video corpo cad

ELIS DUO
16Pages

{{requestButtons}}

Catalog excerpts

ELIS DUO - 2

• Heating capacity table 14

Open the catalog to page 2
ELIS DUO - 3

GENERAL CHARACTERISTICS Max. range (m) Heating capacity*** (kW) Colour**** Casing ELiS DUO /EL ELiS DUO/ EL Curtain Heater 2,5 m* 8 m** 14,7 6,8 7,3 3,3 silver - grey sheet steel + plastic * Vertical range of isothermal stream (at velocity boundary equal to 2 m/s). ** Horizontal range of isothermal stream (at velocity boundary equal to 0,5 m/s). *** At inlet/outlet water temperature 90/70oC, inlet air temperature 10oC. **** On customer’s demand, unit is available in all colours of RAL palette. Curtain-Heater ELiS DUO is an 2-in-1 unit, designed to operate indoors. Part of air curtain has a...

Open the catalog to page 3
ELIS DUO - 4

WATER HEAT EXCHANGER High-performance heat exchanger made of copper and aluminium. ADJUSTABLE AIR STREAM Air blades installed in the outlet of heater section direct air into the occupied area. Variable angle of blades ensures adjustment of air barrier to the door opening area. QUIET OPERATION OF FANS Centrifugal fans are placed in a casing made of light, durable and sound-absorbing material. Quiet operation and low power consumption in relation to their performance (efficiency). CONTROL SYSTEM WITH BMS PROTOCOLS Advanced control system makes it possible to connect and control units by BMS...

Open the catalog to page 4
ELIS DUO - 5

TECHNICAL DATA Fan Max. air flow - air curtain [ m3/h] Max. air flow - fan heater [ m3/h] Power supply [V/Hz] Max. current consumption [A] IP Max. acoustic pressure level* [dB(A)] Max. air stream range - air curtain** [m] Max. air stream range - fan heater*** [m] Fan step Revs (RPM) [1/min] Air curtain air flow [m3/h] Current consumption by air curtain fans [A] Power consumption by air curtain fans [W] Fan heater air flow [m3/h] Current consumption by fan heater fans [A] Power consumption by fan heater fans [W] Total air stream [m3/h] Total current consumption [A] Total power consumption...

Open the catalog to page 5
ELIS DUO - 6

Air curtain range defines the maximum height of installation. For ELiS DUO it is 2,5 m - at this height the fan heater section has an 8 m range. 1st step 2nd step 3rd step distance from the outlet [m] 1st step 2nd step 3rd step distance from the outlet [m]

Open the catalog to page 6
ELIS DUO - 7

RECOMMENDED INSTALLATION DISTANCES Two ways of console installation. ELiS curtains can be installed using pins. CORRECT INSTALLATION The key to the correct operation of the unit is to ensure air barrier on entire door opening space. ELiS DUO can be linked, so covering wider door openings doesn’t make any problem. Incorrect installation may result in heat loss during winter and chill loss in the air-conditioned rooms during summer.

Open the catalog to page 7
ELIS DUO - 8

CONTROL SYSTEMS three-way valve with actuator AF system in ELiS DUO unit controls both air streams. If it is needed the two- or three-way valve can be connected to this system. Both curtain and heater sections can be controlled in various configurations: • DUO1 program - is used in the case of curtain’s connection with door switch and TA speed controller or TS speed controller with room thermostat. • DUO2 program - is used in the case of curtain’s connection with door switch and TS speed controller with room thermostat. In this configuration door switch is the overriding controller. In both...

Open the catalog to page 8
ELIS DUO - 9

IDLE SPEED When the doors are closed, curtain’s fans are operating with lower speed. This solution eliminates air barrier’s delay, which is caused by the time needed to switch on the fans. A) Doors are closed standby mode. B) Doors are opening rapid start and speed of fans is rising. C) Doors are closing - speed of fans is still higher. D) Doors are closed - back to standby mode. AIR CURTAIN’S SWITCH OFF DELAY TIME It the case when doors in building keep opening and closing constantly, AF system makes possible to set time delay of the switching off the curtain or returning it to the idle...

Open the catalog to page 9
ELIS DUO - 10

BMS PROGRAMMING AF system enables to connect the unit to BMS (Building Management System). It is equipped with communication protocol MODBUS in RTU mode. Communication takes place at a speed of 9600 (without parity control, 1 bit of stop, 8 bits of data, RS485). It is possible to set up to 255 addresses. Thanks to BMS you can get the access to control a 3-step fan speed regulation and valve or electric heaters operation. Control of the operation via BMS does not exclude the control by manual controllers. In this case, unit operates according to the last set signal. MODBUS Register Address...

Open the catalog to page 10
ELIS DUO - 11

CONTROL SYSTEM COMPONENTS Technical data SRQ2d-1/2 two-way valve 1/2” with actuator Protection degree: IP20 Power supply: 200-240 V 50/60 Hz Max. water temperature: +93°C Max. operating pressure: 1,6 MPa Kvs: 1/2” - 3,0 Installation: on water outlet pipe Opening/closing time: 18s/5s Dimensions (HxWxL): 1/2” - 108x86x66 mm SRQ3d-1/2 three-way valve 1/2” with actuator Protection degree: IP20 Power supply: 200-240 V 50/60 Hz Max. water temperature: +93°C Max. operating pressure: 2,0 MPa Kvs: 1/2” - 3,4 Installation: on water inlet pipe Opening/closing time: 18s/5s Dimensions (HxWxL): 1/2” -...

Open the catalog to page 11
ELIS DUO - 12

CONNECTION DIAGRAMS AF SYSTEM - DUO1 operation program allows: • to control curtain section by door switch DCe or DCm and TA fan speed controller • to control heater section by TS fan speed controller with room thermostat. power supply CONFIGURATION 2 AF SYSTEM - DUO2 operation program allows: • to control curtain section by door switch DCe or DCm and TS fan speed controller with room thermostat • to control heater section by TS fan speed controller with room thermostat. power supply

Open the catalog to page 12
ELIS DUO - 13

CONNECTION DIAGRAMS AF SYSTEM - UNITS CHAINING It is possible to connect more ELiS DUO units to each other. All of the control system components must to be connected to the first device (MASTER). Control signals are transmitted to the other units (SLAVE) by CW wire (with RJ12 plugs) - it is possible to connect up to 5 units in this way. power supply power supply power supply

Open the catalog to page 13
ELIS DUO - 14

HEATING CAPACITIES *maximum water flow rate and water pressure drop. For operating parameters concerning other water temperatures, please contact Sales Office. V PT Tp1 Tp2 air flow heating capacity inlet air temperature outlet air temperature inlet water temperature outlet water temperature water flow rate in heat exchanger water pressure drop in heat exchanger ELiS DUO EL Air curtain section 1st step Fan heater section 3rd step Air curtain - Fan heater 3rd step * given parameters at inlet air temperature 10oC