V-COOL Catalogue 2007 (Heat Pump & Air conditioner) - 2 Pages

Brine systems are built in 3 designs:
- Standard flat-collectors are positioned 120 to 140 cm below ground level
- Trenches which use less surface for collectors
- Earth taps with up to 100 m depth use mainly geothermal energy (Recommended
if there is not enough only little area in the garden)
BWA Series
(With water tank)
DRIER FILTER
EXPANSION VALVE
COMPRESSOR
CONTROL
(INDUCATION KEY)
WATER TANK
(STAINLESS STEEL)
3 WAY VALVE FOR HEATING
CIRCUIT AND HOT VATER
WATER PUMP
ELECTRICAL HEATING
STAINLESS STEEL PLATE
HEAT EXCHANGER
Connnections:
1.Electrical lead-in for main power supply
2.Lead-in for communication cable
3.Feed line radiators 28Cu
4.Retum line radiators 28Cu
5.Cold water connection(cw) 22Cu
6.Hot water connection(cw) 22Cu
7.Expansion R25
8.Cooling medium in(to HP)* 28Cu
9.Cooling medium out(to HP)* 28Cu
*)Connection can be made from either the left or right side.
SYSTEM WATER SYSTEM
INSTALLATION MASTER PLAN
SPECIFICATION
MODEL Performance at Heating Capacity Power Cop Supply power Auxiliary heater Refrigerant Compressor Heat exchanger Water tank Flow Temperature Dimensions(HxWxD) Weight
SS KW KW V/Ph/Hz KW L C mm Kg
B0/W35 5.5 1.3 4.2
B0/W50 5.0 1.7 2.9
B0/W60 4.9 2.2 2.2
6 230/1/50 3 R407C Rotary (1) PBHE/PBHE 150 65 1780x600x650 245
GROUND SOURCE WITH BRINE ALL IN ONE
B0/W35 8.0 1.8 4.3
B0/W35 10.0 2.2 4.4
B0/W35 12.0 2.7 4.4
B0/W35 15.7 3.7 4.3
B0/W50 7.0 2.3 3.0
B0/W50 9.1 2.9 3.1
B0/W50 10.4 3.3 3.1
B0/W50 14.7 4.6 3.2
B0/W60 6.7 3.0 2.2
B0/W60 8.9 3.6 2.4
B0/W60 10.1 4.2 2.4
B0/W60 14.4 5.7 2.5
8 230/1/50 3/6 R407C Rotary (1) PBHE/PBHE 150 65 1780x600x650 247
10 400/3/50 3/6/9 R407C Scroll (1) PBHE/PBHE 150 65 1780x600x650 250
12 400/3/50 3/6/9 R407C Scroll (1) PBHE/PBHE 200 65 1780x600x650 278
16 400/3/50 3/6/9 R407C Scroll (1) PBHE/PBHE 200 65 1780x600x650 283
In accordance with En255.
C L
H E A T P U M P
9
8
3
2 1
4 7
5 6
GOA
C
S
E
R410a R407c
GO
A
C
S
E
BWB Series
DRIER FILTER
EXPANSION VALVE
COMPRESSOR
CONTROL
(INDUCATION KEY)
3 WAY VALVE FOR HEATING
CIRCUIT AND HOT VATER
WATER PUMP
ELECTRICAL HEATING
STAINLESS STEEL PLATE
HEAT EXCHANGER
Connnections:
1.Electrical lead-in for main power supply
2.Lead-in for communication cable
3.Feed line radiators 28Cu
4.Retum line radiators 28Cu
5.Feed line radiators 28Cu
6.Retum line radiators 28Cu
7.Expansion R25
8.Cooling medium in(to HP)* 28Cu
9.Cooling medium out(to HP)* 28Cu
*)Connection can be made from either the left or right side.
SYSTEM WATER SYSTEM
INSTALLATION MASTER PLAN
GROUND SOURCE WITH BRINE SPLIT TYPE
Brine systems are built in 3 designs:
- Standard flat-collectors are positioned 120 to 140 cm below ground level
- Trenches which use less surface for collectors
- Earth taps with up to 100 m depth use mainly geothermal energy (Recommended
if there is not enough only little area in the garden)
SPECIFICATION
MODEL Performance at Heating Capacity Power Cop Supply power Auxiliary heater Refrigerant Compressor Heat exchanger Water tank Flow Temperature Dimensions(HxWxD) Weight
SS KW KW V/Ph/Hz KW L C mm Kg
B0/W35 12.0 2.7 4.4
B0/W50 10.4 3.3 3.1
B0/W60 10.1 4.2 2.4
12 400/3/50 3/6/9 R407C Scroll (1) PBHE/PBHE 260 65 1150x600x650 148
B0/W35 15.7 3.7 4.3
B0/W35 18.8 4.3 4.4
B0/W50 19.8 6.4 3.1
B0/W35 32.0 8.2 3.9
B0/W50 14.7 4.6 3.2
B0/W50 17.8 5.5 3.2
B0/W35 25.3 5.7 4.4
B0/W50 30.0 10.7 2.7
B0/W60 14.4 5.7 2.5
B0/W35 21.0 4.6 4.5
B0/W50 22.3 7.4 3.0
16 400/3/50 3/6/9 R407C Scroll (1) PBHE/PBHE 300 65 1150x600x650 153
20 400/3/50 3/6/9 R407C Scroll (2) PBHE/PBHE 300 55 1150x600x650 188
25 400/3/50 3/6/9 R407C Scroll (2) PBHE/PBHE 360 55 1150x600x650 195
40 400/3/50 3/6/10 R407C Scroll (2) PBHE/PBHE 500 55 1150x600x650 220
33 400/3/50 3/6/9 R407C Scroll (2) PBHE/PBHE 360 55 1150x600x650 205
In accordance with En255.
C L
H E A T P U M P
9
8
3 2 1
5 7
4
6
GOA
C
S
E
R410a R407c
GO
A
C
S
E
WWA Series
(With water tank)
DRIER FILTER
EXPANSION VALVE
COMPRESSOR
CONTROL
(INDUCATION KEY)
WATER TANK
(STAINLESS STEEL)
3 WAY VALVE FOR HEATING
CIRCUIT AND HOT VATER
WATER PUMP
ELECTRICAL HEATING
STAINLESS STEEL PLATE
HEAT EXCHANGER
Connnections:
1.Electrical lead-in for main power supply
2.Lead-in for communication cable
3.Feed line radiators 28Cu
4.Retum line radiators 28Cu
5.Cold water connection(cw) 22Cu
6.Hot water connection(cw) 22Cu
7.Expansion R25
8.Cooling medium in(to HP)* 28Cu
9.Cooling medium out(to HP)* 28Cu
*)Connection can be made from either the left or right side.
SYSTEM WATER SYSTEM
INSTALLATION MASTER PLAN
WATER SOURCE ALL IN ONE
TUBE IN TUBE EVAPORATOR
SPECIFICATION
MODEL Performance at Heating Capacity Power Cop Supply power Auxiliary heater Refrigerant Compressor Heat exchanger Water tank Flow Temperature Dimensions(HxWxD) Weight
SS KW KW V/Ph/Hz KW L C mm Kg
W10/W35 5.6 1.0 5.6
W10/W50 4.5 1.2 3.7
W10/W60 4.0 1.5 2.7
6 230/1/50 3 R407C Rotary (1) Titanium/PBHE 150 65 1780x600x650 245
W10/W35 7.5 1.4 5.4
W10/W35 9.6 1.7 5.8
W10/W35 12.4 2.1 5.7
W10/W35 15.3 2.7 5.8
W10/W50 6.6 1.8 3.7
W10/W50 8.4 2.2 3.8
W10/W50 11.3 2.9 3.9
W10/W50 14.3 3.6 4.0
W10/W60 6.1 2.2 2.8
W10/W60 8.0 2.8 2.8
W10/W60 10.5 3.5 3.0
W10/W60 13.1 4.6 2.8
8 230/1/50 3/6 R407C Rotary (1) Titanium/PBHE 150 65 1780x600x650 247
10 400/3/50 3/6/9 R407C Scroll (1) Titanium/PBHE 150 65 1780x600x650 250
12 400/3/50 3/6/9 R407C Scroll (1) Titanium/PBHE 200 65 1780x600x650 278
16 400/3/50 3/6/9 R407C Scroll (1) Titanium/PBHE 200 65 1780x600x650 283
In accordance with En255.
C L
H E A T P U M P
The ideal heat source is ground-water because of its relatively high temperature of
8 to 12 C all the year round. The water must be available at a reasonable depth,
With sufficient quantity, quality and without contamination.
The ground water is taken from a source-well and sink well
to the heat pump and pumped back into the ground is the
sink-well at some 15 m distance.
9
8
3
2 1
4 7
5 6
GO
A
C
S
E
R410a R407c
GO
A
C
S
E
GROUND SOURCE HEAT PUMP
AIR SOURCE HEAT PUMP
WATER SOURCE HEAT PUMP
GROUND SOURCE HEAT PUMP
AIR SOURCE HEAT PUMP
WATER SOURCE HEAT PUMP
GROUND SOURCE HEAT PUMP
AIR SOURCE HEAT PUMP
WATER SOURCE HEAT PUMP
E-mail: fengsimiao@gmail.com / info@vtcool.com.cn Tel:0086 757 28807767 26278643
Fax:0086 757-28812659
C L
H E A T P U M P
V-COOL ELECTRICAL HOLDINGS CO., LIMITED.
Add:daliang, Shunde, Foshan City Of Guangdong, China.
Basing on china serving world
Http//www.vtcool.com.cn

V-COOL Catalogue 2007 (Heat Pump & Air conditioner)
  1. P. 1

  2. P. 2

    AWA Series AIR SOURCE ALL IN ONEDRIER FILTEREXPANSION VALVECOMPRESSORCONTROL(INDUCATION KEY)WATER TANK(STAINLESS STEEL)3 WAY VALVE FOR HEATINGCIRCUIT AND...
Text version

All V-COOL Electrical Holdings Co.,Limited catalogues and technical brochures