KNX 2007 - 283 Pages
140
5 Description of application 1. Scene with switching, value priority
On each of the 4 channels you can choose between the following telegram types:
– switching telegram (1 Bit)
– priority telegram (2 Bit)
– brightness value or value telegram (8 Bit)
Cyclic transmitting can be selected for each channel, this is controlled by a common timer.
By choice, a switching, priority or value telegram (command) can be sent on each of the channels 1 to 3.
Additionally a scene with up to 4 types of telegram (command) can be implemented on the 4th channel.
During a switching time, up to four telegrams (commands) can be transmitted via bus on channel 4 (end of a working day: switch off main lighting,
drive shutter down, lower ambient temperature, lock external doors).
These additional objects can be a 1 or 2 Bit or a 1 Byte type.
In addition the possibility exists of suppressing the time switch progam of the clock by control of a blocking object via the bus.
Objects
Number of addresses: 10
Number of assignments: 10
Communication objects: 8
Object Name Function Type Flag
0 Channel 1 Send telegram switch 1 Bit R, T
1 Channel 2 Send telegram switch 1 Bit R, T
2 Channel 3 Send telegram switch 1 Bit R, T
3 Channel 4 Send telegram switch 1 Bit R, T
7 Block Reception telegram block 1 Bit W, T
max. extension with four switch messages (commands) on channel 4:
0 Channel 1 Send telegram switch 1 Bit R, T
1 Channel 2 Send telegram switch 1 Bit R, T
2 Channel 3 Send telegram switch 1 Bit R, T
3 Channel 4 object 1 Send telegram switch 1 Bit R, T
4 Channel 4 object 2 Send telegram switch 1 Bit R, T
5 Channel 4 object 3 Send telegram switch 1 Bit R, T
6 Channel 4 object 4 Send telegram switch 1 Bit R, T
7 Block Reception telegram block 1 Bit W, T
Description of application 2. Switching, value, send time and date
On each of the 4 channels you can choose between the following telegram types:
– switching telegram (1 Bit)
– priority telegram (2 Bit)
– brightness value or value telegram (8 Bit)
Cyclic transmitting can be selected for each channel, this is controlled by a common timer.
By choice, a switching, priority or value telegram (command) can be sent on each of the channels 1 to 3.
Date and time-of-day can be transmitted each minute, each hour, each day or only on request.
Date and time-of-day are always transmitted together.
Objects
Number of addresses: 8
Number of assignments: 8
Communication objects: 7
Object Name Function Type Flag
0 Channel 1 Send telegram switch 1 Bit R, T
1 Channel 2 Send telegram switch 1 Bit R, T
2 Channel 3 Send telegram switch 1 Bit R, T
3 Channel 4 Send telegram switch 1 Bit R, T
4 Time Send time 3 Byte R, T
5 Date Send date 3 Byte R, T
6 Time demand Ask for time + date 1 Bit W, T
Time switch, 4 channel Ref.-No. 2154 REG
-
P. 1
-
P. 137
Analog outputExtension Module123(A)(C)(B)(D)K1 K2 K3 K4+UsGNDAC 230 V50/60 Hz AC 24 VUs GND K1 K2 K3 K4 GND Us24V DCBereich:Linie:TLNNr.:24V DCKNX/EIBState•... -
P. 138
Time Switch2 channel123Ref.-No.KNX time switch, 2 channel 2152 REGETS-product family: Time switchProduct type: TimerSeries embodiment (SE)-device (2 units)1364... -
P. 139
1375 Description of application 2 scenes with switching, value, priorityOn each of the 2 channels you can choose between the following telegram types:–... -
P. 140
Time Switch4 channel123Ref.-No.KNX time switch, 4 channel 2154 REGETS-product family: Time switchProduct type: TimerSeries embodiment (SE)-device (6 units)138The... -
P. 141
4 Technical data:SupplyVoltage: 24 V DC (+6 V / –4 V)Power consumption: max. 150 mWwith DCF: 230 V for integrated power supplyConnection: KNX connection... -
P. 142
-
P. 143
Time switch, 4 channel Ref.-No. 2154 REG1415 Description of application 3. Switching, value, temperature, receive time and dateOn each of the 4 channels... -
P. 144
Time Switch16 channel123Ref.-No.KNX year time switch, 16 channel 2156 REGETS-product family: Time switchProduct type: TimerSeries embodiment (SE)-device... -
P. 145
143Year time switch, 16 channel Ref.-No. 2156 REG4 Technical dataKNX SupplyVoltage: 21 – 32 V DC (SELV)Power consumption: < 150 mWConnection:... -
P. 146
144Year time switch, 16 channel Ref.-No. 2156 REG45Obelisk memory chipFor the transfer of data, only the Obelisk memory card 64K (supplied with the 16-channel... -
P. 147
Time SwitchAccessories123Ref.-No.Software setfor OBELISK memory card 2154 PCThe programming set consists out of an OBELISK memory card for the data transmission... -
P. 148
-
P. 149
-
P. 150
-
P. 160
-
P. 170
-
P. 180
-
P. 190
-
P. 200