BOILER CONNECTIONS
Gas Safety (Installation and Use) Regulations From left to right the fixing jig comprises : D- In your interests and that of gas safety, it is the law
that ALL gas appliances are installed and serviced
by a competent person in accordance with the
above regulations. Domestic hot water outlet. A- Heating return with isolating valve ( m ). E- Electrical connection box. B- Cold water inlet with isolating valve ( p ). F- Gas supply. C- Heating flow with isolating valve ( q ), drainscrew ( r ) and safety valve ( s ). Gas connection >
Diagram 5 •The supply from the governed gas meter must
be of adequate size to provide a constant inlet
working pressure of 20 mbar (8 in w.g.).
To avoid low gas pressure problems, it is recom-
mended that the gas supply is connected using 22
mm pipe.
•On completion, the gas installation must be
tested using the pressure drop method and purged
in accordance with the current issue of BS6891. >
Filters and washers:1 -Fibre washer 2 -Metal filter 5555 3 -Plastic filter 23113
4, 5 and 6 -Black graphite 34
57,557,5 25 33
m 123456 p r A q B s C D FE
Pla 041 PIPING SYSTEM INSTALLATION
•Heating system connections - Pipe diam 22 mm•Hot water system connections - Pipe diam 15 mm•Gas connection - Pipe diam 22 mm
•Safety valve discharge - Pipe diam 15 mm Water connection diagram 5 . Connect thesystem pipework to the boiler observing the cor-
rect flow and return format as shown in diagram 5.Safety valve discharge Connect the copper tails and isolating cocks sup-
plied, to the boiler, see WARNING. It must not discharge above an en-
trance or window or any type of public access
area.
Connect the safety valve discharge pipe to the
boiler, the discharge must be extended using not
less than 15 m o.d. pipe, to discharge in a visible
position outside the building, facing downward
preferably over a drain. The pipe must have a con-
tinuous fall and be routed to a position so that any
discharge of water, possibly boiling or steam, can-
not create any danger to persons, damage to
property or external electrical components and
wiring. Tighten all pipe connection joints.
Connect the safety valve discharge pipe to theboiler, the discharge must be extended using not
less than 15 m o.d. pipe, to discharge in a visible
position outside the building, facing downward
preferably over a drain. The pipe must have a con-
tinuous fall and be routed to a position so that any
discharge of water, possibly boiling or steam, can-
not create any danger to persons, damage to
property or external electrical components and
wiring. Tighten all pipe connection joints. 7 >