video corpo

FloorLine_Catalogue
24Pages

{{requestButtons}}

Catalog excerpts

FloorLine_Catalogue - 1

Convec Panels FloorLine product programme Product Description. . . . . . . . . . . . . . . . . . 2 Technical information / specifications . . . . . . . . . . 3 Design. . . . . . . . . . . . . . . . . . . . . . . . . 4 Dimensions. . . . . . . . . . . . . . . . . . . . . . 5 Installation. . . . . . . . . . . . . . . . . . . . . . . 5 Adjustments . . . . . . . . . . . . . . . . . . . . . . 6 Defining the connection side of a panel. . . . . . . . . 6 Applications. . . . . . . . . . . . . . . . . . . . . . 7 Panel variants - left . . . . . . . . . . . . . . . . . . . 8 Panel variants - right . . . . . . . . . . . . . . . . . . 9 Panel configuration I. . . . . . . . . . . . . . . . . 10 Panel configuration II. . . . . . . . . . . . . . . . . 11 Heat output I . . . . . . . . . . . . . . . . . . . . . 12 Heat output II. . . . . . . . . . . . . . . . . . . . . 13 Heat output III . . . . . . . . . . . . . . . . . . . . 14 Output/Fan speed - correction factors . . . . . . . . 15 Calculating pressure loss. . . . . . . . . . . . . . . 16 Controls. . . . . . . . . . . . . . . . . . . . . . . 17 CHR room thermostat. . . . . . . . . . . . . . . . . 18 System with BMS control. . . . . . . . . . . . . . . 20 CHM motor control . . . . . . . . . . . . . . . . . . 21 TDM power supply . . . . . . . . . . . . . . . . . . 22 Ordering FloorLine Panels. . . . . . . . . . . . . . . 23 Accessories. . . . . . . . . . . . . . . . . . . . . . 23 Placing orders. . . . . . . . . . . . . . . . . . . . .24

Open the catalog to page 1
FloorLine_Catalogue - 2

Product description Convec FloorLine Panel FloorLine is a compact panel for installing in heating applications in buildings. Applications Aesthetics and comfort are the keywords for FloorLine panels . The discreet panels enable you to create a room with harmony and balance regardless of the building style and purpose FloorLine can be used in district heating, oil/gas boilers, heating pumps or similar systems - as a primary source of heating or in combination with other heat emitters, e.g. floor heating. Technical information Heated system water is conducted through Convec panels by two...

Open the catalog to page 2
FloorLine_Catalogue - 4

Floor grating (aluminium) Moulding strip (Santoprene) Guide profile (aluminium) Finned pipe, flow (copper) Finned pipe, return (copper) Velcro tape Flexible pipes Motor Fan (aluminium) Bearing block (aluminium/brass) Fan coupling (plastic) Pipe fixture (aluminium) Installation profile (aluminium) Panel end (aluminium) CHM motor control print Motor connection Connection cable and terminals Adjustment blocks (aluminium)

Open the catalog to page 4
FloorLine_Catalogue - 5

Dimensions Product dimensions Installation measurements Convec FloorLine panels measure 135 mm in width and 59 mm in height. Installation ducts must meet certain measurements if an optimal finish is to be achieved. The duct should be long enough to allow room for thermal expansion. The length of the duct can be calculated as follows: 1. For panels shorter than 6000 mm, the length equals the total panel length + 5 mm. 2. For panels longer than 6000 mm, the channels should extend a further 1 mm per meter panel exceeding 6 meters. The panels are equipped with integrated adjustment screws,...

Open the catalog to page 5
FloorLine_Catalogue - 6

Adjustments Height adjustment Floor support The panel can be adjusted 10 mm in height. Installation ducts must not be deeper than 73 mm to ensure adequate, stable support of the panel. It is very important that all adjustment screws are in contact with the base of the installation channel to ensure panel stability. The height of the panel including grating can be adjusted to align with the floor covering. The edges of the installation channel must be straight and “sharp” to ensure a good finish and correct securement of the grating. A carpet strip can be used to achieve a correct finish...

Open the catalog to page 6
FloorLine_Catalogue - 7

One-pipe system Two-pipe system FloorLine panels can be used in a traditional two-pipe system or connected in series of lengths of up to 15000 mm with the potential for intermediary pipe work. The same panel string can be used for several rooms as the panel output is controlled by fan speed rather than flow. FloorLine panels can also be used in a one-pipe system . However, this will create a different output than stated in this product sheet. Contact MEINERTZ for further information regarding one pipe systems.

Open the catalog to page 7
FloorLine_Catalogue - 8

Panel variants - left FloorLine is available in six different panel variants, which Each panel variant can be supplied with left or right differ according to use and panel connections. connection. Stand-alone panels (S & ST) S-panel: Stand-alone panel unit with connection to system supply, incl. return bend with air vent. ST-panel: Stand-alone panel unit with connection to system supply, incl . return valve with TWA-A thermal actuator and air vent C-panel with connection to system supply and nipples for direct panel extension with other panels. Kv E-panel for use with direct connection...

Open the catalog to page 8
FloorLine_Catalogue - 9

Panel variants - right The different panel variants can be combined together. Left or right connection must be requested in orders. See panel codes for orders on page 25. NOTE! The stated Kv values are used when calculating the total pressure loss over one or more panels. See guidance on page 16. Kv S-panel: Stand-alone panel unit with connection to system supply, incl. return bend with air vent. ST-panel: Stand-alone panel unit with connection to system supply, incl. return valve with TWA-A thermal actuator and air vent. Connection panel (C) C-panel with connection to system supply and...

Open the catalog to page 9
FloorLine_Catalogue - 10

Panel configuration I Panel length up to 3500 mm (stand-alone solution) If possible, panels of up to 3500 mm should be constructed as a stand-alone solution. In principle, this is carried out like a traditional radiator installation, connected to a two-pipe system. 60 cm of a panel unit is used for motor, connections and fittings. To ensure maximum output per meter of panel, it is recommended using panel units as long as possible. Example Stand-alone panel (S or ST) Panel length 3500 mm to 7000 mm (connection of 2 panels) Panels longer than 3500 mm are created by connecting a connection...

Open the catalog to page 10

All Meinertz A/S catalogs and technical brochures

  1. SkyLine

    1 Pages

  2. SKA-Line

    1 Pages

  3. L-Line

    1 Pages

  4. Finned Tubes

    16 Pages

Archived catalogs