Specification –Robust constructions for operation under rough conditions.–Corrosion resistant casingsmade from galvanised steel. –Very safe in operation throughblack heat, enclosed heating elememts made from stainlesssteel.–Built-in overheat protection(except EHL).–Completely maintenance freefor continuous operation. –Total enclosed fan motors,protection to IP 54, with tropical protection of windings.–Contact safety to DIN EN 294 (except EHL).–Delivered ready to connect inshipment carton.

Selection chart and technical information

Operation Models KHL Pure air intake unit to warm up the fresh air for flush mounted wall installation. Example 1: Main heating Room volume: 600 m Running costs Specific operation of electric heaters can be cost effective. HELIOS fan heaters can be – controled by timer thermostats – an advantageous solution. Calculation of heat requirements Models EHL The required heat power is dependent on following: 1.Desired room temperature or difference to outside temperature. 2.Room size in m Example 2: Additional heating Compact fan heater unit forvarious applications e.g. installation in ventilation ducts and OEM machines. Existing heating is not enough in winter. The top requirement should be covered with an electric heater. Room volume: 600 m

3

Desired temperature: +20 °C. Lowest outside temp.:–15 °C. Insulation: Good. That results in a temperature increase of 35 °C (see 1. column).Depending on the room volumeand the insulation the result is the required heat power. ln this case: 15 kW. In rooms of every kind e.g. in workshops, stores, offices. Models STH and TH Transitional or additional heating Full heating For large rooms that are only used periodical for longer intervals e.g. in assembly rooms, churches,exhibition halls and others. Site heating Preferably models STH and TH for room heating as well as space drying. Frost protection heating To prevent freezing temperatures in frost sensitive rooms e.g. stores,waterworks, pump and gate stations. Drying and condensationprevention

3

.Desired temperature Increase: 10 °C. Insulation: poor(table values with*).In column 1 from value 10 °Cto go horizontal to the right untill the room size of 600 m of rooms of every kind in commercialand industrial applications.

3

withpoor insulation is to be reached. The power to be installed amounts 5 kW.

3

. 3.Quality of room or building insulation. 4.Use of the unit as full oradditional heating. The table below is based on experiences for room heating – not valid for ventilation. It shows values for good and poor insulation.

Desired temperaturerequired heat power in kWincrease

∆ t

3 kW5 kW10 kW15 kW20 kW30 kW Room volume in m

3

Room volume in m

3

Room volume in m

3

Room volume in m

3

Room volume in m

3

Room volume in m

3

40 °C75* – 100 m

3

125* – 175 m

3

250* – 350 m

3

375* – 500 m

3

575* – 800 m

3

850* – 1200 m

3

35 °C90* – 120 m

3

150* – 200 m

3

300* – 400 m

3

450* – 600 m

3

690* – 900 m

3

1000* – 1300 m

3

30 °C100* – 150 m

3

175* – 250 m

3

350* – 500 m

3

500* – 750 m

3

800* – 1150 m

3

1200* – 1700 m

3

25 °C120* – 180 m

3

200* – 300 m

3

400* – 600 m

3

600* – 900 m

3

920* – 1380 m

3

1550* – 2000 m

3

20 °C150* – 210 m

3

250* – 350 m

3

500* – 700 m

3

750* – 1050 m

3

1150* – 1600 m

3

1750* – 2400 m

3

15 °C200* – 280 m

3

340* – 470 m

3

680* – 940 m

3

1000* – 1400 m

3

1550* – 2150 m

3

2300* – 3200 m

3

10 °C300* – 420 m

3

500* – 700 m

3

1000* – 1400 m

3

1500* – 2100 m

3

2300* – 3200 m

3

3500* – 4800 m

3

5 °C600* – 800 m

3

1000* – 1400 m

3

2000* – 2800 m

3

3000* – 4200 m

3

4600* – 6400 m

3

6900* – 9600 m

3

The figures with * are valid for a poor room insulation. Approximately double the heat power is required for fast heating on occasional operation thus the warmup time is reduced.

33

ArchiExpo's Virtual Library: PDF Catalogues | Documentation | Brochures | Manuals | Directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
page 28 p.28
page 29 p.29
page 30 p.30
page 31 p.31
page 32 p.32
page 33 p.33
page 34 p.34
page 35 p.35
page 36 p.36
page 37 p.37
page 38 p.38
page 39 p.39
page 40 p.40
page 41 p.41
page 42 p.42
page 43 p.43
page 44 p.44
page 45 p.45
page 46 p.46
page 47 p.47
page 48 p.48
page 49 p.49
page 50 p.50
Pages:
1-50
51-100
101-150
151-200
201-250
251-300
pdf-page pdf ae En 2008-10-41-11