KNX 2007 - 283 Pages
Switch actuator Ref.-No. 2131.16 UP/2132.6 UP
147
4 Technical data
KNX supply
Cable type: YY 6 x 6.0 mm; red: bus (+) / black: bus (–)
Voltage: 21 – 32 V DC SELV
Power consumption: typically 150 mW
Connection: approx. 33 cm ready-made; connecting terminal (0.6 – 0.8 mm)
Input
Number: 2 (depending on parameterization either as extension inputs for push-button local control
of the actuator or as independent binary inputs acting on the bus)
Cable type: YY 6 x 0.6 mm
green: extension input 1
white: reference potential (com)
yellow: extension input 2
brown: reference potential (com)
Cable length: approx. 33 cm ready-made, extendible to 5 m max.
Scanning voltage: approx. – 19 V DC referred to “com”; continuous signal
Loop resistance: max. 2 kOhm for safe “1” signal detection (rising edge)
Output, for 2131.16 UP
Number: 1
Cable type: 2 x H05 V-K 2.5 mm2 with ferrules
Cable length: approx. 20 cm ready-made
Switch type: make-contact, potential-free (ì-contact) bistable
Switching voltage: 230 V AC; 50/60 Hz
Max. switching current: 16 A
Max inrush current: 400 A, 20 ms
Switching capacity: Incandescent lamps 2.500 W (at 100.000 switching operations)
HV halogen lamps 2.200 W (at 100.000 switching operations)
LV halogen lamps
inductive transformers 1.000 VA
electronic transformers 1.000 W
capacitive loads 230 V AC, 10 A switching current, max. 105 ìF
Output, for 2132.6 UP
Number: 2 (with common phase connection “L”)
Cable type: 3 x H05 V-K 2.5 mm2 with ferrules
Cable length: approx. 20 cm ready-made
Switch type: make-contact, potential-free (ì-contact) bistable
Switching voltage: 230 V AC; 50/60 Hz
Max. switching current: 6 A for each output
Max inrush current: 120 A, 20 ms
Switching capacity: Incandescent lamps 1.200 W (at 25.000 switching operations)
HV halogen lamps 1.200 W (at 25.000 switching operations)
LV halogen lamps
inductive transformers 500 VA
electronic transformers 500 W
capacitive loads 230 V AC, 6 A switching current, max. 14 ìF
Protection: IP 20
Safety class: III
Mark of approval: KNX
Ambient temperature: –5°C ... +45°C
Storage/transport temperature: –25°C ... +70°C (storage above +45°C results in shorter lifetime)
Mounting position: any
Minimum spacings: none
Fastening: e.g. placing into deep flush-mounting box (Ø 60 mm x 60 mm)
-
P. 1
-
P. 144
Time Switch16 channel123Ref.-No.KNX year time switch, 16 channel 2156 REGETS-product family: Time switchProduct type: TimerSeries embodiment (SE)-device... -
P. 145
143Year time switch, 16 channel Ref.-No. 2156 REG4 Technical dataKNX SupplyVoltage: 21 – 32 V DC (SELV)Power consumption: < 150 mWConnection:... -
P. 146
144Year time switch, 16 channel Ref.-No. 2156 REG45Obelisk memory chipFor the transfer of data, only the Obelisk memory card 64K (supplied with the 16-channel... -
P. 147
Time SwitchAccessories123Ref.-No.Software setfor OBELISK memory card 2154 PCThe programming set consists out of an OBELISK memory card for the data transmission... -
P. 148
ActuatorsSwitching – Flush mounted123Prog.EIB+ / RDEIB- / BK1 / GNcom / WH2 / YEcom / BNL L‘BN BNL1L2L3NRef.-No.KNX switch actuator, flush... -
P. 149
-
P. 150
Switch actuator Ref.-No. 2131.16 UP/2132.6 UP1484 Note:• Never connect the mains voltage (230 V) or other external voltages to the extension inputs.Connecting... -
P. 151
Switch actuator Ref.-No. 2131.16 UP/2132.6 UP149Description of software applicationObjects for the output of 2131.16 UPObject Name Function Type Flag0... -
P. 152
ActuatorsSwitching 2-gang123Ref.-No.KNX switch actuator,2-gang, 16 A 2132.16 REG (will be replaced by 2302.16 RECHM)ETS-product family: OutputProduct type:... -
P. 153
Description of software application– Switching of 2 independent channels.– Hand operation possible.– Outputs can be adjusted as make... -
P. 154
ActuatorsSwitching 6-gang123Ref.-No.KNX switch actuator,6-gang, 6 A 2136.6 REGETS-product family: OutputProduct type: 6-gang binary outputSeries embodiment... -
P. 160
-
P. 170
-
P. 180
-
P. 190
-
P. 200