video corpo

VULCAN MEDIUM - 3 / 4 Pages

versions and configurations

LOW TEMPERATURE:

> - Low temperature: not required (Standard)

>B Water low temperature

ENERGY RECOVERY:

> - Energy recovery: not required (Standard)

> D Partial energy recovery

O

O

I

CO

o

o

o

<

m

5

a

technical data

Size-WBAN 82 122 162 202 262 302

Unit for radiant panels

A7/W35

       

► Heating capacity

kW

28,6

40,7

51,7

70,2

82,8

98,4

Total power input

kW

7,60

10,9

13,4

18,1

21,3

25,9

COP (EN 14511:2011)

 

3,75

3,73

3,86

3,87

3,89

3,80

COP (EN 14511:2008) (1)

 

4,11

4,13

4,13

4,12

4,10

4,13

A2/W35

       

► Heating capacity

kW

25,5

36,0

45,3

60,6

73,1

86,5

Total power input

kW

7,45

10,4

12,8

17,4

20,7

25,1

COP (EN 14511:2011)

 

3,42

3,46

3,53

3,48

3,53

3,45

A-5/W35

       

► Heating capacity

kW

19,4

273

34,1

45,7

55,2

64,9

Total power input

kW

730

10,1

12,4

16,6

19,9

24,2

COP (EN 14511:2011)

 

2,65

2,71

2,74

2,75

2,78

2,68

A35/W18

       

► Cooling capacity

kW

33,3

46,7

61,5

86,5

97,4

123

Total power input

kW

9,07

13,2

16,6

23,8

26,8

33,8

EER(EN 14511:2011)

 

3,68

3,53

3,71

3,63

3,64

3,62

Waterflowrate(UtilitySide) (2)

l/s

1,62

2,27

3,00

4,23

4,76

5,98

Useful pump discharge head (2)

kPa

133

139

127

138

131

158

Standard power supply

V

400/3/50+N

400/3/50+N

400/3/50+N

400/3/50+N

400/3/50+N

400/3/50+N

Sound Pressure Level (10m)

dB(A)

47

48

50

50

52

53

Terminal units

A7/W45

       

► Heating capacity

kW

28,6

40,2

52,9

69,2

84,6

98,2

Total power input

kW

9,03

12,7

16,1

21,1

26,2

30,2

COP (EN 14511:2011)

 

3,16

3,16

3,29

3,29

3,22

3,25

A2/W45

       

► Heating capacity

kW

25,5

35,8

47,6

61,3

75,0

86,4

Total power input

kW

8,48

12,0

15,1

20,2

25,2

28,6

COP (EN 14511:2011)

 

3,01

2,97

3,14

3,03

2,97

3,02

A-5/W45

       

► Heating capacity

kW

19,5

274

36,3

46,7

56,5

64,9

Total power input

kW

8,29

11,6

14,5

19,3

24,0

273

COP (EN 14511:2011)

 

2,35

2,36

2,51

2,42

2,36

2,38

A35/W7

       

► Cooling capacity

kW

25,6

35,9

471

65,9

78,6

94,6

Total power input

kW

8,48

12,2

15,3

21,4

25,3

30,8

EER(EN 14511:2011)

 

3,02

2,95

3,07

3,08

3,11

3,07

ESEER

 

3,21

3,19

3,40

3,47

3,68

3,40

Waterflowrate(UtilitySide) (3)

l/s

1,20

1,70

2,20

3,10

3,70

4,50

Useful pump discharge head (3)

kPa

158

164

149

169

159

183

Standard power supply

V

400/3/50+N

400/3/50+N

400/3/50+N

400/3/50+N

400/3/50+N

400/3/50+N

Sound Pressure Level (10m)

dB(A)

47

48

50

50

52

53

Radiators

A7/W55

       

► Heating capacity

kW

28,6

39,8

53,6

68,9

86,3

98,5

Total power input

kW

10,3

14,4

19,4

25,7

30,8

35,3

COP (EN 14511:2011)

 

2,77

2,76

2,77

2,68

2,80

2,79

A2/W55

       

► Heating capacity

kW

25,7

35,6

48,1

52,0

76,7

86,9

Total power input

kW

10,1

14,0

18,6

23,4

29,6

33,8

COP (EN 14511:2011)

 

2,55

2,55

2,59

2,22

2,59

2,57

A-5/W55

       

► Heating capacity

kW

22,0

30,7

41,3

48,8

64,4

73,2

Total power input

kW

9,78

13,5

176

22,8

28,2

32,0

COP (EN 14511:2011)

 

2,25

2,27

2,35

2,14

2,28

2,29

Min air inlet temperature (W.B.)

°C

-15

-15

-15

-15

-15

-15

Max water outlet temperature

°C

60

60

60

60

60

60

ID COP (EN 14511:2008) performance coefficient in heating mode. Ratio between heating capacity

;3;

supplied and abs<

ium of the p

oower absort

Data referrec

exchanger air

Data referrec

sd power in accordance with EN 14511:2008, The absorbed power is the

:isorbed by the compressor + electric auxiliary circuit + percentage of

ne pump to prevent pressure drops inside the unit

following conditions : Internal exchanger water = 23/1 S^C; Externa

ollowing conditions : Internal exchanger water = 12/7°C; Externa

exchanger air return 35°C

Performances according to EN 14511:201'

A7/W35 internal exchanger water 30/35°C;external air temperature 7°C D.B./ 6°C W.B.

A2/W35 internal exchanger water 30/35°C; external air temperature 2"C D.B./ 1,1°C W.B

A-5/W35 internal exchanger water 30/35°C; external air temperature -5°C D.B./ -5,4°C W.B.

A7/W45 internal exchanger water40/45°C; external air temperature 7°C D.B./6°C W.B.

A2/W45 internal exchanger water40/45°C; external air temperature 2°C D.B./ 1/TC W.B.

A-5/W45 internal exchanger water 40/45°C; external air temperature -5°C D.B./-5,4°C W.B.

A7/W55 internal exchanger water 50/55°C; external air temperature 7°C D.B./6°C W.B.

A2/W55 internal exchanger water 50/55°C; external air temperature 2°C D.B./ 1/TC W.B.

A-5/W55 internal exchanger water 50/55°C; external air temperature -5°C D.B./-5,4°C W.B

A35/W18 internal exchanger water 23/18°C; external air temperature 35°C

A35/W7 internal exchanger water 12/7°C; external air temperature 35°C

©EUVET

VULCAN MEDIUM
  1. P. 1

    ELFOEnergy Vulcan MediumWBANHigh temperature heat pump: able toproduce hot water at 60°C even when theoutdoor temperature falls to -10°C.The...
  2. P. 2

    ELFOSystemWBAN82÷302Reversible heat pumpAir cooledOutdoor installationCapacity from 28,6 to 98,4 kWELFOEnergy Vulcan MediumELFOEnergy Vulcan Medium...
  3. P. 3

  4. P. 4

    accessories E >» I/) o >CCCA Copper/aluminium condenser coil with acrylic lining >CLSE >...
Text version

All Clivet catalogues and technical brochures

  1. SMARTPACK

    4 Pages

    En
  2. CLIVETPACK-FFA

    2 Pages

    En
  3. WDAT-SL2

    2 Pages

    En
  4. WDATB

    2 Pages

    En
  5. MDE3

    2 Pages

    En
  6. SPINCHILLER

    2 Pages

    En
  7. GAIA Acqua

    4 Pages

    En
  8. EQV-X

    2 Pages

    En
  9. WDH-HE

    2 Pages

    En
  10. SPINSAVER

    2 Pages

    En
  11. ELFORoom2

    2 Pages

    En
  12. ELFOFresh2

    2 Pages

    En
  13. GAIA Aria

    2 Pages

    En
  14. Zephir2

    2 Pages

    En
  15. MultiSystem

    27 Pages

    En
  16. LargeCOM System

    49 Pages

    En
  17. Company Profile

    28 Pages

    En

Archived catalogues

  1. LightCom System

    4 Pages

    En
  2. HIGHdronic

    12 Pages

    En