Stand
Group: Jung

KNX 2007 - 283 Pages

Technical data:
Supplying
Voltage: 230 V AC, +10/–15 %, 45 ... 65 Hz
Power consumption: < 60 VA
Power loss: < 10 W
KNX Output
Number 1 line with integrated choke
Output voltage: 30 V DC, +1/–2 V, SELV
Nominal current: 640 mA, permanent short circuit proof
Permanent short-circuit current: < 1.5 A
Mains failure bridgeover time: 200 ms (without connected battery)
Battery type: lead-gel battery
Number: max. 2 in parallel
Rated voltage: recommended 1 Ah, 7 Ah, 12 Ah, 17 Ah
Rated battery charge current: 650 mA, at battery capacity > 5 Ah
150 mA, at battery capacity < 5 Ah
Temperature control: temperature-controlled charging voltage via temperature sensor
Floating contact
Rated voltage: 230 V AC resp. 12/24 V AC/DC
Max. switching current: 6 A AC resp. 4 A DC
Min. switching current: 100 mA (at U < 30 V AC/DC)
Connections
Change-over contact: 3 screw terminals each
Battery and temperatur sensor: 2 screw terminals each
Screw terminals: 0.2 ... 4 mm2
Operation temperature: –5°C ... +45°C
4
17
Uninterrupted power supply 640 mA Ref.-No. USV 640 MA

KNX 2007
  1. P. 1

  2. P. 14

    System DevicesPower Supply123Ref.-No.KNX power supply 640 mA 2002 REGETS-product family: System componentsProduct type: Power supplySeries embodiment (SE)-device...
  3. P. 15

    Technical data:Input supplyingVoltage: 161 V – 264 V AC, 50-60 HzOperation with 2 lines of 110 V mains possible !176 V – 270 V DC (for emergency...
  4. P. 16

    System DevicesPower Supply123Ref.-No.KNX power supply 320 mA 2005 REGETS-product family: System componentsProduct type: Power supplySeries embodiment (SE)-device...
  5. P. 17

    Technical data:Input supplyingVoltage: 161 V – 264 V AC, 50-60 HzOperation with 2 lines of 110 V mains possible !176 V – 270 V DC (for emergency...
  6. P. 18

    System DevicesPower Supply123Ref.-No.KNX uninterruptedpower supply 640 mA USV 640 MAETS-product family: System componentProduct type: Power supplySeries...
  7. P. 19

  8. P. 20

    System DevicesLead-gel battery123Ref.-No.Lead-gel battery BGA 12 AH12 V DC, 12 AHIn combination with the uninterrupted KNX power supply, the lead-gel battery...
  9. P. 21

    Technical data for: KSB 4 KSE 2Cable: 4-wire cable 2-wire cableDiameter: 0,75 mm2 0,75 mm2Length: 2 m 2 mColoursBattery connection: red (12 V battery)...
  10. P. 22

    System DevicesLine coupler20123Ref.-No.KNX line coupler 2142 REGETS-product family: System componentProduct type: Line couplerSeries embodiment (SE)-device...
  11. P. 23

    CommissioningDuring commissioning of a project with area/line couplers, the following sequence of operations should be observed:1. Project design of the...
  12. P. 24

    System DevicesBus coupling unit (BCU)1Ref.-No.KNX bus coupling unitwith supporting frame 2070 Ufor flush mountingETS-product family: System componentsProduct...
  13. P. 30

  14. P. 40

  15. P. 50

  16. P. 60

  17. P. 70

  18. P. 80

  19. P. 90

  20. P. 100

  21. P. 200

Text version

All Jung catalogues and technical brochures

  1. Anthracite

    8 Pages

    En
  2. JUNG Bus

    32 Pages

    En
  3. KNX Catalogue

    171 Pages

    En
  4. JUNG CATALOGUE

    536 Pages

    En
  5. News items 2012

    29 Pages

    En

Archived catalogues

  1. Facility pilot

    3 Pages

    En
  2. The JUNG Radio

    5 Pages

    En
  3. KNX 2007 - Small

    32 Pages

    En
  4. LS Ranges

    8 Pages

    En
  5. Hotel

    14 Pages

    En
  6. Chrome

    8 Pages

    En
  7. Anthracite

    8 Pages

    En
  8. Aluminium

    5 Pages

    En
  9. Radio Management

    72 Pages

    En
  10. Sensor modules

    5 Pages

    En
  11. Export 23

    544 Pages

    En
  12. Saving energy

    7 Pages

    En
  13. KNX HOME

    5 Pages

    En