Catalogue GOLD - air handling units
www.swegon.com
print switch display
Page / 20
Contact the
Manufacturer
Where to buy
this product ?
Request
a Quote
SWEGON - 31623, 110055
/ 20
See other catalogues for SWEGON
Text version of the page
Now with Alternative Heat Exchangers!
RECOnomic Rotary heat exchangers are very economical
The GOLD RX is equipped with the RECOnomic, which is the most effective building heat exchanger on the market. The RECOnomic offers high temperature efficiency, up to 85%, and low pressure drop.
The heat exchanger is driven by a stepping motor, which offers great precision when it comes to controlling the rotor speed and hence the degree of heat recovery. The built-in rotation monitor warns if the heat exchanger due to some impediment isn't rotating. When cooling is required, the heat exchanger operates inversely, recovering cooling energy just as efficiently as it recovers heat.
Its excellent performance optimally lowers the cost of operating the building's heater system. This also limits the size of cooling unit needed, as well as the amount of power consumed for cooling.
GOLD RX
Plate heat exchanger with unique anti-frost protection
The GOLD PX is as standard equipped with bypass and shut-off damper for stepless and automatic regulation of the heat exchanger's heat recovery efficiency.
When the weather is cold and the extract air is humid, freezing is likely inside plate heat exchangers. The GOLD PX is equipped with a highly effective anti-frost protection. This involves measuring the temperature inside the "cold corner" of the heat exchanger and the moisture content in the extract air as well.
The built-in IQnomic control system considers the moisture content in the extract air and computes the lowest permissible temperature without risk of freezing inside the heat exchanger. The control unit regulates the bypass damper to prevent the temperature from dropping below this temperature.
This ensures optimal heat recovery by the plate heat exchanger all year
round! GOLD PX
Complete, tilled and ready-to-use coil heat exchanger from the factory.
The GOLD CX is supplied complete from factory including mounted pipework package with all the components required. The system is filled with liquid, vented, adjusted and performance tested before it is delivered.
This saves you time and money at the site!
The pipework package's valve is used to variably regulate the heat recovery efficiency of the coil heat exchanger and the circulation pump is demand controlled.
When the weather is cold and the extract air is humid, freezing is likely inside coil heat exchangers. The GOLD CX is equipped with highly effective anti-frost protection that measures the temperature of the liquid in the extract air coil and also measures the mois­ture content in the extract air.
The built-in IQnomic control system considers the moisture content, computes the lowest permissible temperature of the liquid without risk of freezing. The control unit regulates the valve in the pipework package to prevent the temperature from dropping below this temperature.
This ensures optimal heat recovery generated by the coil heat exchanger all year round!
GOLD CX
3
Due to its policy of continuous product development and improvement, Swegon reserves the right to alter specifications without notice.
ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
pdf-page pdf ae En 2008-12-49-05