OMNIZONE? 50XCW06-24 Water-Cooled
1 / 44ページ

{{requestButtons}}

カタログの抜粋

OMNIZONE? 50XCW06-24 Water-Cooled - 1

Product Data OMNIZONE™ 50XCW06-24 Water-Cooled Indoor Self-Contained Systems with PURON® Refrigerant (R-410A) 5 to 20 Nominal Tons The 50XCW single-package watercooled units with integral air-cooled condensers offer: • Compact, durable, and attractive cabinet fits any working environment • Ducted or free return with rear return connections with vertical supply air discharge • High-efficiency cooling for commercial and industrial projects • Puron® refrigerant (R-410A) Features/Benefits The Omnizone 50XCW units provide a practical and economical approach to comfort conditioning requirements for offices, factories, and other applications in existing buildings when indoor aircooled condensers are required. Design flexibility The 50XCW water-cooled indoor packaged units are designed to provide the flexibility required in replacement, renovation, and new construction. Units are available in 6 sizes from 5 tons to 20 tons which meet the needs for cooling restaurants, retail stores, warehouses, offices, and building additions. a50-8527 Copyright 2011 Carrier Corporation Form 50XCW-2PD

カタログの1ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 2

Features/Benefits (cont) The compact footprint and service from the front of the units save valuable floor space in equipment rooms. Belt drive motors provide adequate static to overcome ducting and louver static losses. These units can be installed in the equipment room or the conditioned space and used for either ducted or free return applications. Unit supply air discharge is vertical. Easy installation and maintenance The units are completely pre-piped and wired at the factory to ensure time and money saving installation and service. Exterior access panels are easily removed to provide...

カタログの2ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 3

Model number nomenclature 50XC W 24 A A – G 5 A A – 0 AA Factory-Installed Options Code See codes in unit price pages 50XC – OMNIZONE™ Indoor Packaged Unit Condenser Option W – Water-Cooled Design Revision Level 0 – Original Release Unit Size – Nominal Tons 06 – 5 14 – 12 08 – 7.5 16 – 15 12 – 10 24 – 20 Reserved for later use Condenser Coil Options A – No Low Ambient Option, No Service Valve, No Strainer Water Connections/Discharge Air Options A – Right Hand, Vertical Discharge, Ducted E – Right Hand, Horizontal Discharge, Ducted Control Options A – Standard Controls Heating Coil Options A...

カタログの3ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 5

Dimensions — 50XCW06,08 REAR RETURN, VERTICAL DISCHARGE SIZE SIZE UNIT 50XCW 06 08 WIDTH HEIGHT DEPTH COND SECTION EVAP SECTION A 53.1 53.1 B 57.0 57.0 C 29.0 29.0 D 25.8 25.8 E 31.0 31.0 NOTE: Dimensions are in inches. WATER RETURN CONN EVAPORATOR RETURN DUCT F 47.2 47.2 G 24.8 24.8 H 28.9 28.9 I 4.8 4.8 J 14.4 14.4 K 23.0 23.0 WATER SUPPLY CONN L 22.9 22.9 M 7.5 7.5 EVAP SUPPLY DUCT (Blower Opening) N 13.4 13.4 O 12.8 12.8 P 2.7 2.7 Q 19.8 7.6 SUPPLY/ RETURN DIAMETER (OD) R 1.625 1.625 a50-8667 5

カタログの5ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 6

Dimensions — 50XCW12,14 REAR RETURN, VERTICAL DISCHARGE UNIT 50XCW 12 14 WIDTH A 68.0 68.0 HEIGHT DEPTH B 64.0 64.0 C 31.2 31.2 NOTE: Dimensions are in inches. 6 COND SECTION EVAP SECTION D 28.0 28.0 E 35.5 35.5 EVAPORATOR RETURN DUCT F 61.1 61.1 G 31.8 31.8 H 29.4 29.4 I 5.5 5.5 WATER RETURN CONN J K 17.7 22.7 17.7 22.7 WATER SUPPLY CONN L M 10.8 4.2 10.8 4.2 EVAP SUPPLY DUCT (Blower Opening) N 12.5 12.5 O 13.8 13.8 P 8.5 8.5 Q 13.6 13.6 SUPPLY/ RETURN DIAMETER (OD) R 2.125 2.125 a50-8668

カタログの6ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 7

REAR RETURN, VERTICAL DISCHARGE WITH HEAD PRESSURE CONTROL (HPC) UNIT 50XCW 12 14 WIDTH A 68.0 68.0 HEIGHT DEPTH B 64.0 64.0 C 31.2 31.2 NOTE: Dimensions are in inches. COND SECTION EVAP SECTION D 28.0 28.0 E 35.5 35.5 EVAPORATOR RETURN DUCT F 61.1 61.1 G 31.8 31.8 H 29.4 29.4 I 5.5 5.5 WATER RETURN CONN J K 17.7 22.7 17.7 22.7 WATER SUPPLY CONN L M 25.6 10.1 25.6 10.1 EVAP SUPPLY DUCT (Blower Opening) N 12.5 12.5 O 13.8 13.8 P 8.5 8.5 Q 13.6 13.6 SUPPLY/ RETURN DIAMETER (OD) R 2.125 2.125 a50-8669 7

カタログの7ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 8

Dimensions — 50XCW12,14 (cont) REAR RETURN, FRONT DISCHARGE UNIT 50XCW 12 14 WIDTH A 68.0 68.0 HEIGHT DEPTH B 64.0 64.0 C 31.2 31.2 NOTE: Dimensions are in inches. 8 COND SECTION EVAP SECTION D 28.0 28.0 E 35.5 35.5 EVAPORATOR RETURN DUCT F 61.1 61.1 G 31.8 31.8 H 29.4 29.4 I 5.5 5.5 WATER RETURN CONN J K 17.7 22.7 17.7 22.7 WATER SUPPLY CONN L M 10.8 4.2 10.8 4.2 EVAP SUPPLY DUCT (Blower Opening) N 12.5 12.5 O 13.8 13.8 P 2.7 2.7 Q 13.6 13.6 a50-8670 SUPPLY/ RETURN DIAMETER (OD) R 2.125 2.125

カタログの8ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 9

REAR RETURN, FRONT DISCHARGE WITH HEAD PRESSURE CONTROL (HPC) UNIT 50XCW 12 14 WIDTH A 68.0 68.0 HEIGHT DEPTH B 64.0 64.0 C 31.2 31.2 NOTE: Dimensions are in inches. COND SECTION EVAP SECTION D 28.0 28.0 E 35.5 35.5 EVAPORATOR RETURN DUCT F 61.1 61.1 G 31.8 31.8 H 29.4 29.4 I 5.5 5.5 WATER RETURN CONN J K 17.7 22.7 17.7 22.7 WATER SUPPLY CONN L M 25.6 10.1 25.6 10.1 EVAP SUPPLY DUCT (Blower Opening) N 12.5 12.5 O 13.8 13.8 P 2.7 2.7 Q 13.6 13.6 SUPPLY/ RETURN DIAMETER (OD) R 2.125 2.125 a50-8671 9

カタログの9ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 10

Dimensions — 50XCW16,24 REAR RETURN, VERTICAL DISCHARGE UNIT 50XCW 16 24 WIDTH A 88.0 88.0 HEIGHT DEPTH B 66.7 70.8 C 31.2 31.2 NOTE: Dimensions are in inches. 10 COND SECTION EVAP SECTION D 31.2 31.2 E 35.5 39.5 WATER RETURN CONN EVAPORATOR RETURN DUCT F 81.0 81.5 G 31.8 35.8 H 33.2 33.3 I 5.5 5.5 J 17.8 17.8 K 22.8 22.8 WATER SUPPLY CONN L 10.7 10.7 M 4.2 4.2 EVAP SUPPLY DUCT (Blower Opening) N 12.5 14.9 O 13.8 13.8 P 8.5 8.6 a50-8672 Q 13.5 8.3 S 11.7 13.2 SUPPLY/ RETURN DIAMETER (OD) R 2.625 2.625

カタログの10ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 11

REAR RETURN, VERTICAL DISCHARGE WITH HEAD PRESSURE CONTROL (HPC) UNIT 50XCW 16 24 WIDTH A 88.0 88.0 HEIGHT DEPTH B 66.7 70.8 C 31.2 31.2 NOTE: Dimensions are in inches. COND SECTION EVAP SECTION D 31.2 31.2 E 35.5 39.5 WATER RETURN CONN EVAPORATOR RETURN DUCT F 81.0 81.5 G 31.8 35.8 H 33.2 33.3 I 5.5 5.5 J 17.8 17.8 K 22.8 22.8 WATER SUPPLY CONN L 25.6 25.6 M 10.1 10.1 EVAP SUPPLY DUCT (Blower Opening) N 12.5 14.9 O 13.8 13.8 P 8.5 8.6 Q 13.5 8.3 S 11.7 13.2 SUPPLY/ RETURN DIAMETER (OD) R 2.625 2.625 a50-8673 11

カタログの11ページ目を開く
OMNIZONE? 50XCW06-24 Water-Cooled - 12

Dimensions — 50XCW16,24 (cont) REAR RETURN, FRONT DISCHARGE UNIT 50XCW 16 24 WIDTH A 88.0 88.0 HEIGHT DEPTH B 66.7 70.8 C 31.2 31.2 NOTE: Dimensions are in inches. 12 COND SECTION EVAP SECTION D 31.2 31.2 E 35.5 39.5 WATER RETURN CONN EVAPORATOR RETURN DUCT F 81.0 81.5 G 31.8 35.8 H 33.2 33.3 I 5.5 5.5 J 17.8 17.8 K 22.8 22.8 WATER SUPPLY CONN L 25.6 25.6 M 10.1 10.1 EVAP SUPPLY DUCT (Blower Opening) N 12.5 14.9 O 13.8 13.8 P 2.6 2.6 Q 13.5 8.3 S 11.7 13.2 SUPPLY/ RETURN DIAMETER (OD) R 2.625 2.625 a50-8674

カタログの12ページ目を開く

CARRIER commercialのすべてのカタログと技術パンフレット

  1. 40UV-UH-14SI

    32 ページ

  2. 42B-6SI

    24 ページ

  3. A WORLD OF COMFORT

    20 ページ

  4. A World of Comfort

    2 ページ

  5. 19DV

    32 ページ

  6. 30XA

    136 ページ

  7. 30RAP

    104 ページ

  8. Carrier VRF

    44 ページ

  9. A World of Comfort

    2 ページ

  10. ComfortVIEW 3

    6 ページ

  11. VVT Zoning System

    8 ページ

  12. Comfort? Series

    2 ページ

  13. GEMINI? 38AKS028-044

    40 ページ

カタログアーカイブ