climaVAIR
24Pages

{{requestButtons}}

Catalog excerpts

climaVAIR - 3

For the fitter VAM 2-050 W2N VAM 2-060 W2N VAM 2-085 W3N VAM 2-110 W4N Installation Manual Air-conditioner - climaVAIR Split Type EN

Open the catalog to page 3
climaVAIR - 4

2 Contents Split Type Installation Manual Contents 1 Your Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.1 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Correct Use of the Unit . . . . . . . . . . . . . . . . . . . . . . . 3 2 Extreme Operating Conditions . . . . . . . . . . . . . .3 3 Identification of the Unit . . . . . . . . . . . . . . . . . .3 4 Declaration of Conformity . . . . . . . . . . . . . . . . 4 5 Description of the Unit . . . . . . . . . . . . . . . . . . . 4 5.1 Indoor Unit . . . . . . . . . . . . . . . . . . . . . . ....

Open the catalog to page 4
climaVAIR - 5

Split Type Installation Manual EN 3 1 Your Safety 1.1 Symbols used Danger! Direct danger for life and health. Danger! Danger of electric shock. Warning! Potentially dangerous situation for the product and the environment. Note! Useful information and indications. 1.2 Correct Use of the Unit This unit has been designed and manufactured for the sole purpose of comfort cooling and heating occupied residential and commercial premises. The use thereof for other domestic or industrial purposes shall be the exclusive responsibility of the persons specifying, installing or using them in that way....

Open the catalog to page 5
climaVAIR - 6

4 Split Type Installation Manual 4 Declaration of Conformity The manufacturer declares that this unit has been designed and constructed in compliance with the standard in force with regard to obtaining the CE Marking. 5 Description of the Unit This unit is comprised of the following elements: - Indoor unit. - Outdoor unit. - Remote controller. - Connections and accessories. Figure 5.1 shows the unit components. Fig. 5.1 Unit components. Legend 1 Indoor Unit 2 Outdoor Unit 3 Remote controller 4 Interconnecting pipework (not supplied) 5 Condensed water drainage pipe 5.1 Indoor Unit The indoor...

Open the catalog to page 6
climaVAIR - 7

Split Type Installation Manual EN 5 5.2 Outdoor Unit The outdoor unit ensures that the absorbed heat is released to the outside from the room during operation in cooling mode and that the heat introduced into the room during operation in heat pump mode is taken from the outside. The dimensions and weights of the outdoor unit are shown on Figure 5.3 and Table 5.2, depending on the model (please consult the model nameplate). The dimensions are given in mm. Fig. 5.3 Dimensions of the outdoor unit. Legend H Height L Length D Depth A Length of valves B Distance between valves C Distance from the...

Open the catalog to page 7
climaVAIR - 8

6 Split Type Installation Manual 5.3 Infra red Controller The remote control allows using the unit. 5.4 Valve Connections This outdoor unit has the following connections and shut off valves: - Gas (G) and liquid connections (L): they carry the refrigerant between the outdoor and indoor unit. - Discharge connections for condensate water (in the outdoor and indoor unit): they allow the water to be properly discharged which condenses during the normal operation of the unit. - Electric connections: these supply electric energy to the unit. 5.5 Supplied Accessories This unit is provided with the...

Open the catalog to page 8
climaVAIR - 9

Split Type Installation Manual EN 7 5.6 Technical Specifications Units VAM 2-050 W2N VAM 2-060 W2N VAM 2-085 W3N VAM 2-110 W4N Power supply V/Ph/Hz 230/1/50 Cooling Capacity kW 5,20 5,40 8,10 9,10 Power input kW 1,62 1,66 2,48 2,78 Operating current A 7,00 7,20 10,80 12,10 Heating Capacity kW 6,10 6,25 9,05 10,10 Power input kW 1,67 1,73 2,49 2,78 Operating current A 7,30 7,50 10,80 12,10 Indoor Unit Air Flow volume 1 m3/h 250/300/500 250/300/500 250/300/500 250/300/500 Air Flow volume 2 m3/h 250/300/500 310/450/580 250/300/500 250/300/500 Air Flow volume 3 m3/h / / 310/450/580 250/300/500...

Open the catalog to page 9
climaVAIR - 10

8 Split Type Installation Manual 6 Transport Danger of injury and physical damage! During transport and unloading, the unit could fall and injure anyone within the immediate vicinity. To avoid this: - Only use transport and lifting gear with suitable load capacity for the unit weight. - Use only the transport and lifting gear correctly (consult the respective user manuals). - Use the slinging points provided for this purpose on the unit. - Secure the unit correctly using propriety fixings in the mounting points provided. - Always use suitable personal protection equipment (helmet, gloves,...

Open the catalog to page 10
climaVAIR - 11

Split Type Installation Manual EN 9 8.3 General Installation Diagram Warning! Danger of breakdowns or malfunction. Observe the minimum clearences indicated in Figure 8.1. Fig. 8.1 General diagram of the installation and the minimum assembly distances. Legend 1 Indoor Unit 2 Outdoor Unit 3 Condensate connection for outdoor unit A Clearance to the front of the internal unit (minimum 10 cm) B Clearance to ceiling above (minimum 5 cm) D Height in relation to the floor (minimum 2 m) E Side clearance opposite side connections (minimum 20 cm) F Rear clearance (minimum 20 cm) G Side clearance...

Open the catalog to page 11
climaVAIR - 12

10 Split Type Installation Manual 9.3 Installation of the Pipe Work 9.3.1 Correct Removal of Condensate Water Warning! Danger of breakdowns or malfunction. Danger of condensed water leakage. In order to ensure that the unit drains correctly take the recommendations described in this section into account. Methods for the removal of the condensed water which is generated in the indoor unit: - Condensed water can be allowed to drain naturally using the natural fall of the condensed water pipe to a suitable drain point. In order for it to be aesthetically pleasing, use a solid pipework or...

Open the catalog to page 12
climaVAIR - 13

Split Type Installation Manual EN 11 9.3.3 Correct Installation of the Condensate Pipe Work Warning! Danger of breakdowns or malfunction. Danger of water leaks and blockages from unit and pipework: - Ensure that sufficient air breaks and traps are provided to avoid water being retained within the indoor unit. Otherwise, the condensed water could leak from the indoor unit. - For gravity drains ensure fall is sufficient, the pipework is adequately supported and does not sag and bends are of large radius to avoid blockages. - If the water pipe is run outdoors, ensure that it is insulated...

Open the catalog to page 13

All VAILLANT catalogs and technical brochures

  1. sensoCOMFORT

    6 Pages

Archived catalogs