Catalogue Xeon 30ff
www.saunierduval.com
print switch display
Page / 40
Saunier Duval - 5833, 798
/ 40
See other catalogues for Saunier Duval
Text version of the page
1 General Data
1.12 Boiler Clearances
Refer to diagram 1.3.
This boiler must be positioned so that at least the minimum operational and servicing clearances are provided.
Additional clearances may be required for installation.
If fixtures are positioned next to the boiler they should be made removable for access to pipework.
At least a minimum clearance of 500mm must be left in front of the boiler for servicing, see diagram 1.3.
1.13 Room Ventilation
The boiler is room sealed and does not require the room or space containing it to have permanent air vents.
1.14 Boilers in a Compartment
Where the installation of the boiler will be in an unusual position, special requirements are needed, the current issue of BS6798 gives detailed guidance on these requirements.
A compartment used to enclose the boiler must be designed and constructed specifically for this purpose. An existing cupboard or compartment modified for the purpose may be used. Details of essential requirements for cupboard or compartment design are given in the current issue of BS6798.
The doorway opening should be of sufficient size to allow for easy removal of the boiler.
Where the boiler is fitted in a cupboard or compartment, permanent high and low level ventilation must be provided. The minimum ventilation areas required are given in Table 2.
1.15 Timber Frame Building
If the boiler is to be installed in a timber frame building it should be fitted in accordance with the Institute of Gas Engineers document IGE/UP/7/1998. If in doubt seek advice from the local gas undertaking or Hepworth Heating Ltd.
1.16 Heating System Controls
The heating system should have installed: a programmer and room thermostat controlling the boiler.
Thermostatic radiator valves maybe installed, however they must not be fitted in a room where the room thermostat is located.
Note: For further information, see The Building Regulations 1991 - Conservation of fuel and power, 1995 edition - Appendix G, table 4b.
co o o
500mm
Additional clearances may be required for installation
SIDE OR REAR FLUE 5mm
100mm
u
1
5mm
6mm
6mm
FRONT VIEW
65mm
MINIMUM CLEARANCES FROM WALLS, CEILING, FLOOR, CUPBOARD, WORKTOPS AND INFLAMMABLE MATERIALS Diagram 1.3
TABLE 2. COMPARTMENT AIR VENTS
VENTILATION REQUIREMENTS
HIGH LEVEL VENT AREA
LOW LEVEL
VENT AREA
VENTILATION FROM ROOM OR SPACE
cm2
in2
cm2
in2
99
15
99
15
VENTILATION FROM
OUTSIDE
50
7.5
50
7.5
CO
o
CO CO
7
221656D
ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Marine directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40