| | | 1.Absorption chiller (1) Lower shell •Evaporator and refrigerant dispersion tray •Absorber and absorbent dispersion tray •Eliminators (2) Heat exchangers •High temperature (H.T.) heat exchanger •Low temperature (L.T.) heat exchanger (3) Upper shell •Low temperature (L.T.) generator •Condenser •Eliminators (4) High temperature (H.T.) generator (5) Heat reclaimer (6) Pumps •Absorbent pump(s) with isolating valves •Refrigerant pump with isolating valves •Purge pump (7) Control panel •CE marking (if requested according to the regulation). (8) Steam control valve •Control valve (electric type) •Shutoff valve | | 2.Factory test Tests below are carried out in the SANYO factory. •Check of external dimensions •Leak test (vacuum side) •Hydraulic pressure test for water and steam headers •Electric insulation resistance test •Dielectric breakdown test •Function test only for electric circuit and safety devices •Performance test (one unit is tested for performance when several units of the same model are ordered for one project) 3.Scope of supply of the purchaser (1) Unloading, transportation, and insurance depend on the individual sales contractor between your company and SANYO group. (2) Foundations with foundation bolts. (3) External chilled/water, cooling water, steam and drain piping work including various safety valves, isolating valves, etc. (4) Rupture disk, flange of rupture disk, bolts, nuts, piping work and tank, etc, if necessary. (5) External wiring and piping for the chillers including necessary parts. (6) Insulation for the chillers including necessary parts. | | |
| | | (7) Mating flanges, gaskets, bolts and nuts •Steam inlet nozzle flange for H.T. generator steam header. •Steam drain outlet nozzle flange. •Inlet/outlet nozzle flanges for chilled water, (evaporator) •Inlet/outlet nozzle flanges forcooling water, (absorber/condenser) (8) Finish painting of the chillers. (9) Cooling water inlet temperature control device. (10) Furnishing air-piping* and electric wiring/piping of steam control valve including necessary parts. (11) Various temp./press. gauges for steam and water lines. (12) Steam drain tank. (13) Cooling tower(s), chilled water pump(s) and cooling water pump(s) and its auxilialy accessaries. (14) Electric power supply (specified value). (15) Supply of chilled water, cooling water, steam and air* at rated conditions. (16) Necessary tools, workers and materials for installation and site test operation. | | |
| | | (9) Locally mounted controls and electric parts •Temperature sensor •H.T. generator solution level electrodes •H.T. generator pressure gauge (10) Purge unit •Storage tank •Ejector and liquid trap •Piping and various manual valves •Palladium cell with heater (11) Interconnecting piping and wiring (12) Initial charge •Absorbent (lithium bromide) •Refrigerant •Inhibitor (13) Painting •Main unit: rust preventive painted •Control panel: finish painted (14) Accessories •Operation manual : One set •Washer (for fixing foundation bolts): One set •Manometer: One piece •Gasket and sealant for rupture disk : One set (if requested according to the regulation). | | |