| | | ENVIRONMENTALLY FRIENDLY TECHNOLOGY | | SUPER ABSORPTION | | |
| | | |
| | | Examples of Installation | | |
| | | Cooling water blow system | | |
| | | |
| | | |
| | | A part of circulating water should be blown to prevent degrading of cooling water quality. Since concentration ratio is considered about 3 to 4 blowing, water quantity is calculated as follows. N : Concentration ratio generally N=3 M : Make-up water volume | | |
| | | |
| | | 3,024X1.85 (exhaust factor) 575 (Latent heat of evaporation at 40°C) generally W=0.2% of circulating water volume ., E+W+B | | |
| | | E : Evaporation loss W : Splashing loss B : Blow volume M : E+W+B | | |
| | | |
| | | |
| | | W+B | | |
| | | |
| | | by the above
| |
| | | |
| | | B | | 1 | | (E+W-NW) | | |
| | | |
| | | |
| | | |
| | | N-1 | | N-1 | | |
| | | |
| | | Figure 70. | | |
| | | |
| | | | | |
| | | Over Flow Make-up water is over supplied by manual valve for over-flow in cooling tower. | | |
| | | water | | |
| | | |
| | | |
| | | |
| | | Overflow | | |
| | | |
| | | Figure 71. | | |
| | | |
| | | Blow regulation valve | | |
| | | IOO I | | |
| | | Continuous Flow Certain amount of circulating water is blown by blow regulation valve. | | |
| | | |
| | | |
| | | "7*--7* | | |
| | | Make-up | | |
| | | |
| | | -M- | | |
| | | |
| | | |
| | | "LT | | |
| | | |
| | | Absorption chiller | | |
| | | |
| | | Higher than cooling water level | | |
| | | |
| | | |
| | | Figure 72. | | |
| | | |
| | | Solenoid valve | | |
| | | |
| | | | | |
| | | Make-up water | | |
| | | |
| | | Circulation pump is controlled by pressure switch. | | |
| | | |
| | | Pressure switch | | |
| | | |
| | | | | |
| | | |
| | | Solenoid valve t*t—i Make-up | | |
| | | Conductivity Meter+Solenoid Valve PH Meter+Solenoid Valve Blow is controlled. | | |
| | | -Xt | | |
| | | |
| | | Kitakyusyu Media Dome | | |
| | | |
| | | |
| | | Absorption chiller | | |
| | | |
| | | Sensor | | |
| | | |
| | | Overflow | | |
| | | |
| | | Kyoto Station Building 1 | | |
| | | |
| | | 96 | | 97 | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |