Fire protection shutter K 90-DIN 18017BAE
BAEApproval No. Z-41.3-614Maintenance free. >
NEW!
Special features >
Pressure drop and sound levels Pa V·(m 3 /h) Fire rating 90 minutes K 90-DIN18017 Installation examples >
Spiral ducting Maintenance free. In-line installation Insertion in spiral ducting without additional mounting frame. The element is to be installed
through simple insertion (e.g. in
spiral ducting) and to be fixedtogether with the duct in thewall.Suitable for installation in
both directions, independent
from air flow direction. Installation Shutter to prevent fire and smoke
transmission. Suitable for in-stallation in ventilation shafts and ducting with required fire re-
sistance class K 90-DIN 18017.
Suitable for insertion into spiral
ducting or for wall installationwith mounting sleeve EH (accessory). Installation allowed outside theshaft wall. Function When the surroundingtemperature of +72 °C is exeeded, the integrated fusible link releases the spring
loaded semicircle blades. Two
safety bows bar the shutter blades. Certified rating For air flow in both directions,suitable for extract and intakesystems. This unit has been tested for use in ventilation systems to
DIN 18017 by the DIBt (German institute for Bautechnik, Berlin).
Approval No. Z-41.3-614. Low resistance even with highair flows. Wall installation With mounting sleeve (accessory) in walls of brick, thermolite block or plaster panel, shaft
partition walls in F 90, F 60 and F 30... or systemproofed walls with more than 40 mm thickness.
Suitable for installation in both
directions, independent from air
flow direction. >
Insertion in standard spiral ducting Connection to cooker hoods without motor allowed. Noiseless. Also for commercial applications,e.g.
kitchens,
toilets and smallstaff rooms. Specification Cylindrical duct sleeve with butterfly shutter and integrated fusable link. >
Installation with mounting sleeve or spiral ducting and inserted intake/extract element
(not fire resistant) Contents One shutter in plastic bag. Installation and setting The certificate contains exactdata relating to operation andinstallation. Available onrequest. If the mounting sleeve is to beused for wall installation, it mustbe plastered in with mortar class II or III DIN1053 or other approved material. >
Order data Accessory: Type Ref.Dim. in mmWeight Mounting Ref.Dimensions in mm BAEEH >
No.ø ABin kg sleeve No.ø Cø DEF BAE 80 262478360.13 BAE 100 262598420.19 EH 100 26391019892120 BAE 125 2626123470.27 EH 125 264012812392120 BAE 160 2627158640.41 EH 160 2641162158114140 BAE 200 2628197700.57 EH 200 2642201197120150 Dimensions in mm see table 266 >