KNX 2007 - 283 Pages
Analog output
Extension Module
1
2
3
(A)
(C)
(B)
(D)
K1 K2 K3 K4
+Us
GND
AC 230 V
50/60 Hz AC 24 V
Us GND K1 K2 K3 K4 GND Us
24V DC
Bereich:
Linie:
TLNNr.:
24V DC
KNX/EIB
State
• AC 24 V
0-10V DC
0(4)-20mA
Us: 24V DC
+ max. 100mA
• AC 24 V
WSSV10
AC 24 V
Ref.-No.
Analog output module 2204.01 REG AM
(No KNX device)
Series embodiment (SE)-device (4 units)
The analog output extension module exceeds a KNX Analog output, 2204.01 REGA by four additional sensor outputs.
The analog output extension module offers four analog outputs which can be software parameterised for one of the following ranges.
Outputs not used can be deactivated.
Voltage signals: 0 ... 1 V DC 0 ... 10 V DC
Current signals: 0 ... 20 mA DC 4 ... 20 mA DC
The analog output extension module needs an external 24 V power supply, WSSV 10.
135
4 Technical data
Supply voltage: 24 V AC ± 10 %
Current consumption: max. 170 mA
Power consumption at system plug: typ. 150 mW
Connection: Screw terminals: 0.5 mm2 to 4 mm2, single-wire
0.34 mm2 to 4 mm2, fine-wire (without ferrule)
0.14 mm2 to 2.5 mm2, fine-wire (incl. ferrule)
Connection to KNX device: 6-pole system plug
Sensor input: 4 x analog
Output signal load: voltage signal: 1 kÙ
current signal: 100 Ù
Output current: voltage signal: max. 10 mA per channel
current signal: max. 20 mA per channel
Connection: Screw terminals: 0.5 mm2 to 4 mm2, single-wire
0.34 mm2 to 4 mm2, fine-wire (without ferrule)
0.14 mm2 to 2.5 mm2, fine-wire (incl. ferrule)
Protection: IP 20
Safety class: III
Ambient temperature: –5°C ... +45°C
Storage/transport temperature: –25°C ... +70°C (storage above +45°C reduces the lifetime)
-
P. 1
-
P. 132
Weather station Ref.-No. WS 10 ..130123Ref.-No.Temperature sensor WS 10 T(No KNX device)The temperature sensor is used for the measuring and evaluation... -
P. 133
Analog output4-gang123Ref.-No.KNX analog output 2204.01 REGAETS-product family: OutputProduct type: 4-gang analog outputSeries embodiment (SE)-device (4... -
P. 134
132Analog output Ref.-No. 2204.01 REG A4 Technical dataKNX SupplyVoltage: 21 – 32 V DC (SELV)Power consumption: typically 150 mWConnection: Bus terminal... -
P. 135
133Analog output Ref.-No. 2204.01 REG A4 Technical dataModule connectionNumber: 1Connection: 6-pole system connector for extension moduleAnalog outputsNumber:... -
P. 136
134Analog output Ref.-No. 2204.01 REG A5 ApplicationObjectsNumber of addresses: 200Number of assignments: 200Communication objects: 058Object Function... -
P. 137
-
P. 138
Time Switch2 channel123Ref.-No.KNX time switch, 2 channel 2152 REGETS-product family: Time switchProduct type: TimerSeries embodiment (SE)-device (2 units)1364... -
P. 139
1375 Description of application 2 scenes with switching, value, priorityOn each of the 2 channels you can choose between the following telegram types:–... -
P. 140
Time Switch4 channel123Ref.-No.KNX time switch, 4 channel 2154 REGETS-product family: Time switchProduct type: TimerSeries embodiment (SE)-device (6 units)138The... -
P. 141
4 Technical data:SupplyVoltage: 24 V DC (+6 V / –4 V)Power consumption: max. 150 mWwith DCF: 230 V for integrated power supplyConnection: KNX connection... -
P. 142
1405 Description of application 1. Scene with switching, value priorityOn each of the 4 channels you can choose between the following telegram types:–... -
P. 150
-
P. 160
-
P. 170
-
P. 180
-
P. 190
-
P. 200