Text version of the page
Text version of the page
20 Minute Fire Protective Glazing Without Hose Stream Product Advantages > • SuperLite I shown in door manufacturer with SuperLite II-XL 45 minute sidelites in HM Framing Intertek/WHI Tested and Approved Sizes and Ratings > Fire RatingApplicationMax. CV AreaMax. CV WidthMax. CV HeightStops 20 minutesSteel Door2,687 sq. in.34” 77-7/8”5/8”20 minutesWood Door3,299 sq. in.36-1/8”91-5/16”5/8”20 minutesAluminum Door3,436 sq. in.36-3/4”95-1/2”5/8”20 minutesSteel, Wood and Aluminum Sidelites, Transoms5,760 sq. in.96”95-1/2”5/8”20 minutesSteel Windows5,760 sq. in.96”95-1/2”5/8” UL and Intertek/WHI Testing and Certifications > • GREEN Protection from radiant heat allows safe egress in corridors > Fire ProtectiveFire Resistive Contains smoke and flames, does not block radiant heatContains smoke, flames and modern blocks the passage of radiant heat
|