| Remote signal The unit can be operated by the following five type signal. (1 )Non-voltage normal open contact(A) for start & stop (DC24V 10mA). :Wiring the terminal 330 and 333. (2)Non-voltage normal open contact(A) for start (DC24V 10mA). :Wiring the terminal 330 and 333. Non-voltage normal open contact(A) for stop (DC24V 10mA). :Wiring the terminal 331 and 333. (3)Non-voltage normal open contact(A) for start (DC24V 10mA). :Wiring the terminal 330 and 333. Non-voltage normal close contact(B) for stop (DC24V 10mA). :Wiring the terminal 331 and 333. (4)Continuous signal of DC/AC 24V for start & stop. :Wiring the terminal 330 and 332.(Those terminals are non-polarity.) (5)Pulse signal of DC/AC 24V for start. :Wiring the terminal 330 and 332.(Those terminals are non-polarity.) Signal of DC/AC 24V for stop. :Wiring the terminal 331 and 332.(Those terminals are non-polarity.) Terminal strips in the control panel 171 171 171 |