ENVIRONMENTALLY FRIENDLY TECHNOLOGY
SUPER ABSORPTION
Capacity ratings (DE and NE)
Capacity ratings (LE)
Table 14. Capacity factor (DE and NE)
Table 15. Capacity factor (LE)
Chilled water temperature
Cooling water inlet temperature (°C)
Outlet temp.
Inlet temp.
28
29
30
31
32
33
5.0
8.0
0.826
0.803
0.780
0.753
0.716
0.634
9.0
0.883
0.859
0.834
0.805
0.766
0.678
10.0
0.922
0.898
0.871
0.841
0.800
0.708
11.0
0.940
0.915
0.888
0.857
0.815
0.721
12.0
0.957
0.932
0.904
0.873
0.830
0.735
6.0
8.0
0.929
0.904
0.877
0.847
0.806
0.713
9.0
0.993
0.966
0.938
0.905
0.861
0.762
10.0
1.038
1.010
0.980
0.946
0.900
0.797
11.0
1.050
1.029
0.999
0.964
0.917
0.812
12.0
1.050
1.048
1.017
0.982
0.934
0.827
7.0
8.0
1.032
1.004
0.975
0.941
0.895
0.792
9.0
1.050
1.050
1.042
1.006
0.957
0.847
10.0
1.050
1.050
1.050
1.050
1.000
0.885
11.0
1.050
1.050
1.050
1.050
1.019
0.902
12.0
1.050
1.050
1.050
1.050
1.038
0.919
8.0
8.0
1.050
1.046
1.016
0.980
0.933
0.825
9.0
1.050
1.050
1.050
1.048
0.997
0.883
10.0
1.050
1.050
1.050
1.050
1.042
0.922
11.0
1.050
1.050
1.050
1.050
1.050
0.940
12.0
1.050
1.050
1.050
1.050
1.050
0.957
CHW AT = 4 deg
CHW AT = 5 deg
COW inlet
CHW outlet
Hot water outlet (°C)
Hot water outlet (°C)
80.0
81.0
82.0
83.0
84.0
85.0
80.0
81.0
82.0
83.0
84.0
85.0
28.0
6.0
1.046
1.092
1.137
1.183
1.228
1.272
1.066
1.112
1.158
1.204
1.249
1.294
7.0
1.111
1.156
1.202
1.247
1.291
1.300
1.132
1.178
1.223
1.268
1.300
1.300
8.0
1.176
1.221
1.266
1.300
1.300
1.300
1.198
1.243
1.288
1.300
1.300
1.300
29.0
6.0
0.934
0.980
1.027
1.073
1.119
1.164
0.953
1.000
1.047
1.093
1.139
1.185
7.0
0.999
1.046
1.092
1.137
1.182
1.227
1.019
1.066
1.112
1.158
1.204
1.249
8.0
1.065
1.111
1.156
1.201
1.246
1.291
1.085
1.132
1.177
1.223
1.268
1.300
30.0
6.0
0.820
0.868
0.915
0.962
1.008
1.055
0.837
0.886
0.934
0.981
1.028
1.074
7.0
0.886
0.934
0.980
1.027
1.073
1.118
0.905
0.953
1.000
1.047
1.093
1.139
8.0
0.953
0.999
1.046
1.091
1.137
1.182
0.972
1.019
1.066
1.112
1.158
1.203
31.0
6.0
0.703
0.753
0.802
0.850
0.897
0.944
0.719
0.769
0.819
0.867
0.915
0.963
7.0
0.771
0.820
0.868
0.915
0.962
1.008
0.788
0.837
0.886
0.934
0.981
1.028
8.0
0.838
0.886
0.934
0.980
1.027
1.073
0.856
0.905
0.953
1.000
1.047
1.093
32.0
6.0
0.583
0.635
0.685
0.735
0.784
0.832
0.597
0.649
0.701
0.751
0.801
0.849
7.0
0.653
0.703
0.753
0.802
0.850
0.897
0.668
0.719
0.770
0.819
0.867
0.915
8.0
0.722
0.771
0.820
0.868
0.915
0.962
0.738
0.788
0.838
0.886
0.934
0.981
CHW AT = 6 deg
COW inlet
CHW outlet
Hot water outlet (°C)
80.0
81.0
82.0
83.0
84.0
85.0
28.0
6.0
1.084
1.131
1.177
1.223
1.268
1.300
7.0
1.151
1.197
1.243
1.288
1.300
1.300
8.0
1.217
1.263
1.300
1.300
1.300
1.300
29.0
6.0
0.970
1.017
1.065
1.111
1.158
1.204
7.0
1.037
1.084
1.131
1.177
1.223
1.268
8.0
1.104
1.151
1.197
1.242
1.288
1.300
30.0
6.0
0.853
0.902
0.950
0.998
1.046
1.092
7.0
0.921
0.970
1.017
1.064
1.111
1.158
8.0
0.989
1.037
1.084
1.131
1.177
1.223
31.0
6.0
0.733
0.784
0.834
0.883
0.932
0.980
7.0
0.803
0.853
0.902
0.950
0.998
1.045
8.0
0.872
0.921
0.970
1.017
1.064
1.111
32.0
6.0
***
0.661
0.714
0.765
0.815
0.865
7.0
0.680
0.733
0.784
0.834
0.883
0.932
8.0
0.752
0.803
0.853
0.902
0.950
0.998
Note :
1) Cooling water temperrature difference : 6°C constant Hot water temperature difference : 5°C constant
2) The table is used only for the purpose of presumpting the capacity factor.
3) It requires proper consumption of hot water for required cooling capacity.
4) Please contact your SANYO representative, if your request is not indicated in the table.
5) " *** " mark means out of operation condition.
Note :
1) Cooling water temperature difference : 5.5°C constant
2) The table is used only for the purpose of presuming the capacity factor.
3) In DE model, the proper flow rate of hot water is required in case of heating mode. It requires proper consumption of hot water for required cooling capacity.
4) Please contact your SANYO representative, if your request is not indicated in the table.
Graph 11.
Cooling capacity and steam pressure (steam-fired chillers)
100
Graph 12. Partial load characteristics
110 100
90
80
70
<
Adoption of the controlling circulation amount of the solution
In order to have a stable and effective operation under the wide range of hot water temperature given, absorbent pump driven by an inverter con­trols the optimal operation. This control is that hot water is effectively utilized to regenerate the refrigerant instead of heating up the solution not attributed to the cooling capacity at the partial load.
Features;
1. To shorten the start-up period in time.
2. To prevent the excessive heat rejection to the cooling water system. Even if the heating amount of heat source becomes less, the unit can operate without fail by means of the procedure that the input is almost rejected to cooling water.
3.To improve COP at the partial load due to less input.
90
o
CO CL CO
o
O)
c
Ö
o
o
80
60
50
40
30
20
10 0
70
Q_
O
o
60
5 6 7
Supply steam pressure(Kg / cm2G)
Selection condition
1) Chilled water 12°C-»7°C
2) Cooling water 32°C->37.5°C
10
20
30
40 50 60
Load (%)
70
80
90 100
82
83
ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18