Stand
Group: Gefran

StringBoxQS - 2 Pages

and data logger

1. Assembly

JBXCOM JBX PWR-0-S4 JBX COM

Pin layout of components inside the string box

Figure 5.1 : Active String Box (JBX COM)

(1): 8 fuses, at the positive pole, (type gPV 12A1000V 10x38mm)

(2): 8 Hall effect current sensors

(3): Data processing card with RS485 port and analog and digital

I/O, see following section.

(4): Cable inlet for external sensors, M16 cable glands

(5): 8 string inputs for positive pole; 8 string inputs for negative pole

(6) copper bar 20 x 3 mm.

Bars + string current collectors (to connect to circuit breaker

boxes)

(7) mounting plate

List of connectors

The connectors listed below identify the digital and analog

inputs and serial communication on the active string box regula-

tion card.

Connectors

Terminal

Input

J10

1

(X1/8)

+24V Dc (power supply from JBX PWR circuit breaker box)

2

(X1/11)

GND (ground: OV)

J12 (-) J11

( + )

1

(D1)

Surge protection X1/7

2

(D2)

Circuit breaker

3

(D3)

Cover

4

(D4)

Free

5

(D5)

Free

6

(D6)

Current sensor setting

NB: J12: ground (OV); J11:+24V DC

J16

1

(Aí)

Radiation (IRR... sensor)

2

(A2)

Wind speed sensor (WIND...sensor)

3

(A3)

Free

4

(A4)

Free

5

(A5)

Ground (OV)

6

(A6)

Ground (OV)

J7

1

(Aí)

Ambient temperature (TEMP PT100 sensor)

2

(A2)

Ambient temperature (TEMP PT100 sensor)

3

(A3)

Ambient temperature (TEMP PT100 sensor)

J8

1

(Aí)

Regulation card temperature (Internal sensor included)

2

(A2)

Regulation card temperature (Internal sensor included)

3

(A3)

Regulation card temperature (Internal sensor included)

J9

1

(Aí)

Module temperature (Optional external sensor TEMP PT100)

2

(A2)

Module temperature (Optional external sensor TEMP PT100)

3

(A3)

Module temperature (Optional external sensor TEMP PT100)

NB: A=Analog; D = Digital

0PT-RS485-JBX

TB1 is the input

serial connec-

tion via RS485

port

Terminal

Description

A

Ain

B

B in

EQP

Ground

SH

Shield

0PT-RS485-JBX

TB2 is the

output serial

connection via

RS485 port

A

Août

B

Bout

EQP

Ground

SH

Shield

Fuse


 

Description

F1


 

Fuse 3.15A 250 Vac GL (slow-blow)

2.1 Layout of the active string box regulation card (JBX COM only)

SW2

jisrswi

J16

©

BSEDH,

HI- I^TH I-I I-

HHHHBH

S B B B B B

B g.

i H

mm

isl

BDBHD BÍ ra

i m

ses IH

a™ M 1

snsn-i I-I i-i i-i I-I i-i i H ¡ M

BB BB BB BB B| □ ||

- S -

I -ED ED

O ; aaa

0

»!

EE

E! m TE

ei UH

m CB

l

r^[H7]

BBB3

EBBE

O

O

SW2/SW1 = Rotary Switch

RS485

lm

E15EH

TB1 (IN) -TB2 (OUT)

Termination

120 ohm

S1

J7

J8

J9

x

m

m

ci

o.

O

3. Pin layout of components inside the circuit breaker box

(1): circuit breaker:

- TYPE S1 : 1x63A for coupling 1 string box to the circuit breaker

box

- TYPE S4: 2x63A for coupling 2 string boxes to the circuit

breaker box

Tripping coil

(-BC versions only)

Status contact

(-BC versions only)

(1a): Tripping coil and (1 b) status contact (-BC versions only)

(2): surge protection devices

(2a): fuse holders (Backup fuses on surge protection devices, 4A

1000V gR 10x38mm)

(3): 24 Vdc power supply for string boxes

(4): 3 terminals for:

-1 power cable for positive pole (OUTPUT for connection to

inverter)

-1 power cable for negative pole (OUTPUT for connection to

inverter)

-1 ground connection cable

(5): terminal board for signal cables

(6): Inlet for power cable (M32 cable gland) and ground cable (M20

cable gland)

(7): Power supply cable inlet (M20 cable gland)

(8): Signal cable inlet (M20 cable gland)

3.1 Power cables

IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIM

ES: The identifier may differ according to the version

IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIM

identifier

 

001

005 (black, -)

Negative cable to string box

002

006 (red, +)

Positive cable to string box

  

003 +

Positive output to inverter

004-

Negative output to inverter

StringBoxQS
  1. P. 1

  2. P. 2

    4. Safety precautions for installation Caution Caution Devices must be installed: • in places where they are protected from solar...