BOILER LOCATION
Clearances
The position of the boiler must be such that there is adequate space for servicing. The recommended clearances are: 40 mm either side of the boiler. 600 mm at the front of the boiler. 300 mm below the boiler.
Fixing jig
The fixing jig comprises three parts:
1) The connecting plate which allows the connec­tion and soundness testing of all the pipework be­fore the boiler is fitted and helps support the weight of the boiler.
2) The hook which supports the weight of the boiler.
3) The template which ensures the hook and con­necting plate are correctly fitted relative to one another.
• Place template on wall in required position, mak­ing allowances for the necessary clearances etc., see diagram 7.
Note: It is permissible to install the boiler with re­duced clearances at the bottom and sides of the boiler PROVIDING that adequate consideration is given for Servicing/Repairs at a later date. If any doubt exists, contact the Saunier Duval Technical Helpline 01773 828400.
• Mark the position of the holes for the hook and connecting plate.
• Drill, plug and fix the connecting plate and hook to the wall using suitable screws.
• Check that both the hook and connecting plate are level.
If the boiler is not installed immediately, protect the various couplings to prevent any ingress of foreign materials e.g. plaster, paint etc.
Terminal position
The minimum acceptable spacings from the ter­minal to obstructions and ventilation openings are shown in diagram 8.
Diagram 7
The boiler must be installed so that the terminal is
exposed to the external air.
Note: Under certain weather conditions the flue
may produce a plume of condensation, this is quite
normal.
If the terminal is fitted within 850mm of a plastic or painted gutter or 450m of painted eaves, an alu­minium shield of a minimum length of 750mm should be fitted to the underside of the gutter or painted surface.
Should any doubt exist as to the permissible posi­tion of the terminal, contact the Saunier Duval Technical Helpline 01773 828400.
Cupboard or compartment ventilation
The boiler can be fitted in a cupboard or compart­ment without need for permanent ventilation.
Minimum dimensions (in mm) for the positioning of flue terminals
A - Under a window.................................................300
B- Under an air vent................................................300
C- Under a gutter.......................................................75
D- Under a balcony.................................................300
E- From an adjacent window................................300
F- From an adjacent air vent.................................300
G- From vertical drain pipes or soil pipes..................75
H- From an external corner of the building..........300
I- From an internal corner of the building...........300
L- From the ground or from another floor............300
M- Between two terminals vertically....................1500
N- Between two terminals horizontally..................300
Diagram. 8
\
ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Marine directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28