Catalogue Air-to-Air heat exchangers
www.toshiba-aircon.com
print switch display
Page / 1
Where to buy
this product ?
TOSHIBA air conditioning - 110055
/ 1
See other catalogues for TOSHIBA air conditioning
Text version of the page
TOSHIBA
75
Technical specifications air-to-air heat exchanger
Outdoor unit
VN-250SE
VN-350SE
VN-500SE
VN-800SE
VN-1SAE
Air flow (h/l)
m3/h - l/s
250/170 - 70/48
350/280 - 98/78
500/370 - 140/104
800/650 - 224/182
1000/810 - 218/227
Temperature exchange efficiency (h/l)
%
75/77
75/77
75/77
75/77
75/77
Sound pressure level (h/l)
dB(A)
Heat reclaim mode
27/22
30/26
32/36
37.5/34
37/33
Bypass mode
27.5/22.5
31/27
33/27.5
38/35
37.5/33.5
Operating range
°C
-10 - 40°C
-10 - 40°C
-10 - 40°C
-10 - 40°C
-10 - 40°C
Power input (h/l)
W
Heat reclaim mode
114/90
137/128
188/166
329/327
391/359
Bypass mode
114/90
132/125
182/164
325/316
85/355
Enthalpy exchange efficiency (h/l)
%
70/73
69/71
67/71
71/74
71/74
Cooling
%
63/66
66/69
62/67
65/68
65/68
Max. external static pressure (h/l)
Pa
80/37
65/42
70/38
110/70
55/35
Dimensions (H x W x D)
mm
270 x 599 x 882
270 x 804 x 882
270 x 904 x 962
388 x 884 x 1322
388 x 1134 x 1322
Weight
kg
29
37
43
71
83
Duct diameter
mm
150
150
200
250
250
Filtration efficiency grade (EU3)
%
82
82
82
82
82
Power supply
V-ph-Hz
220/240-1-50
220/240-1-50
220/240-1-50
220/240-1-50
220/240-1-50
Maximum relative humidity
%
85
85
85
85
85
ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Directory | Specifications | Characteristics