bulkhead Active Chilled Beams 3 CB-ABB-YK / CB-ABC-YK Performance Data 5 Johnson Controls

カタログの2ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 3

YORK® Bulkhead Active Chilled Beams Energy Efficiency Delivered YORK® bulkhead chilled beams are the air distribution device of choice in high performing energy efficient buildings. Utilizing an integrated sensible cooling coil, active beams reduce the volume of air required for space cooling. A smaller volume of primary air minimizes energy consumed treating outdoor air and nearly eliminates energy wasted by parasitic reheat. When compared to conventional VAV systems a 30% energy savings can be realized. Superior Performance Aerodynamically designed nozzles inject conditioned primary air...

カタログの3ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 4

Standard Features: • 2 foot to 6 foot lengths, 1 foot increments • 2-pipe and 4-pipe coil configurations • Configured nozzle geometry for capacity optimization • Commissioning port with roomside access for balancing • Mounting brackets with adjustments in two directions • V2" Sweat water coil connections • Coil air vent • Louvered supply grille • Perforated return grille Options and Accessories: • Linear bar supply grille • Linear bar return grille • Egg crate return grille • V2" thick foil-faced EcoShield, anti-microbial external insulation • Coil drain valve • ^" MNPT water coil...

カタログの4ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 9

1. All performance data based on test performed in accordance with ASHRAE Standard 200-2015 2. APr . values are measured in inches of water 3. NC values are based on room absorption of 10 dB. A dash (-) indicates an NC value less than 15 4. Throw values are based on isothermal supply air and represent throw distances to terminal velocities of 150, 100 and 50 fpm respectively 5. AP . values are measured in feet of water. AP . values in shaded cells indicate use of a two circuit coil. All other values Coil Coil represent a single circuit coil. 6. Induction ratio is multiplied by the volume...

カタログの9ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 10

SCREW HOLES ON GRILLES NOT SHOWN 271RS SUPPLY AND 8R RETURN SHOWN. OTHER OPTIONS AVAILABLEJohnson Controls 10

カタログの10ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 11

: F - ,‘ ON GRLLES NOT SHOWN -, I -•: C . -'-1Y AN_| bR RETURN SHOWN CBAB SUBMITTAL FOR PIPE SUPPLY AND RETURN DETAILS

カタログの11ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 12

1.01 Summary This section describes the active chilled beams. 1.02 Submittals Submit product data for all items complete with the following information: 1. Operating weights and dimensions of all unit assemblies. 2. Performance data, including sensible and latent cooling capacities, nozzle types, primary and total supply (primary plus induced) airflow rates, chilled (and where applicable hot) water flow rates, noise levels in octave bands, air and water side pressure losses and maximum discharge air throw values. 3. Construction details including manufacturers recommendations for...

カタログの12ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 13

with factory integrated manual air vents. (OPTIONAL, coil from the structure above by a four (4) threaded rods shall be provided with factory integrated drain fittings.) of 3/8” diameter (provided by the installing contractor). Unless otherwise specified, coil connections shall be The upper end of the rods shall be suspended from strut bare copper for field sweating to the water supply circuit. channels that are a) mounted perpendicular to the beam Connections shall face upwards, be located near the length and b) at least four inches wider than the beam left end of the beam (when viewing...

カタログの13ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 14

material due to improper site protection shall be cause for rejection. 2. Clean equipment, repair damaged finishes as required to restore beams to as-new appearance. Guide Specification: CB-ABC-YK Active Chilled Beams PART 1- GENERAL 1.01 Summary This section describes the active chilled beams. 1.02 Submittals Submit product data for all items complete with the following information: 1. Operating weights and dimensions of all unit assemblies. 2. Performance data, including sensible and latent cooling capacities, nozzle types, primary and total supply (primary plus induced) airflow rates,...

カタログの14ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 15

2 or 4 pipe water connections as indicated on plans to that which results in a maximum ten (10) foot head and schedules. Four pipe configurations shall require loss. Water flow velocities through the beam shall not separate supply and return connections for chilled and hot water. The coil shall be mounted horizontally and shall be manufactured with seamless copper tubing (½” outside diameter) with minimum .016 inch wall thickness mechanically fixed to aluminum fins. The aluminum fins shall be limited to no more than ten (10) fins per inch. The coil shall have a working pressure of at least...

カタログの15ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 16

minimum pressure of 360 PSI. Contractor shall assure that the chilled water supplying the beams has been properly treated in accordance to BSRIA publication AG 2/93. 6. Contractor shall mount external cabinet using alignment strips and rails provided. Then cabinet access panels shall be installed using supplied tool-less snap-in fasteners. 7. No power or direct control connections shall be required for the operation of the chilled beam. 3.03 Cleaning and Protection 1. Air and water connections shall be covered before shipment and remain so until final installation. Damaged material due to...

カタログの16ページ目を開く
YORK® HORIZONTAL RECESSED ACTIVE CHILLED BEAMS - 17

For more information www.york.com/chilledbeams Johnson Controls, the Johnson Controls logo, and YORK® are trademarks of Johnson Controls, Inc., or its affiliates, in the United States of America and/or other countries. r2016 Johnson Controls, Inc., P.O. Box 423, Milwaukee, WI 53201 Printed in USA www.johnsoncontrols.com