Catalogue SMMS R410A VRF inverter
www.toshiba-aircon.com
print switch display
Page / 1
Where to buy
this product ?
TOSHIBA air conditioning - 24157, 110055
/ 1
See other catalogues for TOSHIBA air conditioning
Text version of the page
TOSHIBA
Technical specifications heat pump manufacturer
Outdoor unit
CO
MAP0501T8
MAP0601T8
MAP0801T8
MAP1001T8
MAP1201T8
HP
MAP0501HT8
MAP0601HT8
MAP0801HT8
MAP1001HT8
MAP1201HT8
5 HP
6 HP
8 HP
10 HP
12 HP
Cooling capacity*
kW
14
16
22.4
28
33.5
Power input, cooling
kW
3.65
4.64
5.67
7.67
11.92
EER, cooling
W/W
3.84
3.45
3.95
3.65
2.81
Energy efficiency class, cooling
A
A
A
A
C
Running current, cooling
A
5.85
7.28
8.62
11.55
18.30
Heater capacity**
kW
16
18
25
31.5
37.5
Power input, heating
kW
3.84
4.56
5.88
7.97
10.19
COP, heating
W/W
4.17
3.95
4.25
3.95
3.68
Energy efficiency class, heating
A
A
A
A
A
Running current, heating
A
6.09
7.08
8.93
11.98
15.65
Air flow
m3/h - l/s
9000 - 2520
9000 - 2520
9000 - 2520
9000 - 2520
9000 - 2520
Sound pressure level
dB(A)
55
56
57
58
59
Operating range, cooling - db
°C
-5 - 43°C
-5 - 43°C
-5 - 43°C
-5 - 43°C
-5 - 43°C
Operating range, heating - wb
°C
-20 - 16°C
-20 - 16°C
-20 - 16°C
-20 - 16°C
-20 - 16°C
Dimensions (H x W x D)
mm
1800 x 990 x750
1800 x 990 x750
1800 x 990 x750
1800 x 990 x750
1800 x 990 x750
Weight
kg
228
228
228
228
228
Compressor type
Hermetic
Hermetic
Hermetic
Hermetic
Hermetic
Refrigerant charge R410A
kg
8.5
8.5
12.5
12.5
12.5
Pipework
Suction line type - diameter
in
Flare -5/8
Brazed - 3/4
Brazed - 7/8
Brazed - 7/8
Brazed -1-1/8
Liquid line type - diameter
in
Flare - 3/8
Flare - 3/8
Flare - 1/2
Flare - 1/2
Flare - 1/2
Discharge line connection type - diameter
in
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Flare - 3/8
Maximum equivalent length separation
m
175
175
175
175
175
Maximum actual piping separation
m
150
150
150
150
150
Maximum pipe length
m
300
300
300
300
300
Maximum lift (Indoor unit above/below)***
m
40/50
40/50
40/50
40/50
40/50
Power supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
Based on an indoor air temperature of 27°C db/19°C wb and an outdoor air temperature of 35°C db.
Based on an indoor air temperature of 20°C db and an outdoor air temperature of 7°C db/6°C wb.
If the height difference between indoor units exceeds 3 m and if the indoor unit is above, max. lift is reduced to 30 m.
Protectionrjor
devices.
• Discharge and suction temperature sensors
• Internal overload relay
• Compressor overcurrent relay
• Overcurrent sensor
• High pressure switch
• Low pressure sensors
ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Directory | Specifications | Characteristics
Search Go
page 1 p.1
pdf-page pdf ae En 2008-12-49-03