Maxi Air Handling Unit
16Pages

{{requestButtons}}

Catalog excerpts

Maxi Air Handling Unit - 1

Specification data www.systemair.com Rotovex SR 07-11 IAQ Air handling units Airflow 2200-4000 m3/h

Open the catalog to page 1
Maxi Air Handling Unit - 2

2 Rotovex SR IAQ is a series of efficient ventilation units de - signed for schools, shops and offices, etc. The units are complete with controls and are delivered ready for operation. They are compact in design, have very low energy consumption and have high-efficiency rotating heat exchangers. The compact design Rotovex units are very compact and will fit through door openings with a width of 800 mm. Rotovex units can easily be divided into two parts, each of which is 772 mm wide. It could not be easier! Rotovex units are delivered pre-programmed, tested and ready for installation....

Open the catalog to page 2
Maxi Air Handling Unit - 3

3 When the unit is delviered with constant duct pressure (VAV) two DSG 500 pressure sensors are enclosed. The unit is pre-programmed to regulate the temperature through cascade connected extract regulation. General Rotovex units are delivered enclosed in plastic and mounted on pallets. The units are fully connected internally. The automatic control system is preset and has been test-run at the factory. Cables for external components (supply, extract and outdoor air temperature sensors, outdoor air and exhaust air dampers, cooling, etc) are attached to a connection block on the end of the...

Open the catalog to page 3
Maxi Air Handling Unit - 4

4 situation, the unit will re-start when the alarm has been ack nowledged and the overheat protection has returned to its normal state. If the man - ual protection is triggered, the electric heating coil must be removed for inspection and resetting. The heating coils are available in: Rotovex SR07 IAQ: 3 alt. 12 kW. Rotovex SR09 IAQ: 4,5 alt. 15 kW. Rotovex SR11 IAQ: 6, 12 or 24 kW. Electric heater (above 6 KW) has separate incoming power supply. The power demand of the electric heating coil is controlled by a triac power regulator (Pulser) according to the desired supply air temperature,...

Open the catalog to page 4
Maxi Air Handling Unit - 5

5 The units have an outgoing common alarm signal available at terminals (24 V AC, 0.5 A). Control on demand Rotovex have the possibility to control the airflow on demand to carbon dioxide (CO2). The CO2-sensor is easily connected to connection block. The output signal from the sensor can either be an analogue (0…10V DC) or a digital (1/10) signal. When using an analogue signal the airflow is controlled linear between two CO2 (ppm) setpoints. When using a digital signal the unit switch from reduced to normal airflow at the CO2 (ppm) setpoint. The CO2-sensors are accessories. Communication...

Open the catalog to page 5
Maxi Air Handling Unit - 6

6 Accessories SR07 IAQ EL/HW SR09 IAQ EL/HW SR11 IAQ EL/HW E-Tool cable ETC ETC ETC Shut-off damper EFD 60-30 EFD 60-40 EFD 80-40 Valve actuator for HW AQM AQM AQM Valve, 3-way STR15-2.1 STR15-2.1 STR15-2.7 Outdoor set ODS ODS ODS Cooler, cold water* PGK PGK PGK Silencer, supply/exhaust/extract/outdoor * LDR LDR LDR Timer T 120 T 120 T 120 Room temperature sensor TG-R5/PT1000 TG-R5/PT1000 TG-R5/PT1000 Outdoor sensor, wall mount TG-UH/PT1000 TG-UH/PT1000 TG-UH/PT1000 Duct sensor/Exhaust air sensor, duct mounted TG-KH/PT1000 TG-KH/PT1000 TG-KH/PT1000 Filter EU3, Extract air, bag filter BFRO...

Open the catalog to page 6
Maxi Air Handling Unit - 7

7 Accessories EFD – Damper for outdoor/exhaust air Shutter damper EFD is a shut-off damper. The damper is provided with 24 V motors with spring-return actuators. EFD is manufactured to leakage performance class 3 according to EN 1751:1998 Annex C.2. Outdoor/exhaust air damper has the function to prevent the hot water battery to from freezing and also prevent the cold air from cooling down the building if the unit stops. Design The EFD multi-leaf damper comprises a number of opposed blades, swivelling on nylon bearings in a sheet metal framework. The blades are connected via a system of...

Open the catalog to page 7
Maxi Air Handling Unit - 8

8 TG-KH/PT1000 – Temperature sensor (duct) Technical data Temperature range -30...+70°C Time constant* 50 s Protection class IP65 *Time constant = The time the sensor needs to reach 67% of the end value for any temperature change. STR – Water valve/heating water, 3-way STR is a 3-way control valve to control the hot water to the heating battery. The valves have a self-adjusting teflon packing box and a Viton Oring. They are intended for use together with the AQM actuator. Technical data Maximum difference pressure 1,6 MPa. Square flow characteristics. Media temp. -5...+185°C Media Hot,...

Open the catalog to page 8
Maxi Air Handling Unit - 9

9 AQM – Valve motor, water valve A microprocessor based actuator controlled by a 0...10 V signal from Rotovex control system. Supply voltage 24 V AC. The actuator has automatic stroke adjustment. Technical data Supply voltage 24 V AC Control signal 0...10 V Transformer size 6 VA Stroke 20 mm Stroke time 5 s/mm Force 450 N Ambient temp. 0...50°C Storage temp. -40...+60°C Ambient humidity 5...95% RH Cable connection Screw terminals Degree of protec. IP54 This product conforms to the EMC standard CENELEC EN50081-1 och EN50082-1. TG-R5/PT1000 – Temperature sensor (room) Technical data...

Open the catalog to page 9
Maxi Air Handling Unit - 13

13 Dimensions Technical data Rotovex SR07 IAQ EL SR07 IAQ HW SR09 IAQ EL SR09 IAQ HW Voltage/Frequency V/50Hz 400 400 400 400 Phase - 3 3 3 3 Input power, motors kW 2x1.07 2x1.07 2x1.98 2x1.98 Input power, heater battery kW 3 alt. 12 – 4,5 alt. 15 - Fuse A 3x10 alt. 3x25 3x10 3x16 alt. 3x32 3x16 Weight kg 300 300 340 340 Filter, supply- and exhaust air EU7/5 EU7/5 EU7/5 EU7/5 SR11 IAQ EL SR11 IAQ HW Voltage/Frequency V/50Hz 400 400 Phase - 3 3 Input power, motors kW 2x2.95 2x2.95 Input power, heater battery kW 6 alt. 12 or 24 - Fuse A 3x20, 3x32 or 3x50 3x20 Weight kg 375 375 Filter,...

Open the catalog to page 13
Maxi Air Handling Unit - 16

Systemair • Inhouse studio • March 2008 • Art no E8068 Systemair AB • SE-739 30 Skinnskatteberg, Sweden Tel +46 222 440 00 • Fax +46 222 440 99 mailbox@systemair.se • www.systemair.com

Open the catalog to page 16

All Systemair catalogs and technical brochures

  1. SYSAQUA_BLUE_H

    24 Pages

  2. DKIR1

    3 Pages

  3. K 100 M sileo

    10 Pages

  4. MRT Catalogue

    28 Pages

  5. DVu-HP

    8 Pages

  6. AHU Catalogue

    174 Pages

  7. Fan Catalogue

    464 Pages

Archived catalogs

  1. Danvent DV

    82 Pages

  2. Air curtain

    4 Pages

  3. Topvex

    60 Pages

  4. KDRE/KDRD

    8 Pages

  5. Axial Fans

    40 Pages