Surface mounted versionTwo part supply and installation
General modular componentconcept All QuietVent ELS fan units (VE..)
fit in surface and flush mounted
casings. That simplifies design,
installation and storing. Casing
and fan unit are delivered separately in cartons, so that
the casing can be fitted while
the fan is still in its carton. Explanation of symbols forpages 48-53 Without fire rating Connection on common
main riser up to two floors. When exhausting to the outside through one main
duct there are no restrictions on
floor levels in reference to fire protection regulations. Connection
of several levels is allowed. No complicated duct system The fire protection casing enables the shortest and most
direct duct runs. This guarantees a fast installation with minimal material. Fire resistance class K 60-18017 up to 8floors Fire rated 60minutes,
inaccordance with DIN4102, regulated for ventilation
systems–with common main duct–in buildings with . >
1) Connection of 1 or 2 casings perfloor is possible. Minimum installation expenditure The QuietVent ELS installation is
so easy. Large electrical cable storage
speeds installation.
Elongated fixing holes for easy
leveling. Fire resistance class
K 90-18017 Fire rated 90minutes,in accordance with DIN4102, regulated for ventilationsystems
–with common main duct–in buildings with up to 20 floors . >
1) Connection of 1 or 2 casings perfloor up to 20 floors is possible. Unrestricted installation >
A B
Fire resistance classK 90-18017 in kitchen with more than 2floors. The surface mounted QuietVentELS casings can be installed
with the outlet duct in any corner allowing easy fixing close
to wall or ceiling. With the faciavertical the installation looks thesame no matter which corner
the outlet is on. >
125 Fire rated 90minutes,
inaccordance with DIN4102, regulated for ventilation systems–for aeration of apartment kitchen –with common main duct
–in buildings >
115 260 115 1) Connection of 1 or 2 casings perfloor up to 20 floors is possible. >
1) Recommendation without obligation basedon the building supervisory regulations fortechnical fire protection standards on
ventilation units. The decisive local construction regulations as well as the special
information of the respective certificates andapprovals must be considered. C D
Recommended use in type ofroom: >
115 Bathroom >
++ 270 125 125 Toilet Kitchen >
Note: For second room ventilationa unit with·V=100m³/his recommended. Note: UK building regulations
require an air flow of·V=216 m³/h for kitchens. 47 >