Halton FDS
1 / 7ページ

{{requestButtons}}

カタログの抜粋

Halton FDS - 1

Multi-blade-type Fire Damper for Rectangular and Circular Ducts • Type-approved unit compliant with the EN 1366-2 and EN 13501-3 standards. • Fire resistance class ES 60. • Possibility of use as an EIS 60 damper with additional duct insulation (as indicated in national building code). • Installation in separating concrete or masonry walls and ceilings and for lightweight plasterboard walls. • Possibility of wall installation in both vertical and horizontal blade direction. • External quality control management by VTT, the Technical Research Centre of Finland. • Manufacture in accordance with the ISO 9001 quality standard. • Suitability for rectangular ducts from size 200 mm x 200 mm to 1500 mm x 800 mm. • Fire damper casing tightness compliant with EN 1751, Class C. • Suitability for use in ducts with a maximum pressure of 3300 Pa and maximum air speed of 15 m/s. Product models and Accessories • Several automatic release and position indication options • Models equipped with either electrical or pneumatic actuators • Modular damper casing extension for different wall thicknesses • Option of circular connection FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts

カタログの1ページ目を開く
Halton FDS - 2

V Vertical blade direction only H Horizontal blade direction only X Both horizontal and vertical blade direction allowed FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts

カタログの2ページ目を開く
Halton FDS - 3

ACCESSORIES AND PRODUCT MODELS Actuators Pneumatic, AT100 (rotating actuator), P0 Belimo BF 24-T-2 HL, operating voltage AC/DC 24 V (fuse: 72 °C, includes limit switch), B1 Belimo BF 230-T-2 HL, operating voltage AC 230 V (fuse: 72 °C, includes limit switch), B2 ACCESSORIES The fire damper can be equipped with a bipolar limit switch, which indicates the closing of the shut-off blade. The limit switch has potential-free contacts (no=normally open and nc=normally closed), which can be used to control other fire dampers equipped with an electric release (e.g., triggering an alarm in the fire...

カタログの3ページ目を開く
Halton FDS - 4

FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts Function The FDS is a rectangular fire damper, which prevents fire and smoke from spreading in ventilation ducts. Approved fire resistance classes are (EN 1366-2): ■ Ceilings: ES 60 ■ Walls: ES60, E90 (both concrete/masonry and lightweight walls) The fire damper is equipped with either an electrical or pneumatic actuator. Under all options, a fuse responds to a rise in temperature, causing a spring-return blade to close. Alternatively, the damper may be released by a system using an electric motor or using solenoids...

カタログの4ページ目を開く
Halton FDS - 5

Electric actuator wiring diagram A Connect via safety isolating transformer! 230 VAC **) PNEU. INLET (5-10 BAR) FOR A PLASTIC TUBE 0 6 MM 1 SPRING-RETURN ACTUATOR 2 QUICK EXHAUST VALVE 4 FUSIBLE LINK VALVE 5 OPTION: SOLENOID VALVE 9 OPTION: OPEN/CLOSED SWITCHES 10 OPTION: MANUAL VALVE NOTE: ADDITIONAL SOLENOID VALVE MAX. 10 METRES FROM FIRE DAMPER - Multi-blade-type Fire Damper for Rectangular and Circular Ducts Malton 5

カタログの5ページ目を開く
Halton FDS - 6

Servicing To ensure proper operation of the fire dampers, they should be inspected regularly. It is recommended that the fire damper be connected to automatic control and testing system MSH (24-V system). Dampers not connected to an automatic testing system shall be tested periodically. The minimum recommended inspection period is one year or according to building code. An inspection opening shall be installed in the proximity of the fire damper as indicated in the building code (not part of the product). Upon failure during testing of the fire damper, maintenance service shall be ordered...

カタログの6ページ目を開く
Halton FDS - 7

Product code FDS/S-W-H-D S = Type of duct connections R Rectangular connections W = Width S=R: 200, +50, ..., 1500 H = Height S=R: 200, 300, +50, ..., 800 D = Connection size S=C: 630, 800 Specifics and accessories RE = Release type B1 BF-24-T-2 HL, fuse: 72 °C AC = Accessories CE Casing extension, 210 mm, for structural thickness > 200 mm L2 Limit switches, 2 pcs, Bernstein, with pneumatic motor M1 Solenoid valve, 24 VAC, with pneumatic motor M2 Solenoid valve, 230 VAC, with pneumatic motor N1 Safety mesh, 1 side, installed in actuator side N2 Safety mesh, 2 sides FDS -...

カタログの7ページ目を開く

HALTONのすべてのカタログと技術パンフレット

  1. Halton USS

    8 ページ

  2. Halton CBD

    8 ページ

  3. FS Halton AHUs

    28 ページ

  4. Halton KCD

    3 ページ

  5. KVE-CM

    7 ページ

  6. KMC - MobiChef

    5 ページ

  7. Halton MobiChef

    12 ページ

  8. R6B

    9 ページ

  9. Halton Vario

    20 ページ

  10. Halton FDR

    6 ページ

  11. Halton FDI

    6 ページ

  12. Halton FDE

    8 ページ

  13. Halton FDC

    5 ページ

  14. ALE/ALU

    8 ページ

  15. AHF

    5 ページ

  16. JTH

    4 ページ

  17. FDC

    5 ページ

  18. AFB

    7 ページ

  19. TCG 2013

    4 ページ

  20. FCU 2013

    6 ページ

  21. FDB2 -

    4 ページ

カタログアーカイブ

  1. HALTON-POLLUSTOP

    4 ページ

  2. UNIPOINT

    4 ページ

  3. HALTON-KVD

    6 ページ

  4. HALTON-KCE

    10 ページ

  5. HALTON-KSK

    6 ページ

  6. KCJ

    12 ページ