System Devices
Line coupler
20
1
2
3
Ref.-No.
KNX line coupler 2142 REG
ETS-product family: System component
Product type: Line coupler
Series embodiment (SE)-device (2 units)
Function: The coupler connects two KNX lines together and guarantees electrical isolation between these lines.
The exact function of the device is defined by the address and the selected application.
Line coupler: Connection of a line and a main line with or without a filter function.
The coupler is physically assigned to the secondary line (here: line).
Backbone coupler: Connection of a main line and a backbone line with or without a filter function.
The coupler is physically assigned to the secondary line (here: main line).
Amplifier: Preparation and repetition of telegrams on a line, no filter function. Subdivision of a line into max. 4 independent line segments
= max. 3 line repeaters per line connected in parallel. A separate power supply including a choke is required for each line segment.
RUN
HL
UL
DIAG
HL UL
main line line
red
black
red
black
Technical data:
Power supply: 21 – 32 V DC via the primary line
Power consumption
Primary line: approx. 6 mA
Secondary line: approx. 8 mA
Connection: KNX connecting terminal for primary and secondary line
Ambient temperature: –5°C ... +45°C
Storage temperature: –25°C ... +70°C
Protection: IP 20 in accordance with EN 60529
Protection class: III in accordance with EN 61140
Note:
• The filter tables are stored in a non-volatile memory (flash). This means that the stored addresses are not lost after a bus voltage failure
and that no internal backup battery is required.
4
-
P. 1
-
P. 17
Technical data:Input supplyingVoltage: 161 V – 264 V AC, 50-60 HzOperation with 2 lines of 110 V mains possible !176 V – 270 V DC (for emergency... -
P. 18
System DevicesPower Supply123Ref.-No.KNX uninterruptedpower supply 640 mA USV 640 MAETS-product family: System componentProduct type: Power supplySeries... -
P. 19
Technical data:SupplyingVoltage: 230 V AC, +10/–15 %, 45 ... 65 HzPower consumption: < 60 VAPower loss: < 10 WKNX OutputNumber 1 line with... -
P. 20
System DevicesLead-gel battery123Ref.-No.Lead-gel battery BGA 12 AH12 V DC, 12 AHIn combination with the uninterrupted KNX power supply, the lead-gel battery... -
P. 21
Technical data for: KSB 4 KSE 2Cable: 4-wire cable 2-wire cableDiameter: 0,75 mm2 0,75 mm2Length: 2 m 2 mColoursBattery connection: red (12 V battery)... -
P. 22
-
P. 23
CommissioningDuring commissioning of a project with area/line couplers, the following sequence of operations should be observed:1. Project design of the... -
P. 24
System DevicesBus coupling unit (BCU)1Ref.-No.KNX bus coupling unitwith supporting frame 2070 Ufor flush mountingETS-product family: System componentsProduct... -
P. 25
System DevicesLogic module123Ref.-No.KNX logic module 2145 REGXETS-product family: ControllerProduct type: ControllerSeries embodiment (SE)-device (2 units)The... -
P. 26
System DevicesSerial data interface1Ref.-No.KNX serial data interface 2131 REGETS-product family: CommunicationProduct type: SerialSeries embodiment (SE)-device... -
P. 27
System DevicesData-interface123CBARef.-No.Data-interfaceETS-product family: CommunicationProduct type: Serialivory 2130white CD 2130 WWblue CD 2130 BLbrown... -
P. 28
-
P. 29
-
P. 30
-
P. 40
-
P. 50
-
P. 60
-
P. 70
-
P. 80
-
P. 90
-
P. 100
-
P. 200