ENVIRONMENTALLY FRIENDLY TECHNOLOGY
SUPER ABSORPTION
Field wiring (LE)
Start/Stop sequence of auxiliary equipments Start
Figure 60. Typical electrical field connection diagram - Hot water-fired (LE)
Cooling water pump operates and then cooling tower fan operates
|| Start signal ||^ Chilled water pump operates
Operate air conditioners
Machine operates
Stop
To power source 3 Ph, 50/60HZ 380V, 400V, 415V, 440V
Cooling water pump stops and cooling tower fan stops
Stop signal
Chilled water pump stops
Chiller stops entirely
Diluted operation start
Stop air conditioners
For emergency stop signal
(Those terminals are connected by jumper)
Remove the jumper before using those terminals
co.E ■E a. Я E О о.
0) о.
¡I
For message signal
ш
о
о
о
СИ
СО
I-
см
со
о
Remote signal
The unit can be operated by the following five type signal.
(1 )Non-voltage normal open contact(A) for start & stop (DC24V 10mA).
:Wiring the terminal 330 and 333. (2)Non-voltage normal open contact(A) for start (DC24V 10mA).
:Wiring the terminal 330 and 333.
Non-voltage normal open contact(A) for stop (DC24V 10mA). :Wiring the terminal 331 and 333. (3)Non-voltage normal open contact(A) for start (DC24V 10mA). :Wiring the terminal 330 and 333.
Non-voltage normal close contact(B) for stop (DC24V 10mA).
:Wiring the terminal 331 and 333. (4)Continuous signal of DC/AC 24V for start & stop.
:Wiring the terminal 330 and 332.(Those terminals are non-polarity.) (5)Pulse signal of DC/AC 24V for start.
:Wiring the terminal 330 and 332.(Those terminals are non-polarity.)
Signal of DC/AC 24V for stop.
:Wiring the terminal 331 and 332.(Those terminals are non-polarity.)
Terminal strips in the control panel
171 171
Symbols L
51CH: 51CO
51CT :Cooling tower fan overcurrent relay 51H :Hot water pump overcurrent relay 23CO :Cooling tower fan thermostat
Indication lamp furniture
Chilled water pump overcurrent relay Cooling water pump overcurrent relay
171
A
Note
1 .Be sure to insert 23CO at the cooling water inlet side.
2.Be sure to wire the 52CH(interlock) between terminals 171 and 136.
З.Ве sure to wire the 52CO(interlock) between terminals 171 and 135.
4.Be sure to wire the chilled water pump control relay between terminals 302 and 303.
5.Be sure to wire the cooling water pump control relay between terminals 304 and 305.
6.Be sure to wire the hot water pump control relay between terminals 345 and 346.
Va
FT
FT
4Y 1
4Y 1
4Y
4Y 1
U
' то"
DC/AC 24V
у
(2)
(3)
(4)
78
79
ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Marine directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50