Weather station Ref.-No. 2224 REG W
4 Technical data
KNX Supply
Voltage: 21 – 32 V DC (SELV)
Power consumption: typically 150 mW
Connection: Bus terminal (KNX Typ 5.1)
External supply, voltage: 24 V AC ± 10 %
Current consumption: 250 mA max.
Power consumption: max. 4 VA
Connection: Screw terminals: 0.5 mm2 to 4 mm2, single-wire
0.34 mm2 to 4 mm2, fine-wire (without ferrule)
0.14 mm2 to 2.5 mm2, fine-wire (incl. ferrule)
Stud torque max. 0.8 nM
Response to voltage failure
Bus voltage only: No communication with KNX.
Operating voltage only: No communication with KNX, no feeding of the measuring sensors.
Bus and mains/operating voltage: No communication with KNX, no feeding of the measuring sensors.
Response to recovery
Bus voltage only: No communication with KNX, no feeding of the measuring sensors.
Operating voltage only: No communication with KNX.
Bus and mains/operating voltage: Communication with KNX according to initialization parameters.
Module connection
Number: 2
Connection: 6-pole system connector for analog input extension module
4-pole system connector for combi sensor
Analog inputs
Number: 4
Signal voltage/current: 0 ... 1 V DC, 0 ... 10 V DC, 0 ... 20 mA DC or 4 ... 20 mA DC,
depending on parameterization
Input resistance: Voltage measurement: approx. 18 kÙ
Current measurement: approx. 100 Ù
Connection: Screw terminals: 0.5 mm2 to 4 mm2, single-wire
0.34 mm2 to 4 mm2, fine-wire (without ferrule)
0.14 mm2 to 2.5 mm2, fine-wire (incl. ferrule)
Protection: IP 20
Safety class: III
Mark of approval: KNX/VDE
Ambient temperature: –5°C ... +45°C
Storage/transport temperature: –25°C ... +70°C (storage above +45°C reduces the lifetime)
Mounting position: any
Minimum distances: none
Fastening: on DIN rail 35 x 7.5
3 Layout: Dimensions:
Status LED functions:
Controls:
(A)
(C)
(B)
(D)
(E)
K1 K2 K3 K4
+Us
GND
KNX
AC 230 V~ AC 24 V
Us GND K1 K2 K3 K4 GND Us
24V DC
Bereich:
Linie:
TLNNr.:
24V DC
KNX/EIB
State
• AC 24 V
0-10V DC
0(4)-20mA
Us: 24V DC
+ max. 100mA
WSSV10
(F)
Width: 72 mm (4 units)
Height: 90 mm
Depth: 58 mm
LED off no power supply
LED orange/on modul scan by weather station
LED orange/flashing slowly combi sensor module scan (waiting for assignment)
LED orange/flasing fast DIN rail extension module (REG) parameterization
LED red/flashing slowly fault: undervoltage at module connection / US short-circuited
LED red/flashing fast fault: no project, parameterization error
LED green/flashing slowly module scan complete, projecting OK
parameter download into modules
LED green/flashing fast parameter download to modules
LED green/on initialization process terminated, everything OK
slow flashing: approx. 1 Hz
fast flashing: approx. 2 Hz
A: Programming key
B: Programming LED
C: Status LED, three-colour
(red, orange, green)
D: Measuring sensors
E: Module connector, 6-pole
F: Combi sensor connector, 4-pole
-
P. 1
-
P. 117
1155 Notes to software application:• Bus voltage recoveryYou can specify for each input what response is to be made upon bus voltage recovery. If... -
P. 118
Analog Input4-gang123Ref.-No.KNX analog input 2214 REGAETS-product family: InputProduct type: 4-gang analog inputSeries embodiment (SE)-device (4 units)The... -
P. 119
117Analog input Ref.-No. 2214 REGA4 Technical dataKNX SupplyVoltage: 21 – 32 V DC (SELV)Power consumption: typically 150 mWConnection: Bus terminal... -
P. 120
118Analog input Ref.-No. 2214 REGA44Wiring diagram for connection of an analog input moduleRemarks on the hardwarePlease observe the following basic rules... -
P. 121
Analog InputWeather Station123Ref.-No.KNX weather station 2224 REG WETS-product family: InputProduct type: 4-gang analog inputSeries embodiment (SE)-device... -
P. 122
-
P. 123
121Weather station Ref.-No. 2224 REG W4 Technical dataMeasuring sensor power supply outputsNumber: 2Rated voltage: 24 V DC ±10 %Rated current: 100... -
P. 124
122Weather station Ref.-No. 2224 REG W45Remarks on the hardwarePlease observe the following basic rules when installing the analog input extension module:•... -
P. 125
Building orientationThe automatic shading control starts at the moment when at least one of the three brightness sensors indicates that the luminance has... -
P. 126
Analog InputExtension Module123(A)(C)(B)(D)(E)K1 K2 K3 K4+UsGNDKNX/EIBAC 230 V~50/60 Hz AC 24 VUs GND K1 K2 K3 K4 GND Us24V DCBereich:Linie:TLNNr.:24V... -
P. 127
Analog InputPower Supply123AC 230 V~50/60 Hz AC 24 V~AC 24 V~• AC 24 V • AC 24 VAC 230 V~L NLNRef.-No.Power supply WSSV 10(No KNX device)Series... -
P. 128
-
P. 129
-
P. 130
-
P. 140
-
P. 150
-
P. 160
-
P. 170
-
P. 180
-
P. 190
-
P. 200